Allen-Bradley 16 Axis PCI SERCOS Installation Instructions Manual page 23

Interface card
Table of Contents

Advertisement

Card Status Using the OK Indicator
If the OK
Then the card status is:
LED
displays:
Off
The card is not operating.
Flashing
The card has passed internal
green light
diagnostics, but has not
established active
communications.
Solid green
light
Flashing
red light
Solid red
A potential nonrecoverable
light
fault has occurred.
The SERCOS Ring Status LED
The SERCOS Ring Status LED shows the status of the SERCOS ring.
Data is being exchanged.
The card is in the normal
operating state.
A major recoverable
failure has occurred.
An NVS update is in
progress.
16 Axis PCI SERCOS interface Card
Take this action:
Apply power.
Verify the card is completely
inserted into the PCI slot.
None, if you have not
configured the card.
None. The card is ready for action.
If an NVS update is in progress,
complete the NVS update.
If an NVS update is not in progress:
Reboot
Reboot the card.
If the solid red persists, replace
the card.
Publication 1784-IN041A-EN-P – June 2003
23

Advertisement

Table of Contents
loading