CANbus

Specific controller models comprise 1 port for CANbus networking purposes. Via this port,
you can create a decentralized control network of up to 63 controllers. This is sometimes
called a multi-master network. In such a network, CANbus enables inter-PLC data
exchange.
Unitronics' CANbus control network is run by a separate isolated power supply that is not
part of the network power supply.

CANbus Specifications

Power Requirements:
Galvanic Isolation between
CANbus and controller:
Max. Network Cable Length:
1
Mbit/s -
500 Kbit/s -
250 Kbit/s -
125 Kbit/s -
100 Kbit/s -
50 Kbit/s -
20 Kbit/s -
Note: If you require cable lengths over 500 meters, contact technical support.

Wiring Considerations

Use twisted-pair cable. DeviceNet® thick shielded twisted pair cable is
recommended.
Network terminators: These are supplied with the controller. Place terminators at
each end of the CANbus network. Resistance must be set to 1%, 121Ω, 1/4W.
Connect the ground signal to the earth at only one point, near the power supply.
The network power supply need not be at the end of the network
Maximum number of controllers in a network: 63
24VDC (±4%), 40mA max. per unit
Yes
25 m
100 m
250 m
500 m
500 m
1000 m
1000 m