Download Print this page

Siemens PLC-4 Installation Instructions

Power limiting module

Advertisement

Quick Links

Installation Instructions
Model PLC-4
Power Limiting Module
INTRODUCTION
Refer to the MME-3 or MLE-6 Power Limited
Wiring Instructions, P/N 315-094883 or P/N 315-
094970, as applicable, for further information.
The Model PLC-4 from Siemens Industry, Inc.,
(See Figure 1) and its associated PL864 plug-on
boards (See Figure 2) limit the power of the
MXLV system to comply with UL-864. There are
three different PL864 boards that can plug onto
the four slots of the PLC-4:
• the PL864-25A
• the PL864-70A
• the PL864-25S
The PL864-25A and the PL864-70A plug onto
the PLC-4 to limit power to audio circuits. The
PL864-25S plugs onto the PLC-4 to limit power
to strobe circuits.
P2
Circuit 1
Circuit 2
P1
Edge connector
Edge connector
PLC-4 MODULE BOARD
PLC-4 Module Board
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
P/N 315-093312-7
P4
P6
Circuit 3
P3
P5
Figure 1
NOTE: Use the PL-864S for strobe circuits
only. Using the PL-864S for audio
circuits may damage the system.
Use the PL864-70A for 70.7V audio
circuits only.
The PLC-4 plugs onto one of the OMM card
edge connectors. A single PLC-4 with four
PL864 plug-on boards can serve up to four
audio and/or strobe circuits.
The PLC-4 and PL864-25A/70A audio cards do
not supervise themselves. However, since all
audio power to the MXLV system passes
through them, signal losses appear as troubles
for the ASC-1/2 modules.
P8
Circuit 4
P7
Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario
L6T 5E4 Canada
PL864-25S
P1
K1
CB1
PL864-25A/70A
P1
CB1
Figure 2
PL864 Plug-on Boards
P2
P2

Advertisement

loading

Summary of Contents for Siemens PLC-4

  • Page 1 (See Figure 1) and its associated PL864 plug-on circuits only. boards (See Figure 2) limit the power of the The PLC-4 plugs onto one of the OMM card MXLV system to comply with UL-864. There are edge connectors. A single PLC-4 with four...
  • Page 2 Refer to Figure 1 for the location of the the procedure listed below: circuits on the PLC-4 board and to Figure 5 for circuit wiring. 1. Check the PLC-4 to see if the circuitbreaker is tripped. c. Remove the PLC-4 card from its protec- tive bag.
  • Page 3 The Minimum wire size: 18 AWG twisted pair, key prevents installation of any other unshielded card type in the PLC-4 slot. Two other keys already installed in the OMM Input/output ratings for each circuit: prevent reverse installation of the card...
  • Page 4 100W at 70.7V RMS Strobe: 24 VDC at 4A (96W) CIRCUIT 3 OUT 24 VOLTS + TO ZC1-8B STROBE CARD INPUT CIRCUIT 4 OUT 24 VOLTS - TO ZC1-8B STROBE CARD INPUT Terminal Block Figure 5 PLC-4 Wiring Diagram P/N 315-093312-7...