General Specification; General Considerations - EMS EnviroStart Installation & Commissioning Manual

Single phase motor energy control
Table of Contents

Advertisement

3. GENERAL SPECIFICATION

TECHNICAL SPECIFICATION
SUPPLY VOLTAGE
FREQUENCY
STARTS PER HOUR
START DUTY
DOL KICK START TIME
SOFT START TIME
LED INDICATORS
COOLING
CONTROL CIRCUIT
POWER SWITCHING
CONTROL SUPPLY
MECHANICAL RATING
EU DIRECTIVES
UL DIRECTIVES
OPERATING HUMIDITY
OPERATING TEMP
ALTITUDE

3.2 GENERAL CONSIDERATIONS

1. The installer should be a competent person for installation of electrical goods.
2. The power should be disconnected before installation and only put back on once installation is
complete.
3. The only motors for which the Single Phase EnviroStart is suitable are 110v AND 220V AC
single-phase induction motors. (Also known as "Cage" or "Squirrel Cage" motors). EnviroStart
cannot be used on DC motors, Switched Reluctance motors or any form of Three Phase
motor.
4. Check that the current rating of the unit is the same or higher than the full load current (FLA) of
the motor, which should be on the nameplate of the motor. If in doubt contact the motor
manufacturer or supplier.
5. Use the correct size of cable for the current rating of the unit, (See Section 3.11)
6. The EnviroStart must be installed as the last piece of equipment before the motor.
Nominal 110V or 220V Single Phase AC
3 x Unit FLA for 5s at T
Selectable Logarithmic Ramp 3s
Power-on (Green) / Yellow (Optimize) / Fault Condition (Red)
Naturally Cooled Isolated "Cold Wall" Back Plane Enclosure
Integrated Transformer Providing PCB Supply from Mains
IP43, NEMA 1 Galvanized Metal Enclosure
Meets all EMC and Low Voltage Directives
Complies with all UL Requirements for Power Control Electronic
(Conformally Coated Systems Can Be Provided)
o
-15
C to +40
4000m Above Sea Level. De-rate Current by 1%/100m Above
Single Phase Motor Energy Control - Page 7 of 20
(Non Floating Neutral)
50Hz or 60Hz
(Defined at Time of Ordering)
≤45 starts at T
+20
amb
amb
2.5s
12MHz clocked Atmel MPIC
Isolated Base Triac
Supply
Systems
Up to 95% Non Condensing
o
C (De-rate current by 20%/10
4000m
o
C
o
+20
C
o
C)