LG THERMA V HM093MR Installation Manual

Air-to-water heat pump
Table of Contents

Advertisement

Quick Links

INSTALLATION MANUAL
AIR-TO-WATER
HEAT PUMP
Please read this installation manual completely before installing the
product.
Installation work must be performed in accordance with the national
wiring standards by authorized personnel only. Please retain this
installation manual for future reference after reading it thoroughly.
Original instruction
MFL68026607
Rev.17_013023
Copyright © 2018 - 2023 LG Electronics Inc. All Rights Reserved.
www.lg.com

Advertisement

Table of Contents
loading

Summary of Contents for LG THERMA V HM093MR

  • Page 1 Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Please retain this installation manual for future reference after reading it thoroughly. Original instruction www.lg.com MFL68026607 Rev.17_013023 Copyright © 2018 - 2023 LG Electronics Inc. All Rights Reserved.
  • Page 2: Table Of Contents

    TABLE OF CONTENTS TABLE OF CONTENTS PREFACE [Chapter 1] SAFETY INSTRUCTIONS [Chapter 2] INSTALLATION PART [Chapter 3] GENERAL INFORMATION Model Information Model name and related information Parts and Dimensions Control Parts Remote Controller Typical Installation Example Cycle Diagram Water cycle [Chapter 4] INSTALLATION Transporting the Unit...
  • Page 3 Water Quality Frost protection by antifreeze Frost protection by antifreeze valve Water Volume and Expansion Vessel Pressure [Chapter 5] ACCESSORIES INSTALLATION Accessories supported by LG Electronics Accessories supported by 3rd party Companies Before Installation Thermostat 2nd Circuit 3rd Party Boiler...
  • Page 4 TABLE OF CONTENTS Energy State Digital Input for energy saving (ESS, Smart Grid) 2Way Valve 3Way Valve(A) 3Way Valve(B) Electric Heater Typical Installation Example Final check [Chapter 6] CONFIGURATION DIP Switch Setting [Chapter 7] SERVICE SETTING How to enter service setting Service setting Service Contact Model Information...
  • Page 5 TABLE OF CONTENTS Water cooling set temp Air heating set temp Water heating set temp DHW set temp Screed drying Heater on temperature Water supply off temp. during cooling Tank disinfection setting 1, 2 Tank setting1 Tank setting2 Heater priority DHW time setting TH on/off Variable, heating air TH on/off Variable, heating water...
  • Page 6 TABLE OF CONTENTS INSTALLER SETTING (For 4 Series) Select Temperature Sensor Use Heating Tank Heater Mixing Circuit Use External Pump RMC master/slave LG Therma V Configuration Forced operation Pump Prerun/Overrun Water Flow Control Energy Monitoring Anti-Freezing Option 1 Password Reset...
  • Page 7 Recirculation time Solar Thermal System Pump test run Frost Protection Temp. Dry Contact Mode Central Control Address CN_CC LG Therma V Configuration Energy state Thermostat control type Pump operation time IDU operation time Modbus Address Modbus gateway memory map CN_EXT...
  • Page 8: Preface

    Preface PREFACE This installation manual is to present information and guide about understanding, installing, and checking Your careful reading before installation is highly appreciated to make no mistake and to prevent potential risks. The manual is divided into nine chapters. These chapters are classified according to installation procedure.
  • Page 9: Safety Instructions

    PREFACE SAFETY INSTRUCTIONS Read the precautions in This appliance is filled this manual carefully with flammable before operating the refrigerant (for R32) unit. This symbol indicates This symbol indicates that a service personnel that the Operation should be handling this Manual should be read equipment with carefully.
  • Page 10 SAFETY INSTRUCTIONS • For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center. - There is risk of fire or electric shock. • Always ground the unit. - There is risk of fire or electric shock. •...
  • Page 11 SAFETY INSTRUCTIONS • Use a vacuum pump or inert (nitrogen) gas when doing leakage test or purging air. Do not compress air or oxygen and do not use flammable gases. - There is the risk of death, injury, fire or explosion. •...
  • Page 12 SAFETY INSTRUCTIONS • Do not pierce or burn. (for R32) • Be aware that refrigerants may not contain an odour. (for R32) • Dismantling the unit, treatment of the refrigerant oil and eventual parts should be done in accordance with local and national standards.
  • Page 13 SAFETY INSTRUCTIONS • Do not place anything on the power cable. - There is risk of fire or electric shock. • Do not plug or unplug the power supply plug during operation. - There is risk of fire or electric shock. •...
  • Page 14 SAFETY INSTRUCTIONS • Do not touch any electric part with wet hands. you should be power off before touching electric part. - There is risk of electric shock or fire. • Do not touch refrigerant pipe and water pipe or any internal parts while the unit is operating or immediately after operation.
  • Page 15 SAFETY INSTRUCTIONS • If the unit is not used for long time, we strongly recommend not to switch off the power supply to the unit. - There is risk of water freezing. • The appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for operation.
  • Page 16 SAFETY INSTRUCTIONS • Leak detection methods The following leak detection methods are deemed acceptable for systems containing flammable refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate, or may need re- calibration.
  • Page 17 SAFETY INSTRUCTIONS - Cylinders shall be kept in an appropriate position according to the instruction. - Ensure that the refrigeration system is earthed prior to charging the system with refrigerant. - Label the system when charging is complete (if not already). - Extreme care shall be taken not to overfill the refrigerating system.
  • Page 18 SAFETY INSTRUCTIONS Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt.
  • Page 19 SAFETY INSTRUCTIONS The refrigerant charge shall be recovered into the correct recovery cylinders. For appliances containing flammable refrigerants other than A2L refrigerants, the system shall be purged with oxygen-free nitrogen to render the appliance safe for flammable refrigerants. This process may need to be repeated several times.
  • Page 20 SAFETY INSTRUCTIONS • In order to avoid a hazard due to inadvertent resetting of the thermal cut-out, this appliance must not be supplied through an external switching device, such as a timer, or connected to a circuit that is regularly switched on and off by the utility. •...
  • Page 21 SAFETY INSTRUCTIONS • The appliance shall be disconnected from its power source during service and when replacing parts. • Means for disconnection must be incorporated in the fixed wiring in accordance with the wiring rules. • The Installation kit supplied with the appliance are to be used and that old Installation kit should not be reused.
  • Page 22: Installation Part

    INSTALLATION PART INSTALLATION PART Thank you for choosing LG Electronics Air-to-Water Heat Pump Before starting installation, please make it sure that all parts are found inside the product box. *The parts can be found inside the outdoor unit by opening the side panel.
  • Page 23: General Information

