CAUTION
• Install the indoor and outdoor units, power supply wiring and
connecting wires at least 3.3 ft (1 m) away from televisions or
radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 3.3 ft (1 m) may
not be sufficient enough to eliminate the noise.)
• In the case of the installation of the wireless remote controller,
the transmission distance of the wireless remote controller may
be shortened if the room has a fluorescent light of electronic
lighting type (i.e., an inverter or rapid-start fluorescent light).
Keep the distance between the receiver and the fluorescent
light as far as possible.
(2) Use suspension bolts to install the indoor unit. Check that
the place of installation withstands the weight of the indoor
unit. Secure the suspension bolts with proper beams if nec-
essary.
Ceiling
Floor surface
• The H1 dimension indicates the
height of the product.
• Determine the H2 dimension by
maintaining a downward slope of
at least 1/100 as specified in
"7. DRAIN PIPING WORK".
4.

PREPARATIONS BEFORE INSTALLATION

(1) Check the positional relationship between the ceiling open-
ing hole and the suspension bolt of the unit. [unit: in. (mm)]
• For the maintenance, inspection, and other servicing
purposes of the control box and drain pump, prepare one
of the following service spaces.
1. Inspection hatch 1 (17-3/4 × 17-3/4 (450 × 450)) for
the control box and a minimum space of 12 in. (300)
for the lower part of the product. (Refer to Fig. 2-2)
2. Inspection hatch 1 (17-3/4 × 17-3/4 (450 × 450)) for
the control box and inspection hatch 2 for the lower
part of the product (see arrow view A-1). (Refer to
Fig. 2-3)
3. Inspection hatch 3 for the lower part of the product
and the lower part of the control box (see arrow view
A-2). (Refer to Fig. 2-3)
5
[unit: in. (mm)]
Min. 28 (700)
(service space)
[Required installation place]
The dimensions indicate the
minimum required space of
installation.
Fig. 2-1
Case 1
Inspection hatch
28 (700)
24-13/16 (631)
(Suspension bolt pitch)
Air outlet
Bottom of unit
Suspension bolt (× 4)
Case 2, 3
Inspection hatch
(Ceiling opening)
Inspection hatch
A
Inspection hatch 1
(17-3/4×17-3/4) (450×450)
Control box
Inspection
hatch 2
28 (700)
(Same as the
indoor unit
size or more)
Arrow view A-1
• Determine the H3
dimension by maintaining a
downward slope of at least
1/100 as specified in
18 • 24 • 30 type
"7. DRAIN PIPING WORK".
36 • 42 • 48 type
[unit: in. (mm)]
Control box
Ceiling
Inspection hatch 1
(17-3/4×17-3/4)
(450×450)
Control box
Air inlet
Fig. 2-2
Control box
Ceiling
Inspection hatch 3
(Same as the indoor
unit size +12 (300) or more)
Control box
28 (700)
Arrow view A-2
Fig. 2-3
[unit: in. (mm)]
Model
B
C
D
40
40-7/8
52
(1000)
(1038)
(1300)
56
56-5/8
68
(1400)
(1438)
(1700)