Combination smoke/carbon monoxide (co) detector w/built-in wireless transmitter

Advertisement

Quick Links

SiXCOMBO
Combination Smoke/Carbon Monoxide (CO) Detector w/Built-in Wireless Transmitter
(features voice and 360 degree viewable LED ring)
Installation and Setup Guide
This device is intended for use with Honeywell control panels that support SiX series devices. Before installing detectors, please
thoroughly read these installation instructions and read the Limitations of Fire Alarm Systems Insert (P/N 800-15144 5/13) and System
Smoke Detectors Application Guide (P/N SPAG9101 7/12).
FEATURES
• Multi-Criteria Sensing:
uses four
sensing elements to react faster
while minimizing false alarms:
- Photoelectric smoke sensor
detects airborne smoke particles
- Carbon Monoxide (CO) sensor
detects smoldering fires
- Infrared (IR) sensor measures
ambient light and flame
signatures, such as flame flicker
- Thermal detection monitors for
dangerous rise in temperature
Low Temperature sensing:
senses ambient temperature
and reports if temperature goes
below 41° F (5° C).
ENROLLMENT
The Smoke, Heat, and Carbon Monoxide (CO) sensors each have
unique MAC ID numbers (serial numbers) that are enrolled in
separate zones.
• Once enrolled, the device cannot be used with another system
until it is removed from the current controller. See the 24-hour
Enrollment Deletion section below or the controller's instructions.
Enroll the Device Services (Smoke, Heat, CO)
1. Remove the detector from the base plate (tamper switch must
be faulted when enrolling).
2. Put the control panel in Zone Programming mode.
For Lyric Controller: Security > installer code > Program >
(scroll down) > SiX Programming
3. Pull the battery tab to activate enrollment process (be sure
batteries are seated properly to avoid a false low battery
condition). If the battery tab has already been removed and the
unit is powered up, press either Test switch for less than 3
seconds to activate the enrollment process.
4. The device attempts enrollment (green LED flashes about 8
seconds). If successful, the green LED lights steady for 3
seconds and the device announces successful enrollment.
If the LED does not light steady, enrollment failed. Retry by
pressing either Test switch for less than 3 seconds.
All services (Smoke, Heat, and CO) are automatically enrolled
in sequential (or next available) zone numbers with the
following default attributes:
Zone
Device Type
Smoke Det.
Smoke Detector
Heat Det.
Heat Sensor
CO Det.
Carbon Mono. Det.
24-Hour Enrollment Deletion
Use this procedure within 24 hours of initial enrollment to delete
this device from the controller. This allows reenrollment in a
specific controller in case enrollment in that controller failed (i.e.,
the device inadvertently enrolled in a different controller). This
resets the device to factory default settings and removes the.
LANGUAGE SELECTION
1. Press and hold both the Smoke and CO test switches
simultaneously for 5 seconds until Welcome message is
announced, then release. The green light flashes rapidly.
MOUNTING
After enrolling, verify adequate signal strength by
conducting Go/No Go tests (see the controller's
instructions) with the device in its intended mounting
location. Adjust the device location and orientation
as necessary.
1. Using two supplied screws and anchors, mount
the base.
2. Attach the smoke detector to the mounting base
with a clockwise motion.
• One Go / All Go: all smoke
detectors in the system
programmed as one-go-all-
go will sound on alarm.
• CO Detector End-of-Life
reporting (detector needs
replacing)
• Smoke detector maintenance
reporting (detector needs
cleaning)
Low Battery Detection
( )
( )
CO Test
Smoke Test
IR Flame
Detector
LED
Zone Response Type
Fire No Verification
Fire No Verification
Carbon Monoxide
Status LED
MODE
(Top)
Blink Green,
Power Up
every 2 secs
Single Blink
Normal
Green every
(Standby)
10 secs
Smoke
Blink Red
Alarm
every 10 secs
Thermal
Blink Red
Alarm
every 10 secs
Blink Red
CO Alarm
every 10 secs
Powered
Dark
Down
5800combo-ii 001
1
Power - Up
( )Spanish
3 Test
3a) Test CO
NOTE: Maintenance and CO End-of-Life are automatically
enrolled for the respective smoke and CO zones. Upon either of
these conditions, Contact ID code E386 "Low Maintenance
Smoke" is sent for the respective zone.
Supervision: Detector supervision is factory set for 1 minute
and is not programmable.
5. To assign zone descriptors for each of the zones and/or change
device type or zone response type, select the zone then select
Edit and make the desired changes. Press Save when done.
communication link data in the controller in which it is enrolled,
allowing the device to be reenrolled in the desired controller
1. Press and hold both the Smoke and CO test switches
simultaneously for 5 seconds, then release. The green light
flashes rapidly.
2. Press and hold both buttons again for one second and release.
2. Pres the Test button corresponding to the desired language:
English: Press the Smoke (•) test button
Spanish: Press the CO (••) test button
3.Test each detector as described in the Testing
section.
4. Confirm all desired signals have been received
by the Central Station.
NOTE: NFPA 72 recommends the installation of
detectors only after completing construction or any
other dust producing activity.
NOTE: This device should not be located within 5 ft
(1.5 m) of any cooking appliance.
Table 1: Operation Modes
LED Windows
Sounder
(Side)
Dark
Silent
Dark
Silent
Blink red
Temp-3
Blink red
Temp-3
Blink blue
Temp-4
Dark
Silent
Open
Top
Pull Battery Tab
2
Program
Zones > Serial Number.
( )English
LED
Serial Number
Flashes
Zone Description 1
Press Test button for 1 sec.
or
3b) Test Smoke
4
Transmission announcment >
Beep > Serial # sent to panel
(approx. 30 secs)
5
Save
Speaker
Voice welcome,
instructions after first
time power up or
after default
Silent
Voice smoke warning
Voice smoke warning
Voice CO
warning
Silent
Zone n
Loop Number
Zone Description 2
5800 combo-ii-003-USA

Advertisement

loading

Summary of Contents for Honeywell SiXCOMBO

  • Page 1 Installation and Setup Guide This device is intended for use with Honeywell control panels that support SiX series devices. Before installing detectors, please thoroughly read these installation instructions and read the Limitations of Fire Alarm Systems Insert (P/N 800-15144 5/13) and System Smoke Detectors Application Guide (P/N SPAG9101 7/12).
  • Page 2 TESTING CO Test Button Smoke Test Button Test communications between the detector and the control panel. The detector mode has two test buttons; one for smoke testing and one for ~ 5 sec/seg CO testing. The detector may also be functionally tested using canned smoke and canned CO.
  • Page 3 CO ALARM ACTIVATION sensitivity and will need to be replaced. The life span of the CO Per UL standard 2075, the SiXCOMBO detector has been sensor is approximately ten years from the date of manufacture. tested to the sensitivity limits defined in UL standard 2034.
  • Page 4 REFER TO THE INSTALLATION INSTRUCTIONS FOR THE CONTROL WITH WHICH THIS DEVICE IS USED FOR DETAILS REGARDING THE LIMITATIONS OF THE ENTIRE ALARM SYSTEM. 2 Corporate Center Drive P.O. Box 9040, Melville, NY 11747 © 2017 Honeywell International Inc. www.honeywell.com/security Agile Ref: 800-24314 10/17 Rev. A I56-6241-0000 10/17...