Separating work of the indoor
unit (if required)
To install the indoor unit, it can be easily sepa-
rated into 2 sections by making it lighter to
carry and easier to maneuver through open-
ings and in the ceiling.
!
CAUTION
Please separate the indoor unit only when
necessary. Please disassemble and re-
assemble on a flat surface.
The method to separate the indoor
unit is as follows.
① Remove the two side lock straps.
② Unscrew the top cover of the fan deck sec-
tion.
Heat exchanger
section
Side lock
strap
Fan deck section
③ Unscrew the five bolts securing the two
sections.
Heat exchanger
section
Fan deck section
④ Remove the control box cover and unplug
the air and two heat exchanger thermistors
also unplug expansion valve cable.
⑤ Carefully un-clip the three thermistor leads
and push the leads through the back of the
electrical box.
⑥ Unscrew 5 screws and separate the heat
Fan deck
top cover
⑦ Unscrew the 5 screws and separate the
PRODUCT INSTALLATION
exchanger section from unit. Carefully un-
latch the heat exchanger section from the
fan deck section by lifting up the heat ex-
changer section and then pulling away. En-
sure that the thermistor or expansion valve
motor cables do not catch on either section
as the unit is separated.
Lift up
fan deck section from sub drain pan