    GENERAL INFORMATION GENERAL INFORMATION With advanced inverter technology, is suitable for applications like under floor heating, under floor cooling, and hot water generation. By Interfacing to various accessories user can customize the range of the application. In this chapter, general information of is presented to identify the installation procedure.
  • Page 24 GENERAL INFORMATION - For 3 Series - For 4 Series Refrigerant Refrigerant H M 09 1 S U3 3 M 09 Signification Signification Air-to-Water-Heat Pump Air-to-Water-Heat Pump Classification Classification - M : Monobloc - M : Monobloc Heating Capacity Heating Capacity - E.g) 9 kW →...
  • Page 25: Model Name And Related Information

    GENERAL INFORMATION Model name and related information Model Name Capacity (kW) Power Source (Unit) Chassis Phase(Ø) Capacity(kW) Heating Cooling 220-240 V~ 50 Hz UN36A 380-415 V 3N~ 50 Hz 220-240 V~ 50 Hz UN60A 380-415 V 3N~ 50 Hz 1 : Tested under EN14511 (water temperature 30 °C ’...
  • Page 26: Parts And Dimensions

    GENERAL INFORMATION Parts and Dimensions - For 3 Series UN36A (5, 7, 9 kW) (Unit : mm) 1239 3D View 6 holes for Anchor Bolts (M10) Side View 3-ID Ø 20 holes for drain connection h The shape may differ depending on the model.
  • Page 27 GENERAL INFORMATION UN60A (9, 12, 14, 16 kW) (Unit : mm) 1239 6 holes for Ancher Bolts (M10) 3D View Side View 3-ID Ø 20 holes for drain connection h The shape may differ depending on the model.
  • Page 28 GENERAL INFORMATION Description Name Remarks Entering water pipe Male PT 1 inch Leaving water pipe Male PT 1 inch Strainer Filtering and stacking particles inside circulating water Top cover Front Panel Side Panel Low Voltage Communication Cable Hole UNIT Power Power Cable Hole Water Pump Circulating the water...
  • Page 29 GENERAL INFORMATION - For 4 Series UN36A (5, 7, 9 kW) (Unit : mm) 1239 Drain hole for drain nipple (6EA) Note: If you need more drains, remove them. Drain hole for drain nipple (1EA) h The shape may differ depending on the model.
  • Page 30 GENERAL INFORMATION UN60A (12, 14, 16 kW) (Unit : mm) 1239 Drain hole for drain nipple (1EA) Drain hole for drain nipple (6EA) Note: If you need more drains, remove them. h The shape may differ depending on the model.
  • Page 31 GENERAL INFORMATION Description Name Remarks Entering water pipe Male PT 1 Inch Leaving water pipe Male PT 1 Inch Strainer Filtering and stacking particles inside circulating water Top cover Front Panel Side Panel Low Voltage Communication Cable Hole UNIT Power Power Cable Hole Water Pump Plate Heat Exchanger...
  • Page 32: Control Parts

    GENERAL INFORMATION Control Parts - For 3 Series Control box before structural change (Until August, 2020) UN36A (5, 7, 9 kW) UN60A (9, 12, 14, 16 kW) Control box after structural change (From September, 2020) h The shape may differ depending on the model. Refer to “Exploded View” in SVC Manual. Description Name Remark...
  • Page 33 GENERAL INFORMATION - For 4 Series Control box h The shape may differ depending on the model. Refer to “Exploded View” in SVC Manual. Description Name Remark Terminal blocks The terminal blocks allow easy connection of field wiring The main PCB(Printed Circuit Board) controls the functioning of the Main PCB unit...
  • Page 34: Remote Controller

    GENERAL INFORMATION Remote Controller Operation display window Back button On/Off Button OK Button Up/Down/Left/Right Button Operation display window Operation and Settings status display Back button When you move to the previous stage from the menu’s setting stage Up/down/left/right button When you change the menu’s setting value OK button When you save the menu’s setting value On/Off button...
  • Page 35: Typical Installation Example

    GENERAL INFORMATION Typical Installation Example CAUTION is installed with pre-existing boiler, the boiler and should not be operated together. If entering water temperature of is above 55 °C, the system will stop operation to prevent mechanical damage of the product. For detailed electric wiring and water piping, please contact authorized installer.
  • Page 36 GENERAL INFORMATION CASE 2: Connecting DHW Tank Outdoor Indoor Buffer Tank M / F Hot water Fan coil unit Floor heating loop Radiator tank tank tank City water NOTE • DHW tank - It should be equipped with internal electric heater to generate sufficient heat energy in very cold season.
  • Page 37 GENERAL INFORMATION CASE 3: Connecting Solar thermal system Outdoor Indoor Buffer Tank M / F Solar heat source Hot water Fan coil unit Floor heating loop Radiator tank City water NOTE • DHW tank - It should be equipped with internal electric heater to generate sufficient heat energy in very cold season.
  • Page 38 GENERAL INFORMATION CASE 4-1: Connecting 2nd Circuit (For 3 Series) [Circuit 2] Mixing Circuit circuit temp. sensor Outdoor Indoor Mix Kit Floor heating loop Floor heating loop Buffer Tank M / F [Circuit 1] Direct Circuit Radiator Radiator CASE 4-2: Connecting 2nd Circuit (For 4 Series) [Circuit 2] Mixing Circuit Outdoor Indoor...
  • Page 39 GENERAL INFORMATION CASE 5: Connecting 3 Party 3 Way Valve direction Boiler On : Boiler Off : Outdoor Indoor Boiler Buffer Tank M / F Floor Floor Floor heating loop heating loop heating loop NOTE • DHW tank - 3rd Party Boiler - You can control the boiler automatically and manually by comparing the outside temperature and the set temperature.
  • Page 40 GENERAL INFORMATION CASE 6 : Connecting backup heater Outdoor Indoor Buffer Tank Floor heating Floor heating Floor heating loop loop loop NOTE • Backup heater(Accessory) - You can retain sufficient capacity even though ambient temperature will be decreased in winter. - During cooling operation, connect the 3-Way Valve with automatic reset function using the 2-Way Valve connection terminal to prevent water from going to the Backup Heater.
  • Page 41: Cycle Diagram

