4.5.2.3 Outdoor Unit Above Indoor Coil
Figure 5
For applications with the outdoor unit above the
indoor coil the following is required:
• Insulated liquid line in unconditioned space only.
• Follow the proper line sizing, maximum linear
and equivalent length, maximum vertical separa-
tion, charging requirements, and oil level adjust-
ments spelled out in this document.
4.0 INSTALLATION
• Verify at least 5°F [2.8ºC] of liquid subcooling at
the outdoor unit prior to expansion device in the
heating mode.