GE HumiTrac XR Series Installation Manual
GE HumiTrac XR Series Installation Manual

GE HumiTrac XR Series Installation Manual

Advertisement

Quick Links

GE
Sensing & Inspection Technologies
Warranty
GE Sensing & Inspection Technologies warrants equipment
of its manufacture to the original buyer against defective
materials or workmanship, for a period of one year for the
sensor tip and two years for the rest of the product, from the
date of shipment. The sensor element and calibration are not
covered by this warranty.

Calibration

All GE Sensing & Inspection Technologies RH/Dewpoint
and Temperature Products are fully tested and calibrated in
accordance with the National Institute of Standards and
Technology (NIST) prior to shipment. This is the highest
quality calibration standard available.

Power Requirements

12–30 VDC power supply (furnished by the customer).

Specifications

Environmental Conditions
Operating Range:
–40°F to 140°F (–40°C to 60°C)
0-99% RH non-condensing.
Storage Temperature:
–67°F to +185°F (–55°C to +85°C)
Sensing Element:
Capacitive Sensor
Long Term Stability:
Less than 1% drift per year, typical.
Temperature Effect:**
Delta %RH =
(0.0014 x %RH + 0.1325) x T°C –
(0.0317 x %RH + 3.0876)
**Not needed for Signal-Conditioned Temperature units.
Signal Outputs:
4-20 mA, 0-5V or 0-10V (user selectable)
Space (Wall Mount) Range
Dew Point
40° to 90°F (4.4 to 32.2°C)
Enthalpy
0-50 BTU/lb (0-116.3 kJ/kg)
Wet Bulb
40° to 90°F (4.4 to 32.2°C)
Dry Bulb
40° to 90°F (4.4 to 32.2°C)
Duct/Outside Air Mount Range
Dew Point
-20° to 120°F (-28.8° to 49°C)
Enthalpy
0-50 BTU/lb (0-116.3 kJ/kg)
Wet Bulb
0° to 100°F (-17.8° to 37.8°C)
Dry Bulb
-20° to 120°F (-28.8° to 49°C)
Accuracy
Dew Point
±1.8°F (±1°C)
Enthalpy
±2 BTU/lb (±4.7 kJ/kg)
Wet Bulb
±3°F (±1.7°C)
Dry Bulb
±0.5°C (±0.9°F)
Certification
CE Marked
Complies with EMC Directive 89/336/EEC and LVD 73/23/EEC.
IP 42 rating for Duct Mount and Outside Air Transmitters.
Contact Information
To contact the factory, use the following information:
GE Sensing & Inspection Technologies
1100 Technology Park Drive
Billerica, MA 01821-4111
Web: www.gesensing.com
Telephone: +1 814-834-9140 or 800-321-4878
HumiTrac Information
For information specific to the HumiTrac, see the website
www.humitrac.com.

Installation

For your convenience, the transmitters can be mounted
using the base as a mounting template (see Figure 1 or 2).
Wall Mount
Locate the transmitter where it will be exposed to an
unrestricted air circulation that is representative of the
average humidity and/or temperature of the controlled
space. Avoid locations where excessive moisture, corrosive
fumes, vibration, or high ambient temperatures are present.
The wall mount transmitter is designed to install onto a
standard electric switch box. Mount the transmitter on an
indoor wall approximately 4 to 6 feet above the floor. The
base assembly should be positioned with the letters FR/ABS
located on the left side.
3.79 (96.2)
2.37 (60.3)
FR
ABS
2.37
3.30
*
*
(60.3)
(83.8)
Notes:
1. Dimensions are in inches (millimeters).
*
2.
To open the enclosure, squeeze the base
where indicated, and remove the cover.
Figure 1: Wall Mount - Mounting Dimensions
HumiTrac™ XR Transmitter Series
Installation Guide
Duct Mount
The transmitter should be mounted away from fans, corners,
heating and cooling coils, and other equipment that will
affect the measurement of relative humidity. It should be
mounted in a location that receives adequate air flow for
proper operation.
The duct mount transmitter should be mounted so that the
sensor probe is in the center of the duct.
Outside Air Mount
The transmitter should be mounted in a sheltered area that is
protected from rain. Ideally, the transmitter should be located
on the north side of the building (under an eave) to prevent
sun-heated air from rising up the building's wall and
affecting the relative humidity of the sensor.
The outside air mount transmitter should be mounted with
the sensor pointing down to prevent water collection in the
sensor cavity.
3.79 (96.2)
1.50 (38.1)
4.69
(119.1)
Ø.50
(12.7)
Ø.188 (4.76)
mounting hole, 4 pl.
Notes:
1. Dimensions are in inches (millimeters).
2. Ensure the Duct Probe doesn't make any
contact with the metal housing.
*
3.
To open the enclosure, squeeze the base
where indicated, and remove the cover.
Figure 2: Duct / Outside Air - Mounting Dimensions
A40254250
4.69
(119.1)
1.75
*
(44.5)
,Rev. A (August 2009)
Page 1 of 2

Advertisement

loading

Summary of Contents for GE HumiTrac XR Series

  • Page 1 Installation Guide Warranty Installation Duct Mount Accuracy GE Sensing & Inspection Technologies warrants equipment For your convenience, the transmitters can be mounted The transmitter should be mounted away from fans, corners, Dew Point ±1.8°F (±1°C) of its manufacture to the original buyer against defective using the base as a mounting template (see Figure 1 or 2).
  • Page 2 HumiTrac™ XR Transmitter Series Sensing & Inspection Technologies Installation Guide Wiring Wiring (cont.) Match your transmitter with the corresponding diagrams CE COMPLIANCE (Figure 4 through Figure 9), set the switches and wire Current* Ensure that the probe earth ground wire (for Duct and accordingly.