    GENERAL INFORMATION Cycle Diagram - For 3 Series UN60A (12, 14, 16 kW) <Refrigerant Side> <Water Side> : Cooling : Heating High Air Vent Pressure Pressure Sensor Switch Backup Heater Muffler Accessory Accumulator Expansion Tank Relief Water valve Pressure Gage Air Vent EEV1 EEV2...
  • Page 42 GENERAL INFORMATION UN60A (1Ø : 9 kW) <Refrigerant Side> <Water Side> : Cooling : Heating High Pressure Air Vent Sensor Pressure Switch Backup Muffler Heater Accumulator Accessory Relief EEV1 Expansion Tank valve Water Pressure Gage Air Vent EEV3 (Inj.EEV) Water [PHE] W/Pump Strainer Flow...
  • Page 43 GENERAL INFORMATION - For 4 Series UN36A (5, 7, 9 kW) UN60A (12, 14, 16 kW) <Refrigerant Side> <Water Side> : Cooling <Outdoor unit> : Heating Air Vent Backup Heater Pressure Accessory Pressure Sensor Switch Accumulator Expansion Tank Relief EEV1 valve Water Air Vent...
  • Page 44: Water Cycle

    GENERAL INFORMATION Water cycle - For 3 Series...
  • Page 45 GENERAL INFORMATION - For 4 Series...
  • Page 46 GENERAL INFORMATION Description Category Symbol Meaning PCB Connector Remarks Refrigerant temperature sensor (Gas side) CN_PIPE_OUT - Meaning is expressed based on Cooling mode. Refrigerant temperature sensor (Liquid side) CN_PIPE_IN Water temperature sensor (Water In) Water _IN Water temperature sensor (Water Out) Water _OUT Flow Switch CN_FLOW1...
  • Page 47: Installation

    INSTALLATION INSTALLATION Transporting the Unit • When carrying the suspended unit, pass the ropes between legs of base panel under the unit. • Always lift the unit with ropes attached at four points so that impact is not applied to the unit. •...
  • Page 48: Installation Places

    INSTALLATION Installation places - If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted. - Ensure that the spaces indicated by arrows around front, back and side of the unit. - Do not place animals and plants in the path of the warm air.
  • Page 49: Multiple Installation

    INSTALLATION Multiple installation When installing two or more units, please observe the installation space. - If there is an obstruction in the intake Unit : mm - If there is an obstruction in the discharge part Unit : mm...
  • Page 50 INSTALLATION - When there is an obstacle in the suction or discharge part Unit : mm L > H L > H ≤ ≤ - Multiple installation on the roof Unit : mm ≤...
  • Page 51: Installation At Seaside

    INSTALLATION Installation at Seaside CAUTION • Unit should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced. • Do not install the unit where it could be exposed to sea wind (salty wind) directly. It can result corrosion on the unit.
  • Page 52: Foundation For Installation

    INSTALLATION Foundation for Installation • Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installation. • Fix the unit securely by means of the foundation bolts. (Prepare 6sets of M12 foundation bolts, nuts and washers each which are available on the market.) •...
  • Page 53: Electrical Wiring

    INSTALLATION Electrical Wiring • Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring regulations and guidance of each electric power company. WARNING • Be sure to have authorized electrical engineers do the electric work using special circuits in accordance with regulations and this installation manual.
  • Page 54 INSTALLATION CAUTION The power cable connected to the unit should be complied with IEC 60245 or HD 22.4 S4 (This equipment shall be provided with a cable set complying with the national regulation. Pipes and wires should be purchased separately for installation of the product.) Select a circuit breaker and power cable suitable for the current specification.
  • Page 55 INSTALLATION Precautions when laying power wiring Use round pressure terminals for connections to the power terminal block. Power wire Round pressure terminal When none are available, follow the instructions below. - Do not connect wiring of different thicknesses to the power terminal block. (Slack in the power wiring may cause abnormal heat.) - When connecting wiring which is the same thickness, do as shown in the figure below.
  • Page 56 INSTALLATION Point for attention regarding quality of the public electric power supply (For 3 Series) - European/International Technical Standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current ≤ 75 A. - European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current ≤16 A of >...
  • Page 57 INSTALLATION Point for attention regarding quality of the public electric power supply (For 4 Series) - European/International Technical Standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current ≤ 75 A. - European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current ≤16 A of >...
  • Page 58 INSTALLATION Circuit Breaker Specification Perform the electrical wiring work according to the electrical wiring connection. • All wiring must comply with local requirements. • Select a power source that is capable of supplying the current required by the appliance. • Use a recognized ELCB(Electric Leakage Circuit Breaker) between the power source and the unit.
  • Page 59 INSTALLATION Wiring procedure for power cable This cable is generally connected between external power source (such as main electric power distribution panel of user's house) and the unit. Before starting wiring, check if wire specification is suitable and read following directions and cautions VERY carefully. CAUTION After checking and confirming following conditions, start wiring work.
  • Page 60 INSTALLATION Step 2. Connect power cable to main power terminal block. See below figure for detailed information. When connecting power cable, the diameter of cable should be refer to the electrical wiring. For the 1-Phase Main Terminal block For the 3-Phase Main Terminal block 1(L) 2(N) Power Supply...
  • Page 61 INSTALLATION Terminal Block Information - For 3 Series Symbols used below pictures are as follows : - L, L1, L2 : Live (220-240 V~) - N : Neutral (220-240 V~) - BR : Brown, WH : White, BL : Blue, BK : Black Case 1 (From September, 2020) Case 2 (Until August, 2020) Terminal Block 1...
  • Page 62 INSTALLATION - For 4 Series Symbols used below pictures are as follows : - L, L1, L2 : Live (220-240 V~) - N : Neutral (220-240 V~) - BR : Brown, WH : White, BL : Blue, BK : Black Terminal Block 1 2WAY VALVE 3WAY VALVE...
  • Page 63: Wiring Of Main Power Supply And Equipment Capacity

    INSTALLATION Wiring of main power supply and equipment capacity 1. Use a separate unit power and heater power. 2. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections. 3. The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker taking into account the line voltage drops.
  • Page 64: Water Piping And Water Circuit Connection

    INSTALLATION Water Piping and Water Circuit Connection CAUTION Followings are should be considered before beginning water circuit connection. • Service space should be secured. • Water pipes and connections should be cleaned using water. • Space for installing external water pump should be provided if internal water pump capacity is not enough for installation field.
  • Page 65: Pipe Insulation

    INSTALLATION When the water pipes are connected. It must be tightened the nut with two wrench. Otherwise pipes can be deformed. Water Out * The feature may be vary according to the type of model. Water In WARNING Installing shut-off valve •...
  • Page 66: Water Charging

    INSTALLATION Water Charging For water charging, please follow below procedures. Step 1. Open all valves of whole water circuit. Supplied water should be charged not only inside the unit, but also in the under floor water circuit, DHW water tank circuit, FCU water circuit, and any other water circuits controlled by the product.
  • Page 67: Water Pump Capacity

