Operation; Inspect Before Operation; Generator Set's Running - Hyundai DHY14KSE Operation And Maintenance Manual

Soundproof type diesel genset 14kva 50hz
Hide thumbs Also See for DHY14KSE:
Table of Contents

Advertisement

3

Operation

 
3.1 
Inspect Before Operation 
After  finished  installation,  our  diesel  engine 
generator  set  can  be  put  into  use.  Each  time  before 
starting  the  generator  set,  following  items  shall  be 
checked without fail: 
◆If  there  is  foreign  material  exists  in  the  surface  of 
generator  set  or  in  the  ambient  environment  which 
may hamper the generator set's operation. 
◆If  the  air  inlet  and  ventilation  path  in  the  generator 
set working room is expedite. 
◆If the anti‐freeze level is normal. 
◆If the air filter indicator works well 
◆If the lubricant level is within the specified range 
◆If the fuel valve is open, if the fuel has been supplied 
to the engine normally. 
◆If  the  cable  has  been  connected  to  the  battery  in  a 
correct way. 
◆Check if the load equipment has been well prepared. 
When the generator set directly connects to the load, 
the air switch shall be cut off before start. 
Warning: 
Operators 
shall 
(maintenance)  procedure,  this  is  the  precondition  for 
generator set's smooth running in long time period. 
3.2 
Generator set's running 
3.2.1 
Pre‐heat 
For  the  generator  set  which  is  installed  with 
pre‐heater, operators need to decide if pre‐heating is 
needed  before  start  the  generator  set  according  to 
environment temperature. The control panel which is 
installed with pre‐heat switch can instruct the engine 
to start the pre‐heater so that to achieve the purpose 
of pre‐heating. 
3.2.2 
Connect to power 
Turn the air switch in the control panel from "OFF" to 
"ON",  watch  the  panel  until  the  background  light 
turn  on,  that  means  the  control  panel  has  been 
successfully  connected  to  the  power.  At  the  same 
time  make  sure  the  fuel  pipes  are  open,  and  the 
speed  governor  or  the  control  unit  in  the  electronic 
fuel injection generator set is under working status. 
 
establish 
good 
operation 
 
 
 
3.2.3
 Start 
Part  of  the  generator  set  control  panel  has  been 
furnished with idle speed / full speed transfer switch, 
users can choose if the engine need to be started in 
idle speed or in one time full speed. Usually the time 
period  for  idle  speed  shall  not  exceed  five  minutes. 
Do  not  run  the  generator  set  in  idle  speed  in  a  long 
time period. 
Press  on  the  start  button,  the  duration  shall  not 
exceed 30 seconds, engine will be started by the start 
motor. As soon as the engine be started successfully, 
you  can  release  the  start  button  and  the  generator 
set will enter into running status. 
 
Suggestion:   
In order to extend the life expectancy of start battery 
and start motor, the duration for one time start shall 
be controlled within 5 to 10 seconds. If one time start 
fails,  stop  for  some  time  and  begin  the  second  time 
start procedure. 
 
For  the  control  panels  which  are  installed  with 
self‐start(or 
communication) 
generator  set  pre‐heating,  start‐up  period  and 
starting  times  have  been  controlled  by  the  program 
(this  program  can  be  set  and  modified  by  user). 
Operation  procedure  please  refers  to  operation 
manual. 
When  the  generator  set  control  panel  has 
malfunction(s),  timely  overhauling  is  needed  before 
Re‐start the control panel. 
Warning: 
For any start up which is made through force, not by 
control  panel,  the  malfunction  caused  by  it  do  not 
belong to the scope of warranty. 
 
3.2.4
 Running 
When  the  generator  set  begins  full  speed  running, 
and  the  alternator's  voltage  and  frequency  becomes 
normal  and  stable,  operators  can  put  the  generator 
set into normal running. 
During the generator set's running period, operators 
shall often watch and check the parameters such as if 
the  generator  set  is  running  normally,  if  the  control 
panel instrument is indicating the right position, if the 
control panel has pre‐warning indication, and the fuel 
level in the base frame etc, and make record for the 
parameters. (see attach file) 
3.2.5 
Emergency stop 
In  case  the  generator  set  was  found  to  have  severe 
12
User manual
instrument, 
the 