Connection – AM 24
X1
X2
X3
X4
X5
X6
Connection – Vent buttons to AM 24
X4.4
X4.1
X5.4
X5.1
X6.4
X6.1
16/36
CPS-M1
EM-47K
Terminal module
1
2
3
4
X1
X6
4
3
2
1
L
P
LT 84-U (-SD) LT 84-U (-SD)
Ventilation
button 1
English
No.
Name
Description
X1.1
P-
Reference potential, max. 10 A (do not connect to -)
X1.2
MOT.b 1
Drive group 1, max. 10 A
X1.3
MOT.a 1
X1.4
E/HS 1
Monitoring wire / high-speed for actuator group 1
X2.1
P-
Reference potential, max. 10 A (do not connect to -)
X2.2
MOT.b 2
Drive group 2, max. 10 A
X2.3
MOT.a 2
X2.4
E/HS 2
Monitoring wire / high-speed for actuator group 2
X3.4
ACB.B 1
ACB interface of drive group 1
X3.3
ACB.A 1
X3.2
ACB.B 2
ACB interface of drive group 2
X3.1
ACB.A 2
X4.4
SGI 1
Position transmitter for drive group 1 (not yet
implemented)
X4.3
-
Reference potential (do not connect to P-)
X4.2
SGI 2
Position transmitter for drive group 2 (not yet
implemented)
X4.1
-
Reference potential (do not connect to P-)
X5.4
DO 2.1
Freely configurable digital output 1.1, max. 50 mA /
NOT CLOSED signal LT 2
X5.3
-
Reference potential (do not connect to P-)
X5.2
DI 2.1
Freely configurable digital input,
0 to 28 V, active minus or plus / OPEN LT 2
X5.1
DI 2.2
Freely configurable digital input,
0 to 28 V, active minus or plus / CLOSE LT 2
X6.4
DO 1.1
Freely configurable digital output 2.1, max. 50 mA /
NOT CLOSED signal LT 1
X6.3
-
Reference potential (do not connect to P-)
X6.2
DI 1.1
Freely configurable digital input,
0 to 28 V, active minus or plus / OPEN LT 1
X6.1
DI 1.2
Freely configurable digital input,
0 to 28 V, active minus or plus / CLOSE LT 1
1
2
3
4
1
2
X2
X3
AM-1-2-10-24-D6-D2
X5
X4
4
3
4
3
2
1
L
P
Ventilation
button 2
3
4
2
1
99.827.31 1.4/06/18

Advertisement

Table of Contents
loading

Table of Contents