7 Configuration
[2-74]
Heat rejection cancellation setting temperature.
If the unit internal temperature is higher than the zero energy
dissipation setting temperature, the zero energy dissipation control
will start and cool down the unit.
[2-74]
0
77°F (25°C)
1
80.6°F (27°C)
2
84.2°F (29°C)
3 (default)
87.8°F (31°C)
4
91.4°F (33°C)
5
95°F (35°C)
6
98.6°F (37°C)
7
102.2°F (39°C)
Heat pump lockout
[2-16]
Heat pump lockout 1.
Heat pump is always locked out when this setting is ON. If the indoor fan control needs to be changed or the auto-backup function is required,
refer to the setting [2-37].
[2-16]
0 (default)
OFF
1
ON
[2-37]
Heat pump lockout 2.
Heat pump is locked out when this setting and an external input to ABC terminal are made.
[2-37]
0 (default)
OFF
1
Mode 1
2
Mode 2
Mode
Description
Mode 1
Lockout is controlled by an
external input to ABC
terminal
Mode 2
(*1)
*1. For a heater which does not need airflow
*2. Depends on the indoor unit field setting 12(22)-3.
Automatic lockout
When this setting is made, the auto-backup function will
automatically be activated. This will allow the auxiliary or secondary
heat source to be automatically activated in the event of a system
failure related to outside units.
Error codes capable of auto-backup are listed in the table below.
Please be aware that the error codes that are not listed do not auto-
backup in order to protect the unit.
Installation manual
40
Description
Heat pump lockout 1
Heat pump lockout 2
Shorted
Field setting
between
2-37: Mode 1
A-C
B-C
2-37: Mode 2
A-C
B-C
[2-81]
Cooling comfort setting.
This setting is used in conjunction with setting [2-8].
[2-81]
0
Eco
1 (default)
Mild
2
Quick
3
Powerful
[2-82]
Heating comfort setting.
This setting is used in conjunction with setting [2-9].
[2-82]
0
Eco
1 (default)
Mild
2
Quick
3
Powerful
Actions
Heating Thermo-on
Heater
Fan
ON
ON (H/L)
LL
OFF
Error code (Auto
backup possible)
A3
Drain level control system abnormality
E3
Actuation of high pressure switch
E4
Actuation of low pressure sensor
E5
Inverter compressor motor lock
E9
Electronic expansion valve coil abnormality
F3
Discharge pipe temperature abnormality
F9
Branch Selector unit electronic expansion valve
abnormality
VRV W T-Series water-cooled system air conditioner
Cooling comfort setting
Heating comfort setting
Heating Thermo-off
Heater
Fan
OFF
LL (*2)
OFF
LL (*2)
OFF
Error contents
RWEQ96~432TAYCU
4P540122-1B – 2018.11