LG LC098HV4 Engineering Manual page 60

Single-zone four-way ceiling cassette heat pump systems 3/4 to 3-1/2 tons
Hide thumbs Also See for LC098HV4:
Table of Contents

Advertisement

PLACEMENT CONSIDERATIONS
Indoor Unit
Installing in an Area Exposed to Unconditioned Air
In some installation applications, areas (floors, walls) in some rooms may be exposed to unconditioned air (room may be above or next to an
unheated garage or storeroom). To countermeasure:
• Verify that carpet is or will be installed (carpet may increase the temperature by three degrees).
• Add insulation between the floor joists.
• Install radiant heat or another type of heating system to the floor.
Installing in an Area with High Humidity Levels
If the environment is prone to humidity levels of 80% or more (near the ocean, lakes, etc.) or where steam could collect in the plenum:
• Install additional insulation to the indoor unit (glass wool insulation >13/32 inches thick).
• Install additional insulation to the refrigerant piping (insulation >13/16 inches thick).
• Seal all gaps between the indoor unit and the ceiling tiles (make the area air tight) so that humidity does not transfer from the plenum to the
conditioned space. Also, add a ceiling grille for ventilation.
Figure 36: Indoor Unit Clearance Requirements.
Ceiling
Ceiling Tile
≥19-11/16
inches
Installing the Drain System
• Drain piping must have downward gradient of at least 1/50 to 1/100; to prevent
reverse flow, slope should not be straight up and down.
Do not damage the drain port on the indoor unit when connecting the field-sup-
plied drain piping.
• Drain piping specifications:
- Indoor Unit Drain Connection: 1-1/4 inch outside diameter.
- Field-Supplied Drain Piping: Polyvinyl chloride piping with 1-inch inside diameter
and pipe fittings.
60 | INTRODUCTION
Ceiling Tile
≥19-11/16
inches
Floor
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Figure 37: Ceiling Opening Dimensions and Bolt Locations.
23-1/16 inches ~ 26 inches (Ceiling Opening)
20-3/8 inches
18-5/32 inches
Figure 38: Indoor Unit Drain Piping.
22-15/32 i n ches
Uni t Si z e
1/50~
1/100
<27-1/2 inches (9k, 12k)
<31-1/2 inches (18k to 42k)