11. Installation Instruction

11.1 Select The Best Location

If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from
the condenser is not obstructed.
There should not be any animal or plant which
could be affected by hot air discharged.
Keep the spaces indicated by arrows from wall,
ceiling, fence or other obstacles.
Do not place any obstacles which may cause a
short circuit of the discharged air.
Refrigerant piping size
Outdoor Unit
Liquid - side
Gas - side
Table A
Maximum Total
Piping Length
MODEL
for add. Gas
(m)
CU-3TZ52***
30
If total piping length of all indoor units exceed the
maximum total length listed above, additionally
charge with 20 g of refrigerant (R32) for each
additional meter of piping.
A
= (m
/ (2.5 x (LFL)
min
c
A
= Required minimum room area, in m
min
m
= Refrigerant charge amount in appliance, in kg
c
LFL = Lower flammable limit (0.306 kg/m
h
= Installation height of the appliance
0
: (1.8 m for wall mounted is standard reference
installed height)
: (2.5 m for wall mounted is recommended
installed height give by manufacturer)
Outdoor Unit
Allowable piping length of each indoor unit (min. ~ max.)
Allowable total piping length of all indoor unit
Height difference between indoor and
outdoor unit
Height difference between indoor unit
CU-3TZ52***
ø 6.35 t0.8
ø 9.52 t0.8
2
Indoor A
(m
min
Additional
1.8 m for
2.5 m for
Refrigerant
wall
wall
(g/m)
mounted
mounted
20
5.96
3.09
(5/4)
x h
)) ²
0
2
3
)
Allowable piping length
Outdoor unit located on upper side
Outdoor unit located otherwise
Outdoor unit located on upper side
Outdoor unit located otherwise
Outdoor Unit Installation Diagram
This illustration is for explanation purposes only.
* Note:
Respective indoor unit installation procedure shall refer to
instruction manual provided in the indoor unit packaging.
)
25
Installation parts you
should purchase ( )
It is advisable to avoid
more than 2 blockage
directions. For better
ventilation & multiple-
outdoor installation,
please consult authorized
dealer/specialist.
Power supply cord ( )
Connecting cable ( )
Additional drain hose ( )
1/4" Liquid side piping ( )
3/8" Gas side piping ( )
CU-3TZ52***
3 m ~ 25 m
50 m or less
15 m or less
7.5 m or less
7.5 m or less
15 m or less