Technical Data And Information - DEGA NB*-*IL III Series Instruction Manual

Gas detection transmitter
Table of Contents

Advertisement

Do not disassemble the product and ensure against it's contact with water
Contact with internal components of the product may cause an electric shock. In case of any malfuction entrust the servicing
of the product exclusively to a certified service centre. Contact with water can create a short circuit in the product and
consequent damange to property or personal injury.
Use appropriate cable types
To ensure compliance with the parameters of the product, only use cable types recommended in this guide.
Dispose of used products and trasmitter sensors with respect to the environment
Transmitter sensors contain hazardous substances. Dispose of them in accordance with the current legislation on
environmental protection.
Use the transmitter only with the appropriate certified DEGA products
The device is certified as functionally and technically qualified only with original "DEGA" accessories. In case of using the
device with any other products the manufacturer is not liable for any damages that may occur.
Undertake regular functional checks and calibrations of the transmitter
Perform regular "CALIBRATION" (setting the detection limits, checking the responsivness of the sensor, checking the
functionality of the transmitter) and "OPERATIONAL AND FUNCTIONAL CHECKS" of the entire detenction system (sensor
excitation with subsequent control of optical and audible alarms, triggering fans, shutdown technology, etc.). Perform
calibration and operational and functional checks only at certified service centers with a valid certificate of competence or the
manufacturer.
Warning: The transmitter automatically checks it's calibration period - the period of validity of it's calibration. After 12 months since the
last calibration (Max. calibration period) the transmitter will transmit this fact to the host system. The transmitter must be calibrated
immediately at a certified service center with a valid certificate of competance or the manufacturer. See section "Monitoring the
calibration peridos".

Technical data and information

Supply voltage:
Cable connections via 4-20 mA:
Cable connections via RS485:
Diameter range of wires
Output:
Dimensions without bushings:
Weight:
Dead band:
Consumption/input at 24V (output RS485)
DEGA NBx-EL III 25mA/0,6W
DEGA NBx-CL III 70mA/1,7W
DEGA NBx-IL III
50mA/1,2W
DEGA NBx-SL III 70 mA/1,7 W
Consumption/input at 24V (output 4-20mA)
DEGA NBx-EL III 45mA/1,1W
DEGA NBx-CL III 90mA/2,2W
DEGA NBx-IL III
70mA/1,7W
DEGA NBx-SL III 90mA/2,2 W
Response time (T90)
DEGA NBx-EL III max. 180s -
DEGA NBx-CL III max. 30s
DEGA NBx-IL III
max. 30s
DEGA NBx-SL III max. 30 s
24 V nominal, operational range 8-30 V
shielded cable 3 x 1 mm (max. 1200 m)
shielded cable 3 x 1,5 mm (max. 2400 m)
shielded cable 4 x 0,8 mm (max. 1200 m) - see section " instalation of wiring
for RS485"
:
0,08-2,5mm
internal space
4 - 20 mA
RS485 - DEGA protocol
110x100x50 mm (WxHxD)
0,3 kg
max 5% of range
Warm-Up time
DEGA NBx-EL III max. 180s
DEGA NBx-CL III max. 30s
DEGA NBx-IL III
DEGA NBx-SL III max. 180 s
Time to stabilize (>5day without power)
DEGA NBx-EL III Up to several hours -
DEGA NBx-CL III max. 1h
DEGA NBx-IL III
DEGA NBx-SL III max. 1 h
Sensor lifetime in a clean environment
DEGA NBx-EL III 1-3 years
based on sensor type
DEGA NBx-CL III 1-3 years
DEGA NBx-IL III
DEGA NBx-SL III 3-6 years
2
– wire, double line cable 0,25-1,5mm
max. 15s
max. 30min
5+ years
3
2
– double line cable with
based on sensor type