CANbus
Specific controller models comprise 1 port for CANbus networking purposes. Via this port,
you can create a decentralized control network of up to 63 controllers. This is sometimes
called a multi-master network. In such a network, CANbus enables inter-PLC data
exchange.
Unitronics' CANbus control network is run by a separate isolated power supply that is not
part of the network power supply.
CANbus Specifications
Power Requirements:
Galvanic Isolation between
CANbus and controller:
Max. Network Cable Length:
1
Mbit/s -
500 Kbit/s -
250 Kbit/s -
125 Kbit/s -
100 Kbit/s -
50 Kbit/s -
20 Kbit/s -
Note: If you require cable lengths over 500 meters, contact technical support.
Wiring Considerations
•
Use twisted-pair cable. DeviceNet® thick shielded twisted pair cable is
recommended.
•
Network terminators: These are supplied with the controller. Place terminators at
each end of the CANbus network. Resistance must be set to 1%, 121Ω, 1/4W.
•
Connect the ground signal to the earth at only one point, near the power supply.
•
The network power supply need not be at the end of the network
•
Maximum number of controllers in a network: 63
24VDC (±4%), 40mA max. per unit
Yes
25 m
100 m
250 m
500 m
500 m
1000 m
1000 m
Chapter 5: Communications
25