Error Indicator (Outdoor) - LG B62AWYN9L6 Installation Manual

Hide thumbs Also See for B62AWYN9L6:
Table of Contents

Advertisement

Error Indicator (Outdoor)

Outdoor Error
Ex) Error 21 (DC Peack)
2 Times
LED01G
(RED)
1 Sec.
1 Time
LED02G
(GREEN)
2 Sec.
Error
Code
21
DC Peak(IPM Fault)
22
Max. CT(CT2)
23
DC Link Low Volt.
24
Pressure switch/Heater Sink.
26
DC Comp Position Error
29
Comp Over Current
32
D-Pipe High(Inv.)
35
Low pressure Error
41
Inv. D-Pipe Th Error(Open/Short)
43
Pressure Sensor Error
44
Outdoor air Th Error(Open/Short)
45
Cond. Middle Pipe Th Error(Open/Short)
46
Suction Pipe Th Error(Open/Short)
48
Cond. Out-Pipe Th Error(Open/Short)
51
Capacity over
Communication Error(Indoor ÷ Outdoor)
53
54
Open and Reverse Phase Error
60
EEPROM Error(Outdoor)
61
Cond. Middle Pipe High
62
Heatsink Error(High)
65
Heatsink Th Error(Open/Short)
67
BLDC motor fan lock(Outdoor)
2 Times
2 Times
1 Sec.
1 Sec.
1 Time
1
2 Sec.
Description
SETTING & TEST
Error 21
LED 1
LED 2
(Red)
(Green)
2times ◑
1time ◑
2times ◑
2times ◑
2times ◑
3times ◑
2times ◑
4times ◑
2times ◑
6times ◑
2times ◑
9times ◑
3times ◑
2times ◑
3times ◑
5times ◑
4times ◑
1time ◑
4times ◑
3times ◑
4times ◑
4times ◑
4times ◑
5times ◑
4times ◑
6times ◑
4times ◑
8times ◑
5times ◑
1time ◑
5times ◑
3times ◑
5times ◑
4times ◑
6times ◑
0
6times ◑
1time ◑
6times ◑
2times ◑
6times ◑
5times ◑
6times ◑
7times ◑
49
Indoor
status
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

62awyu7l6B70awyn9l6B70awyu7l6

Table of Contents