    INSTALLATION Water pump Capacity The water pump us variable type which is capable to change flow rate, so it may be required to change default water pump capacity in case of noise by water flow. In most case, however, it is strongly recommended to set capacity as Maximum.
  • Page 68: Performance Curve

    INSTALLATION Performance curve GRUNDFOS Water Pump : UPML GEO 20 – 105 CHBL UN60A (12, 14, 16 kW) GRUNDFOS Water Pump : UPM3K GEO 20 – 75 CHBL UN36A (5, 7, 9 kW), UN60A (9 kW) OH SUNG Water Pump : ODM-061P UN60A (12, 14, 16 kW), UN36A (5, 7, 9 kW) Q-H Chart Q [LPM]...
  • Page 69: Water Quality

    INSTALLATION Water Quality Water quality should be complied with EN 98/83 EC Directives. Detailed water quality condition can be found in EN 98/83 EC Directives. CAUTION • If the product is installed at existing hydraulic water loop, it is important to clean hydraulic pipes to remove sludge and scale.
  • Page 70: Frost Protection By Antifreeze Valve

    INSTALLATION Frost protection by antifreeze valve About antifreeze valve This is a valve to prevent freeze in winter. When no antifreeze is added to the water, you can use antifreeze valves at all lowest points of the field piping to drain the water from the system before it can freeze To install antifreeze valve To protect the field piping against freezing, install the following parts:...
  • Page 71 INSTALLATION NOTE • Do not make any trap connections. If the shape of the connection pipe has the potential to create a trap effect, part of the pipe will not be able to drain and frost protection will no longer be guaranteed. •...
  • Page 72: Water Volume And Expansion Vessel Pressure

    INSTALLATION Water Volume and Expansion Vessel Pressure Inside expansion vessel is included which is 8 liter capacity with 1 bar pre-pressure. That means, according to the volume-pressure graph, total water volume of 230 liter is supported as default. If total water volume is changed because of installation condition, the pre-pressure should be adjusted to secure proper operation.
  • Page 73: Accessories Installation

    In this chapter, specifications about supported 3rd party accessories and how to connect to is introduced. It is noted that this chapter only deal with 3rd party accessories. For accessories supported by LG Electronics, please refer to installation manual of each accessories. Accessories supported by LG Electronics Item Purpose...
  • Page 74 ACCESSORIES INSTALLATION Item Purpose Model OSHW-200F : 200 L, Single Heating Coil, 1Ø 230 V 50 Hz 2.4 kW Booster heater OSHW-300F : 300 L, Single Heating Coil, 1Ø 230 V 50 Hz 2.4 kW Booster heater DHW Tank To generate and store hot water OSHW-500F : 500 L, Single Heating Coil, 1Ø...
  • Page 75 ACCESSORIES INSTALLATION Accessories supported by 3 party Companies Item Purpose Specification To generate auxiliary heating energy • Solar collector Solar Heating System for water tank • 3way valve(B) • Mixing valve Mix Kit To use 2nd Circuit • Mix pump 3rd Party Boiler To use auxiliary boiler.
  • Page 76: Before Installation

    ACCESSORIES INSTALLATION Before Installation WARNING Followings should be kept before installation • Main power must be turned off during installing 3rd party accessories. • 3rd party accessories should be comply with supported specification. • Proper tools should be chosen for installation. •...
  • Page 77 ACCESSORIES INSTALLATION General Information The Heat Pump supports following thermostats. Type Power Operating Mode Supported Heating Only (3) Mechanical 230 V~ Heating / Cooling (4) Heating / Cooling / DHW Heating (5) Heating Only (3) Electrical 230 V~ Heating / Cooling (4) Heating / Cooling / DHW Heating (5) (1) There is no electric circuit inside the thermostat and electric power supply to the thermostat is not required.
  • Page 78 ACCESSORIES INSTALLATION How to wire thermostat (For 3 series) Follow below procedures Step 1 ~ Step 5. Step 1. Uncover front cover of the unit and open the control box. Step 2. Identify the power specification of the thermostat. If it is 220-240 V~, go to Step 3. Step 3.
  • Page 79 ACCESSORIES INSTALLATION How to wire Heating / Cooling / DHW Heating thermostat (For 4 Series) Follow below procedures Step 1 ~ Step 3. Step 1. Uncover front cover of the unit and open the control box. Step 2. Identify the power specification of the thermostat. If it is 220-240 V~, go to Step 3. Step 3.
  • Page 80: 2Nd Circuit

    ACCESSORIES INSTALLATION Circuit The 2nd circuit is generally used to control the temperature of 2 rooms differently. To use the 2nd Circuit, you need to prepare a separate Mix Kit. The mix kit must be installed in the main zone. - Main Zone : zone where the water temperature is lowest when heating.
  • Page 81 ACCESSORIES INSTALLATION - For 4 Series [Install Guide 2 Circuit Heating] Circuit 2 Convector Floor (35°C) Radiator (45 °C) Radiator (55 °C) (FCU, 45 °C) Circuit 1 ○ Floor (35 °C) ○ ○ ○ Convector (FCU, 45 °C) ○ ○ ○...
  • Page 82 ACCESSORIES INSTALLATION How to Wire Mix Pump, Mixing Valve and Thermistor for 2nd Circuit - For 3 Series Follow below procedures Step 1 ~ Step 3. Step 1. Uncover front cover of the unit. Step 2. Find terminal block and connect wire as below (L) : Live signal from PCB to mix pump (N) : Neutral signal from PCB to mix pump (L1) : Live signal (for Normal* Closed type) from PCB to...
  • Page 83 ACCESSORIES INSTALLATION - For 4 Series Follow below procedures Step 1 ~ Step 3. Step 1. Uncover front cover of the unit. Step 2. Find terminal block and connect wire as below (L) : Live signal from PCB to mix pump (N) : Neutral signal from PCB to mix pump (L1) : Live signal (for Normal* Closed type) from MIXING VALVE...
  • Page 84 ACCESSORIES INSTALLATION [Thermistor for 2 circuit] Sensor Sensor Holder Sensor Connector Follow below procedures step 1 ~ step 4. Step 1. Install sensor connector to outlet pipe of mix kit water pump. (Welding must be performed to connect the sensor connector to the pipe.) Step 2.
  • Page 85: 3Rd Party Boiler

