Interconnection
CAUTION:
•
All wiring must be done in accordance with approved conduit, boxes, and
fittings, and to procedures in accordance with all governing regulations.
•
Flexible conduit is recommended so excess stress is not applied to the
shaft bearings
•
Interconnection between the speed sensor and the integrator should be
made with 3-wire shielded, 18 AWG cable (Belden 8770 or equivalent).
•
Ground the shield at the integrator ONLY!
MD-36 Speed Sensor/Integrator Connection
MD-36
Description Terminal
1
+ 15 V DC
Speed Out
2
1
(CW)
Speed Out
3
(CCW)
4
Common
G
Ground
1.
To determine direction of rotation, see
ing on page 14.
2.
Terminal positions in brackets denote that only one signal
may be connected at one time.
3.
N/C = No Connection
MD-36 IS Speed Sensor/Isolator/Integrator Connection
MD-36 IS
(P&F #KFA5-S0T2-Ex2)
Terminal
3
4
7ML19985DB01
Milltronics MD-36 Speed Sensor – INSTRUCTION MANUAL
Compu III
TB1
30
2
(31)
(31)
32
3
N/C
IS Switch Isolator
Terminal
1
3
7
8
BW 100
BW 500
TB1
TB1
8
19
(7)
(16)
(7)
(16)
6
17
N/C
N/C
Front View
mount-
BW 100
BW 500
TB1
TB1
7
17
16
14
Page 15