Aux 2 Connector; Table 11 - Aux 2 Connector Pinout - Siemens Sicore II Installation And Commissioning Manual

Table of Contents

Advertisement

System Components

5.6.4. Aux 2 Connector

This 18 way connector carries the following signals:
·
Isolated RS232
·
Duplication of Isolated RS422/RS485 that appears on the main connector
This connector has a different key orientation than Aux 1 to stop cable swapping.
The connector has the following pinout:
No.
Pin
Function
1
L
Isolated RS232 TxD
2
A
Isolated RS232 RxD
3
B
Isolated RS232 RTS
4
C
Isolated RS232 CTS
5
D
Isolated Ground for RS232
1
6
R
Isolated RS422 TxD+ / RS485 Data +
7
E
Isolated RS422 TxD- / RS485 Data -
8
S
Isolated RS422 RxD+
9
G
Isolated RS422 RxD-
10
F
Isolated Ground for RS422/RS485
11
K
Isolated sicore.in.2 bit 4 +
12
J
Isolated Ground for pins K & M
13
M
Isolated sicore.out.1 bit 4 / Digital Output 4 +
14
T
Isolated Ground for Digital Output 4 and RS232
15
N
Isolated sicore.in.2 bit 1 +
1
16
U
Isolated Ground for sicore.in.2 bit 1
1
17
H
Isolated sicore.in.2 bit 3 Signal Input
18
P
Isolated sicore.in.2 bit 3 Ground Return
– Functions not available with standard cables as listed in
1
. If these functions are needed a custom cable will be required.
Sicore II Installation and Commissioning Guide
667/HB/52600/000 Issue 2 Unrestricted
Table 11 – Aux 2 Connector Pinout
Colour
Core
Grey
2
Pink
2
Yellow
2
Green
2
-
-
Brown
1
Yellow
1
Blue
1
White
1
Green + Black
1+1
Red
1
Orange
1
Brown
2
White
2
-
-
-
-
Red
3
Black
3
35