    ACCESSORIES INSTALLATION 3rd Party Boiler The product can be used by connecting an Auxiliary boiler. You can control the boiler automatically and manually by comparing the outside temperature and the set temperature. How to install 3rd party boiler Follow below procedures step 1 ~ step 3. Step 1.
  • Page 86: 3Rd Party Controller

    3rd Party Controller The product can also be linked to 3rd party controller. You can connect external controllers using Modbus protocol except for LG controller. If 3rd party controller is used, LG controller is not applied to AWHP simultaneously. How to install 3 party controller Follow below procedures step 1 ~ step 4.
  • Page 87: Meter Interface

    ACCESSORIES INSTALLATION Meter Interface This product can be used by connecting the meter interface module supplied in the field. The meter interface module can communicate with the wired remote controller. The meter interface module lets you know the amount of power generated by the product. How to install Meter Interface [Parts of Meter interface] Meter interface body...
  • Page 88: Central Controller

    Log in to central controller and register device with address set. Consult a qualified engineer/ technician for the installation of central controller. If you have any installation queries, contact the LG service center or LG Electronics. How to Installation PI485 Fix the PI485 PCB as shown in below images.
  • Page 89: Remote Controller

    ACCESSORIES INSTALLATION Remote Controller Installation of Remote Controller • After fixing the remote controller installation plate on the desired location, fix it firmly with the provided screws. - If the installation plate is not flat on the surface, it may result in the controller being twisted and cause a defect.
  • Page 90 ACCESSORIES INSTALLATION • After fixing the remote controller top side on the installation plate attached to the wall as in the following figure, press the bottom side to combine with the installation plate. - Do not leave a gap in the top, bottom, left, and right side of the remote controller and the installation plate after combining them.
  • Page 91 ACCESSORIES INSTALLATION • For the following cases, separately purchase and use the cables suitable for the situation. - Do not install the cable over 50 m.(It may cause communication issues.) - If the distance between the wired remote controller and the unit is 10 m or more : 10 m extension cable (model name: PZCWRC1) NOTE During the wired remote controller installation, do not bury it in the wall.
  • Page 92 ACCESSORIES INSTALLATION Cable connection method to use external device 1) Wired remote controller-cable connection method. - In the wired remote controller, connect the part marked in the following figure (J02C, DO- Port) to the cable. - According to the installation environment, there are 3 directions (Rear entry, top side, and right side) for the installation.
  • Page 93: Dhw Tank

    ACCESSORIES INSTALLATION DHW Tank To establish DHW circuit, 3way valve and DHW tank kit is required. If solar thermal system is pre-installed at the installation field, solar thermal kit is required to interface solar thermal system – to – DHW tank – to – Installation condition Installing DHW water tank requires following considerations : •...
  • Page 94 ACCESSORIES INSTALLATION Installing recirculation pump - For 3 Series When is used with DHW tank, it is STRONGLY recommended to install recirculation pump to prevent flooding out cold water at the end of hot water supply and to stabilize the water temperature inside DHW tank - The recirculation pump should be operated when DHW demand is not required.
  • Page 95 ACCESSORIES INSTALLATION - For 4 Series When is used with DHW tank, it is STRONGLY recommended to install recirculation pump to prevent flooding out cold water at the end of hot water supply and to stabilize the water temperature inside DHW tank - The recirculation pump should be operated when DHW demand is not required.
  • Page 96 ACCESSORIES INSTALLATION How to Wire Booster Heater Step 1. Uncover heater cover of the DHW tank. It is located side of the tank. Step 2. Find terminal block and connect wires as below. Wires are field-supplied item. (L) : Live signal from PCB to Heater. (N) : Neutral signal from PCB to Heater.
  • Page 97 ACCESSORIES INSTALLATION How to Wire DHW Tank Heater Step 1. Uncover heater cover of the DHW tank. It is located side of the tank. Step 2. Find terminal block and connect wires as below. Wires are field-supplied item. (L) : Live signal from PCB to Heater (N) : Neutral signal from PCB to Heater WARNING Wire specification...
  • Page 98: Dhw Tank Kit

    ACCESSORIES INSTALLATION DHW Tank Kit This product can be used by connecting the DHW tank kit in the field. It can be utilized hot water heated by booster heater in DHW tank. How to install DHW tank kit [Parts of DHW Tank Kit] Tank kit body Sensor Multi harness...
  • Page 99 ACCESSORIES INSTALLATION - For 4 Series CN_TH4 CN_TANK_HEATER Indoor PCB Fig. 1 1(L) 2(N) TO ELB FOR DHW TANK E/HEATER DHW TANK HEATER...
  • Page 100: Solar Thermal Kit (For 3 Series)

    Solar Thermal Kit (For 3 Series) This product can be used by connecting the solar thermal kit in the field. It can be utilized hot water heated by solar thermal system. End-user must be LG AWHP solar thermal kit. How to Install Solar Thermal Kit...
  • Page 101 ACCESSORIES INSTALLATION Solar Thermal Sensor (less than 12 m) 3way valve (Field Supply) Solar Water In Water Tank Sensor Tube Thermal connecter System (less than 12 m) Water Out (Field Supply) Solar Pump Water In Collector (Field Supply) (Field Supply) Water Out Water Tank h Water In / Water Out installation scene may vary depending on the model.
  • Page 102: Solar Thermal Kit (For 4 Series)

    ACCESSORIES INSTALLATION Solar Thermal Kit (For 4 Series) This product can be used by connecting the solar thermal kit in the field. It can be utilized hot water heated by solar thermal system. How to Install Solar Thermal System Follow below procedures step 1 ~ step 3. Step 1.
  • Page 103: Dry Contact

    ACCESSORIES INSTALLATION Dry Contact Dry Contact is a solution for automatic control of HVAC system at the owner's best. In simple words, it's a switch which can be used to turn the unit On/Off after getting the signal from external sources. How to install dry contact [Parts of Dry contact] Dry Contact body...
  • Page 104 ACCESSORIES INSTALLATION [Setting of Contact Signal Input] • For input contact closure only(No power input) Thermostat LG does not supply this section (Field supply) Notes Do not input the voltage signal in “NON VOLT” setting mode. Otherwise it will cause serious damage.
  • Page 105: External Controller - Setting Up Programmable Digital Input Operation

    ACCESSORIES INSTALLATION External Controller - Setting up programmable digital input operation If you require to operate control depending on external digital input(ON/OFF), connect cable to indoor PCB(CN_EXT). Follow below procedures step 1 ~ step 4. Step 1. Check if the power of the unit is turned off. Step 2.
  • Page 106: Remote Temperature Sensor

