SECTION 4 — PROGRAMMING
SSC-500 Hydraulic Press Solid-State Control

BOTTOM DWELL ms

Select the PROG position on the Program/Run selector switch.
t
s
Press the
and
buttons on the keypad to scroll through the
program options. Press ENTER when the LCD displays BOT DWELL ms.
The display now reads: XXXX
Where XXXX = a number between 0 and 60 seconds
t
s
Press the
and
buttons on the keypad to increase or decrease
the BOTTOM DWELL timer. Pressing and holding the arrow keys will
change the numbers at a rapid rate. Press ENTER to program the
BOTTOM DWELL timer to the displayed time and return to the main
menu level. The LCD again displays BOTTOM DWELL ms.
Function
When the ram reaches the BOS limit switch, the down valve stays
energized until the bottom dwell timer (if programmed) times out. Once
the time runs out, the up valve will energize, returning the ram to the
TOS limit switch.
DECOMPRESS TIMER
Select the PROG position on the Program/Run selector switch.
t
s
Press the
and
buttons on the keypad to scroll through the
program options. Press ENTER when the LCD displays Decompress.
The display now reads: XXX
Where XXX = a number between 025 and 250 ms.
t
s
Press the
and
buttons on the keypad to increase or decrease
the Decompress timer. Pressing and holding the arrow keys will
change the numbers at a rapid rate. Press ENTER to program the
Decompress timer to the displayed time and return to the main menu
level. The LCD again displays Decompress Tmr ms.
Function
When the ram reaches the BOS limit switch, the down valve will
deenergize causing the decompress timer (if programmed) to time out.
Once the time runs out, the up valve will energize, returning the ram
to the TOS limit switch.
28
Figure 4.7
BOTTOM DWELL Programming Flowchart
BOTTOM DWELL ms
Selects the Program Menu
ENTER
Item BOT DWELL ms
XXXX = Current BOTTOM DWELL
XXXX
Press the DOWN and UP
arrows to decrease or
increase the current timer
Program the BOTTOM DWELL
ENTER
time and return to Main Menu
MAIN
MENU
Time - seconds
Setting Type:
Range:
0 - 60 ms
Factory Setting:
0 seconds
Figure 4.8
DECOMPRESS TIMER Programming Flowchart
DECOMPRESS TMR ms
ENTER
XXX
ENTER
MAIN
MENU
Time - ms (milliseconds)
Setting Type:
Range:
025 - 250 ms
025
Factory Setting:
timer value
Selects the Program Menu
Item DECOMPRESS TMR ms
XXX = Current DECOMPRESS
timer value
Press the DOWN and UP
arrows to decrease or
increase the current timer
Program the DECOMPRESS
time and return to Main Menu
(Continued on next page.)