Allen-Bradley 857 Quick Start Manual page 19

Protection system for feeder and motor protection
Hide thumbs Also See for 857:
Table of Contents

Advertisement

Table 8 - Terminal X8 Model 857-3C8
No:
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Table 9 - Terminal X6
Available only when arc flash option is selected.
No:
1
2
3
4
5
6
7
(1) Arc sensor itself is polarity free.
Rockwell Automation Publication 857-QS001B-EN-P - April 2017
Mounting and Wiring Instructions
Symbol
Description
DI21
Trip relay 14
DI22
Trip relay 14
COM1
Trip relay 13
DI23
Trip relay 13
DI24
Trip relay 12
COM2
Trip relay 12
DI25
Trip relay 11
DI26
Trip relay 11
COM3
Trip relay 10
DI27
Trip relay 10
DI28
Trip relay 9
COM4
Trip relay 9
T8
Trip relay 8 / Digital input 32
T8
Trip relay 8 / Digital input 32
T7
Trip relay 7 / Digital input 31
T7
Trip relay 7 / Digital input 31
T6
Trip relay 6 / Digital input 30
T6
Trip relay 6 / Digital input 30
T5
Trip relay 5 / Digital input 29
T5
Trip relay 5 / Digital input 29
Symbol
Description
BI
External arc light input
BO
Arc light output
COM
Common connector of arc light I/O
S1>+
Arc sensor 1, positive connector
S1>–
Arc sensor 1, negative connector
S2>+
Arc sensor 2, positive connector
S2>–
Arc sensor 2, negative connector
Chapter 2
(1)
(1)
(1)
(1)
19