    ACCESSORIES INSTALLATION Remote Temperature Sensor Remote temperature sensor can be installed any place a user wants to detect the temperature. Installation condition Role and constraint while installation of remote air temperature sensor is very similar to that of thermostat. • Distance between the unit and the remote air temperature sensor should be less than 15 m due to length of the connection cable of remote air temperature sensor.
  • Page 107 ACCESSORIES INSTALLATION How to Install Remote Temperature Sensor [Parts of Remote Temperature Sensor] Sensor Screw(to fix remote sensor) Follow below procedures step 1 ~ step 5. Step 1. Decide where the remote temperature sensor is Installed. Then, Determine the location and height of the fixing screws in fig.
  • Page 108 ACCESSORIES INSTALLATION Step 6. Integrate the remote temperature sensor with the screws Fixing the Remote Sensor as the order of arrows. CAUTION • Choose the place where the average temperature can be measured for the unit operates. • Avoid direct sunlight. •...
  • Page 109: Solar Pump

    ACCESSORIES INSTALLATION Solar pump Solar pump can be required to energize water flow when solar thermal system is installed. How to install solar pump Follow below procedures step 1 ~ step 4. Step 1. Check if the power of the unit is turned off. Step 2.
  • Page 110: External Pump

    ACCESSORIES INSTALLATION External pump External pump can be required when the room to take floor heating is too large or not well- insulated.(potential free) Also, External pump is installed with buffer tank to retain sufficient capacity. How to install external pump Follow below procedures step 1 ~ step 3.
  • Page 111: Wi-Fi Modem

    ACCESSORIES INSTALLATION Wi-fi Modem Wi-fi modem enables remote system operation from smartphone. Available functions include selection of on/off, operation mode, DHW heating, temperature setup and weekly scheduling etc. How to install Wi-fi Modem [Parts of Wi-fi modem] Wi-fi modem body USB Cable Extension Cable Follow below procedures step 1 ~ step 5.
  • Page 112: Energy State

    ACCESSORIES INSTALLATION Energy State This product provides energy states that enable customers to use as much as possible of their own renewable energy. It can shift setpoints depending on input signal from Energy Storage System (ESS) or from any other third-party device using Modbus RTU or Digital 230V inputs. Available Energy States There are 8 energy states available.
  • Page 113: Digital Input For Energy Saving (Ess, Smart Grid)

    ACCESSORIES INSTALLATION Digital Input for energy saving (ESS, Smart Grid) This product provides two digital inputs (TB_SG1 / TB_SG2) that can be used to switch between energy states when not using Modbus RTU (CN-COM). Available Energy States There are 8 energy states available in total. Four different states can be triggered using the 230V-inputs –...
  • Page 114: 2Way Valve

    ACCESSORIES INSTALLATION 2Way Valve 2way valve is required to control water flow while cooling operation. Role of 2way valve is to cut off water flow into under floor loop in cooling mode when fan coil unit is equipped for cooling operation.
  • Page 115 ACCESSORIES INSTALLATION WARNING Wiring • Normal Open type should be connected to wire (NO) and wire (N) for valve opening in cooling mode. • Normal closed type should be connected to wire (NC) and wire (N) for valve closing in cooling mode.
  • Page 116: 3Way Valve(A)

    ACCESSORIES INSTALLATION 3Way Valve(A) 3Way Valve(A) is required to operate DHW water tank. Role of 3way valve is flow switching between under floor heating loop and water tank heating loop. Plus, it is required to operate 3 party boiler. General Information supports following 3way valve.
  • Page 117: 3Way Valve(B)

    ACCESSORIES INSTALLATION 3Way Valve(B) 3way valve(B) is required to operate Solar thermal system. Role of 3way valve is flow switching between open and close mode of the solar circuit. General Information supports following 3way valve. Type Power Operating Mode Supported Selecting Flow A between SPDT...
  • Page 118: Electric Heater

    ACCESSORIES INSTALLATION Electric Heater How to Pipe Electric Heater Follow below procedures Step 1 ~ Step 4. Step 1. Uncover the electric heater accessory. Step 2. Check the diameter of pre-installed pipes of unit. Step 3. If the diameter of pre-installed pipes is different from diameter of electric heater accessory kit, it is necessary to reduce or expand pipe's diameter.
  • Page 119 ACCESSORIES INSTALLATION Terminal Block Information Symbols used below pictures are as follows : - L, L1, L2 : Live (220-240 V~) - N : Neutral (220-240 V~) - R, S, T : Live (380-415 V 3N~) - BR : Brown, WH : White, BL : Blue, BK : Black <1Ø...
  • Page 120 ACCESSORIES INSTALLATION How to Wire Electric Heater - For 3 Series Follow below procedures Step 1 ~ Step 4. Step 1. Uncover the electric heater accessory. Step 2. Find the terminal block and connect wires. Refer to the installation manual of the electric heater.
  • Page 121 ACCESSORIES INSTALLATION Step 4. Connect power supply cable to terminal block 2. When Tightening the power cable on terminal block, Be careful to prevent a shock or injury. Terminal Block 2 (In 1Ø Backup Heater) Terminal Block 2 (In 3Ø Backup Heater) 1(L) 2(N) 1(R)
  • Page 122 ACCESSORIES INSTALLATION - For 4 Series Follow below procedures Step 1 ~ Step 4. Step 1. Uncover the electric heater accessory. Step 2. Find the terminal block and connect wires. (Wires are field-supplied item.) Step 3. Connect terminal block ports of unit and electric heater accessory. Indoor PCB HEATER 1 HEATER 2 COMMON...
  • Page 123 ACCESSORIES INSTALLATION (3Ø 6 kW) Terminal Block 2 (In Backup Heater) 1(L) 2(N) 3(T) A(A1) A(A2) Power Supply ELECTRIC HEATER A 3Ø 380-415 V, 50 HZ (SIGNAL) Power supply COMMON 3PHASE HEATER 1 HEATER 2 Step 4. Connect power supply cable to terminal block 2. Terminal Block 2 (In 1Ø...
  • Page 124: Typical Installation Example

    ACCESSORIES INSTALLATION Typical Installation Example (Backup heater for Monobloc) Floor heating + Backup Heater (Only Heating) [Outdoor] [Mech. Room] [Room] Backup Heater Collector Collector Product Buffer Tank Filter Safety Valve 2 Way Valve (Signal) Thermostatic Valve 2 Way Valve (Manual) Remote Air vent Control...
  • Page 125 ACCESSORIES INSTALLATION How to Install 3way Valve for Backup Heater Bypass Follow below procedures Step 1 ~ Step 2. Step 1. Uncover front cover of the unit. Step 2. Find terminal block and connect wire as below. When Tightening the connect wire on terminal block, Be careful to prevent a shock or injury. (230 VAC) - For 3 Series WARNING...
  • Page 126: Final Check

