1MRS757641 E
[1] Cannot be used when the protection relay is mounted with the Combiflex 19" equipment frame (2RCA032826A0001)
620 series
Installation Manual
1.2. Install the drain wire.
The wire can be installed, for example, with a Shield-Kon one-piece
connector (Thomas & Betts). For detailed instructions, see the
manufacturer's manual.
1.3. Protect the cable end with a heat shrinkable cap.
Table 3:
Drain wire lenghts
Wire from connector
X110
X115
X130
GUID-C2E9AE68-BD22-4C4D-BCD8-DE53DE79F989 V1 EN
Figure 39:
Screened cable
1 Heat shrinkable cap
2 Drain wire
2.
Connect the functional earthing wires (drain wires) to the protection relay's body
via a connection flange (2RCA036978A0001)
protective earthing conductor.
The wire combination green/yellow should not be used as
the drain wire has no protective function.
Length
~200 mm
~200 mm
~300 mm
1
Section 5
Connecting
2
[1]
to separate them from the
45