4

Installing the Solutions Module

Before installing the Solutions Module, refer to Chapter 3 Safety Information on page 9.
WARNING
Do not remove the Solutions Module when the drive is powered-up. This could damage
the drive and/or the Solutions Module.
CAUTION
4.1

Installation

4.1.1
Unidrive SP / Commander GP20
Three Solutions Module slots are available on Unidrive SP and two on Commander
GP20. The Solutions Module can be plugged into any of these slots but it is
recommended that slot 3 be used for the first Solutions Module, then slot 2 and then slot
1 (slot 2 and then slot 1 on Commander GP20). This ensures the maximum mechanical
support for the Solutions Module once fitted. See Figure 4-2.
Figure 4-1 Removing the Uni SP terminal cover Figure 4-2 Fitting and removing a Solutions
1. Before installing a Solutions Module in any drive, ensure the AC supply has been
disconnected for at least 10 minutes.
2. Ensure that any +24V and low voltage DC power supplies (if used) have been
disconnected from the drive.
3. Check that the exterior of the Solutions Module is not damaged and the multiway
connector on the underside of the module is free from dirt and debris.
4. Do not install a damaged or dirty Solutions Module in the drive.
5. Remove the terminal cover from the drive as shown in Figure 4-1.
6. Position the drive connector of the Solutions Module over the appropriate connector
of the drive. Push the Solutions Module towards the rear of the drive until it locks
into place. Make the connections to the Solutions Module as appropriate.
7. Re-fit the terminal cover to the drive by reversing the procedure shown in Figure 4-1.
SM-I/O 24V Protected User Guide
Issue Number: 2
Pz2
1 N m (8.8 lb in)
www.controltechniques.com
Module into the Unidrive SP
SM slot 1
(Menu 15)
SM slot 2
(Menu 16)
SM slot 3
(Menu 17