    ACCESSORIES INSTALLATION Final check Check point Description - Check if the shut-off valves should be assembled with Connection of Water Water inlet and outlet pipe of the unit Inlet/Outlet - Check the location of the water inlet/outlet water pipe - Check the pressure of supplying water by using pressure gage inside the unit Hydraulic pressure - Pressure of Supplying water should be Under 3.0 bar...
  • Page 127: Configuration

    CONFIGURATION CONFIGURATION is designed to satisfy various installation environment, it is important to set up system correctly. If not configured correctly, improper operation or degrade of performance can be expected. - For 3 Series DIP Switch Setting CAUTION Turn off electric power supply before setting DIP switch •...
  • Page 128: Dhw Tank

    CONFIGURATION DIP Switch Information Option Switch 2 Description Setting Default Unit + Outdoor unit is installed Unit + Outdoor unit + DHW tank Accessory installation is installed information Unit + Outdoor unit + DHW tank + Solar thermal system is installed Heating Only Cycle Heating &...
  • Page 129: Option Switch 3

    CONFIGURATION Option Switch 3 Description Setting Default Remote sensor is not installed Remote Air Sensor Remote sensor is installed Antifreezing solution not using mode ANTIFREEZE Antifreezing solution using mode Outdoor PCB (5, 7, 9 kW) OFF is selected ON is selected Outdoor PCB (12, 14, 16 kW) OFF is selected ON is selected...
  • Page 130 CONFIGURATION DIP Switch Information Description Setting Default Normal Low Noise Mode Low Noise Mode Limited Low Noise Mode Max Mode Peak Control Step 1 - To limit maximum current Peak Control (Power saving) Peak Control Step 2 - To limit maximum current (Power saving) h Only DIP Switch no.
  • Page 131 CONFIGURATION - For 4 Series DIP Switch Setting CAUTION Turn off electric power supply before setting DIP switch • Whenever adjusting DIP switch, turn off electric power supply to avoid electric shock. Indoor PCB OFF is selected ON is selected...
  • Page 132: Accessory Installation Information

    CONFIGURATION DIP Switch Information Option Switch 2 Description Description Setting Setting Default Default Heat pump is installed (Heating(Cooling) circuit only) Heat pump + DHW tank Accessory installation is installed information Heat pump + DHW tank + Solar thermal system is installed Heating Only Cycle Heating &...
  • Page 133 CONFIGURATION Option Switch 1 Description Description Setting Setting Default Default As Master (LG extension modules) MODBUS Communication Type As Slave (3rd party controller) MODBUS Function Unified Open Protocol Antifreeze agent is not used Antifreeze Agent Antifreeze agent is used * * Possibility to allow colder water temperature by setting.
  • Page 134 CONFIGURATION DIP Switch Information Description Setting Default Normal Low Noise Mode Low Noise Mode Limited Low Noise Mode Max Mode Peak Control Step 1 - To limit maximum current Peak Control (Power saving) Peak Control Step 2 - To limit maximum current (Power saving) h Only DIP Switch no.
  • Page 135 CONFIGURATION NOTE Emergency Operation • Definition of terms - Trouble : a problem which can stop system operation, and can be resumed temporally under limited operation without certificated professional's assist. - Error : problem which can stop system operation, and can be resumed only after certificated professional's check.
  • Page 136 CONFIGURATION NOTE • Duplicated trouble : Option trouble with slight or heavy trouble - If option trouble is occurred with slight (or heavy) trouble at the same time, the system puts higher priority to slight (or heavy) trouble and operates as if slight (or heavy) trouble is occurred.
  • Page 137: Service Setting

    SERVICE SETTING SERVICE SETTING How to enter service setting To enter the menu displayed at the bottom, you need to enter the service setting menu as follows. • In the menu screen, press [<,>(left/right)] button to select the setting category, and press [OK] button to move to the setting list.
  • Page 138: Service Contact

    SERVICE SETTING Service Contact Check and input the service center phone number that you can call when there is service issue. • In the service setting list, select the service contact point and press [OK] button to move to the detail screen.
  • Page 139: Model Information

    SERVICE SETTING Model Information Check product and capacity information to which the remote controller is connected. • In the service setting list, select model information category, and press [OK] button to move to the detail screen. • The unit capacity - 1 kWh = 1 kBtu * 0.29307 kWh is the result calculated based on Btu, There may be a small difference between calculated and actual capacity.
  • Page 140: Rmc Version Lnformation

    SERVICE SETTING RMC Version lnformation View the remote controller software version. • In the service setting list, select the RMC version information and press [OK] button to move to the detail screen...
  • Page 141: Open Source License

    SERVICE SETTING Open Source License View the remote controller’s open source license. • In the service setting list, select the open source license category, and press [OK] button to move to the detail screen.
  • Page 142: Installer Setting (For 3 Series)

    It must be set by the installation specialist with the installation license, and if it is installed or changed without installation license, all problems caused will be the responsibility of the installer, and may void the LG warranty. • In the menu screen, press [<,>(left/right)] button to select the setting category, and press [∧(up)] button for 3 seconds to enter the password input screen for the installer setting.
  • Page 143: Installer Setting (For 3 Series)

    INSTALLER SETTING Installer setting (For 3 Series) • You can set the product user functions. • Some functions may not be displayed/operated in some product types. Function Description 3 Minutes Delay Factory use only Selection for setting temperature as air temperature or leaving water Select Temperature Sensor temperature or air+leaving water temperature Dry contact function is the function that can be used only when the...
  • Page 144 INSTALLER SETTING Function Description TH on/off Variable, cooling air Cooling air temperature TH On / Off Type setting TH on/off Variable, cooling Cooling Water Outlet Temperature TH On / Off Type Water At the leaving water control in heating mode, the control reference Heating temp.
  • Page 145: Minutes Delay

    INSTALLER SETTING 3 Minutes Delay Temporarily eliminates the 3-minute delay function of the outdoor unit Comp - Factory use only • In the installer setting list, select 3 Minutes Delay category, and press [OK] button to move to the detail screen.
  • Page 146: Select Temperature Sensor

    INSTALLER SETTING Select Temperature Sensor The product can be operated according to air temperature or leaving water temperature. The selection for setting temperature as air temperature or leaving water temperature is determined. • In the installer setting list, Select Temperature Sensor category, and press [OK] button to move to the detail screen.
  • Page 147: Dry Contact Mode

