Field Setting - Daikin FBQ24PVJU Installation Manual

Ceiling-mounted duct type
Hide thumbs Also See for FBQ24PVJU:
Table of Contents

Advertisement

[ PRECAUTIONS ]
1. Do not ground the equipment on gas pipes, water pipes or
lightning rods, or crossground with telephones.
Improper grounding could result in electric shock.
2. The remote controller wiring (P
wiring (F
and F
) have no polarity.
1
2
10-3 CONTROL BY 2 REMOTE CONTROLLERS (Con-
trolling 1 indoor unit by 2 remote controllers)
• When using 2 remote controllers, one must be set to "MAIN"
and the other to "SUB".
Main/sub changeover
• Refer to the installation manual supplied with the remote con-
troller.
Wiring method
(1) Remove the control box cover.
(2) Add the remote controller 2 (SUB) to the terminal block for
remote controller (P
, P
) in the control box. (There is no
1
2
polarity.)
P
P
F
F
T
T
1
2
1
2
1
REMOTE
TRANSMISSION
FORCED
OFF
CONTRL
WIRING
Remote
controller 1
(MAIN)
Fig. 11
10-4 REMOTE CONTROL (FORCED OFF AND ON/
OFF OPERATION)
(1) Wire specifications and how to perform wiring
• Connect input lines from the outside to the terminals T
and T
on the terminal block (6P) for remote controller to
2
achieve remote control.
• See "11. FIELD SETTING" for details on operation.
P
P
F
1
1
2
REMOTE
TRANSMISSION
CONTRL
WIRING
Fig. 12
Wire specification
Sheathed vinyl cord or 2 core cable
Gauge
AWG18 – 16 (0.75-1.25 mm
Length
Contact that can ensure the minimum appli-
External terminal
cable load of 15 V DC, 1 mA.
English
and P
) and transmission
1
2
2
Remote controller wiring
terminal block
Remote
controller 2
(SUB)
F
T
T
2
1
2
FORCED
OFF
Input A
2
)
Max. 328 ft. (100 m)
(2) Actuation
• The following table explains FORCED OFF and ON/OFF
OPERATIONS in response to Input A.
FORCED OFF
Input "ON" stops operation (impossible by
remote controllers.)
Input OFF enables control by remote con-
troller.
(3) How to select FORCED OFF and ON/OFF OPERATION
• Turn the power on and then use the remote controller to
select operation.
10-5 CENTRALIZED CONTROL
• For centralized control, it is necessary to designate the group
No. For details, refer to the manual of each optional control-
lers for centralized control.

11. FIELD SETTING

Make sure the control box covers are closed on the indoor
and outdoor units.
Field setting must be made from the remote controller in
accordance with the installation conditions.
• Setting can be made by changing the "Mode No.", "FIRST
CODE NO.", and "SECOND CODE NO.".
• For setting procedures and instructions, refer to the "Field
Settings" in the installation manual of the remote controller.
FIELD SET MODE
Field Settings
Unit No.
0
0 –
01
4 –––
8 –––
1
SECOND CODE NO.
FIRST CODE NO.
With wireless remote controller used
Set the wireless remote controller address before using the
wireless remote controller.
For the setting method of the address, refer to the operation
manual provided with the wireless remote controller.
NOTE
• Before the test operation as explained in 12. TEST OPERA-
TION, be sure to make the following field settings.
• A "Mode No." is set on a group basis. To make a mode setting
on an individual unit basis or check the setting made, how-
ever, set the corresponding mode number in the parenthe-
ses.
ON/OFF OPERATION
Input OFF ON turns
ON unit.
Input ON OFF turns
OFF unit.
Mode No.
Mode
20
1 – 01
2 – 02
3 – 01
5 –––
6 –––
7 –––
9 –––
a –––
b –––
Setting
Fig. 13
14