Site requirements

Before installing the device, be sure the following facilities requirements are met.
14
SAN50C-R Installation, Service, and User Guide
representative and ensure that you have received all items, including the
following:
v Grounding lug kit
v Mounting kit
v ESD wrist strap
v Cables and connectors
v Any optional items ordered.
service representative. Have the following information ready when you contact
your customer service representative.
v Invoice number of shipper (see packing slip)
v Model and serial number of the damaged unit
v Description of damage
v Effect of damage on the installation
Table 3. Facility requirements
Type
Requirements
Electrical
v Adequate supply circuit, line fusing, and wire size, as specified
v Circuit protected by a circuit breaker and grounded in
Refer to the Technical Specifications at the end of this guide for
complete power supply specifications.
Thermal
v A minimum airflow of 79.8 cubic meters/hour (47 cubic ft/min.)
v Ambient air temperature not exceeding 40°C (104°F) while the
Rack (when
v Two rack units (2U) in a 48.3 cm (19-inch) rack
rack-mounted)
v All equipment in the rack grounded through a reliable branch
v Additional weight of switch not to exceed the rack's weight
v Rack secured to ensure stability in case of unexpected movement
by the electrical rating on the switch nameplate
accordance with local electrical codes
available in the immediate vicinity of the switch
Note: Although this airflow may exceed the airflow maximum
listed in the device Technical Specifications, the additional
airflow is recommended to pressurize the inlet (cool isle) side of
rack installations relative to the exhaust side to minimize
recirculation of hot air back to the inlet side.
switch is operating
circuit connection
limits