Download Print this page

Honeywell SiX Series Installation Instructions Manual page 10

Wireless carbon monoxide (co) detector
Hide thumbs Also See for SiX Series:

Advertisement

CO ALARM ACTIVATION
Per UL standard 2075, the SiXCO detector has been
tested to the sensitivity limits defined in UL standard
2034.
Parts per Million /
Parts per Million
30 +/- 3ppm
70 +/- 5ppm
150 +/- 5ppm
400 +/- 10ppm
SPECIFICATIONS / SPÈCIFICATIONS
Electrical Specifications
Voltage
/ Voltage
.......................................................................................................... 3 volts DC
Battery Type / Pile
Type
............................................................................................ CR123A OR DURACELL DL123, DL123A lithium
Battery Manufacturer / Pile
Number of Batteries / Number of Batteries ................................................... 2
Sensitivity
/ Sensitivity
.............................................................................................. Meets UL2034/UL2075 CO sensitivity requirements
Audible Signal
/ Audible Signal
Physical Specifications
Diameter
/ Diameter
.................................................................................................. 5.3 inches (13.46cm) Diameter; 1.65 inches (4.19cm) Thick
Weight
/ Weight
............................................................................................................ 7.7oz. (21g)
Operating Temperature /
Storage Temperature
/ Storage Temperature
Operating Humidity
/ Operating Humidity
Tamper/Tamper
........................................................................................................... Wall
REFER TO THE INSTALLATION INSTRUCTIONS FOR THE CONTROL WITH WHICH THIS DEVICE IS USED, FOR
DETAILS REGARDING LIMITATIONS OF THE ENTIRE ALARM SYSTEM.
POUR LES LIMITES DU SYSTÈME D'ALARME AU COMPLET, REPORTEZ-VOUS AU GUIDE D'INSTALLATION DU
PANNEAU DE COMMANDE.
CO Alarm Thresholds /
Detector Response Time (Minutes) /
No alarm within 30 days /
60 - 240
10 - 50
4 - 15
Manufacturer
..................................................... Panasonic, DURACELL
............................................................................. 85dBA
Température de Fonctionnement
.............................................. -10 - 70° C (14 - 158° F)
..................................................... 20-95% RH
CO ALARM ACTIVATION
Per UL standard 2075, the SiXCO detector has been
tested to the sensitivity limits defined in UL standard
2034.
CO Alarm Thresholds
Detector Response Time (Minutes)
No alarm within 30 days
........... 32° – 122° F / 0° – 50° C
Tamper/Wall Tamper
10

Advertisement

loading

This manual is also suitable for:

Sixco