Vision120 OPLC™ User Guide
RS485 Network Termination Settings
The jumper settings shown in Table 4 determine whether the controller can function as an
end device in a RS485 network. Note that the factory default setting is ON. If the OPLC is
not a network end device, set both jumpers to OFF.
RS232/RS485 Jumper Settings
The tables below show how to set a specific jumper to change the functionality of the
controller.
To open the controller and access the jumpers, refer to the instructions on the next page.
Table 3:
COM 1
To use as:
RS232*
RS485
Table 4:
COM 1
Termination
ON*
OFF
•
Default factory setting.
22
RS232/RS485 Jumper Settings
JP1
JP2
aaaaaaa
A
A
B
B
RS485 Termination Settings
JP3
JP4
aaaaaaa
A
A
B
B
COM2
To use as:
RS232*
RS485
COM2
Termination
ON*
OFF
JP5
JP6
A
A
B
B
JP7
JP8
A
A
B
B