    INSTALLER SETTING Dry Contact Mode Dry contact function is the function that can be used only when the dry contact devices is separately purchased and installed. • Change setting values using [<,>(left/right)] button. Value Auto manual NOTE For dry contact mode related detail functions, refer to the individual dry contact manual. What is dry contact? It means the contact point signal input when the hotel card key, human body detection sensor, etc.
  • Page 148: Central Control Address

    INSTALLER SETTING Central Control Address When connecting the central control, set the central control address of the unit. • In the installer setting list, select Central Control Address category, and press [OK] button to move to the detail screen. NOTE Enter address code as hexadecimal value Front: Central Control Gr.
  • Page 149: Pump Test Run

    INSTALLER SETTING Pump test run The pump test run is the function to test run by operating the water pump. This function can be used for air vents / flow sensors and others. • In the installer setting list, Pump Test run category, and press [OK] button to move to the detail screen.
  • Page 150: Air Cooling Set Temp

    INSTALLER SETTING Air cooling set temp Determine cooling setting temperature range when air temperature is selected as setting temperature. • In the installer setting list, select Air cooling set temp category, and press [OK] button to move to the detail screen. Value Default Range...
  • Page 151: Water Cooling Set Temp

    INSTALLER SETTING Water cooling set temp Determine cooling setting temperature range when leaving water temperature is selected as setting temperature. • In the installer setting list, select water cooling set temp category, and press [OK] button to move to the detail screen. Value Default Range...
  • Page 152: Air Heating Set Temp

    INSTALLER SETTING Air heating set temp Determine heating setting temperature range when air temperature is selected as setting temperature • In the installer setting list, select Air heating set temp. category, and press [OK] button to move to the detail screen. Value Default Range...
  • Page 153: Water Heating Set Temp

    INSTALLER SETTING Water heating set temp Determine heating setting temperature range when leaving water temperature is selected as setting temperature • In the installer setting list, select Water heating set temp. category, and press [OK] button to move to the detail screen. Value Default Range...
  • Page 154: Dhw Set Temp

    INSTALLER SETTING DHW set temp Determine heating setting temperature range when DHW temperature is selected as setting temperature • In the installer setting list, select DHW set temp. category, and press [OK] button to move to the detail screen. Value Default Range Min.
  • Page 155: Screed Drying

    INSTALLER SETTING Screed drying This function is a unique feature of AWHP that, when AWHP is installed in a new concrete structure, controls the specific temperature floor heating out temperature for a certain period of time to cure the floor cement. •...
  • Page 156 INSTALLER SETTING NOTE • During Screed drying operation, button input except for installer function and temperature display is restricted. • When the power is applied again after a power outage during product operation, the product operation state before power failure is remembered and the product is automatically operated.
  • Page 157: Heater On Temperature

    INSTALLER SETTING Heater on temperature Depending on local climatic conditions, it is necessary to change the temperature condition in which electric heater turns on / off. • In the installer setting list, Heater on temperature category, and press [OK] button to move to the detail screen.
  • Page 158 INSTALLER SETTING NOTE • Heater on temperature Using Half capacity of electric heater : when DIP Switch No. 6 and 7 is set as ‘OFF-ON’ : - Example : If Heater on temperature is set as ‘-1’ and DIP switch No 6. and 7 is set as ‘OFF-ON’, then half capacity of electric heater will start operation when outdoor air temperature is below -1 °C and current leaving water temperature or room air temperature is much belower than target leaving water temperature or target room air temperature.
  • Page 159: Water Supply Off Temp. During Cooling

    INSTALLER SETTING Water supply off temp. during cooling Determine leaving water temperature when the unit is turned off. This function is used for preventing condensation on the floor in cooling mode • In the installer setting list, select Water supply off temp. during cooling category, and press [OK] button to move to the detail screen.
  • Page 160 INSTALLER SETTING - Stop temp. : cut-off temp. Stop temp. is valid when FCU is set as ‘Use’. - FCU : determines if FCU is installed or not. - Example : If Stop temp. is set as ‘10’ and FCU is ’Use’ and actually FCU is NOT installed in the water loop, the unit stop operation in cooling mode when the leaving water temperature is below 10 °C.
  • Page 161: Tank Disinfection Setting

    INSTALLER SETTING Tank disinfection setting 1, 2 • Disinfection operation is special DHW tank operation mode to kill and to prevent growth of legionella inside the tank. - Disinfection active : Selecting enable or disable of disinfection operation. - Start date : Determining the date when the disinfection mode is running. - Start time : Determining the time when the disinfection mode is running.
  • Page 162: Tank Setting1

    INSTALLER SETTING Tank setting1 • In the installer setting list, select tank setting 1 category, and press [OK] button to move to the detail screen. Value Default Range Min Temp. 5 °C 1 ~ 30 °C Max outdoor temp. 55 °C 40 ~ 58 °C NOTE "Max outdoor temp."...
  • Page 163: Tank Setting2

    INSTALLER SETTING Tank setting2 • In the installer setting list, select tank setting 2 category, and press [OK] button to move to the detail screen. Value Default Range Hysteresis 3 °C 2 ~ 4 °C Heating priority Floor heating / DHW...
  • Page 164 INSTALLER SETTING • Tank setting 1, 2 Descriptions for each parameters are as following. - Min temp. : temperature gap from Max outdoor temp. - Max outdoor temp. : maximum temperature generated by AWHP compressor cycle. - Example : If Min temp. is set as ‘5’ and Max outdoor temp. is set as ’48’, then Session A (see the graph) will be started when the water tank temperature is below 43 °C….
  • Page 165: Heater Priority

    INSTALLER SETTING Heater priority • Heater priority: It is decided whether to use the boost heater for DHW operation and the backup heater for floor heating at the same time by condition. • Example: If the heater priority is set to 'Main+Boost heater ON', the backup heater and boost heater are turned on/off according to the control logic.
  • Page 166: Dhw Time Setting

    INSTALLER SETTING DHW time setting Determine following time duration : operation time of DHW tank heating, stop time of DHW tank heating, and delay time of DHW tank heater operating. - Active time : This time duration defines how long time DHW tank heating can be continued. - Stop time : This time duration defines how long time DHW tank heating can be stopped.
  • Page 167 INSTALLER SETTING Value Default Range Active time 30 min 5~95 min Stop time 180 min 0~600 min Boost heater delay time 20 min 20~95 min...
  • Page 168: Th On/Off Variable, Heating Air

    INSTALLER SETTING TH on/off Variable, heating air It is a function to adjust the heating air temperature Thermal On / Off temperature according to the field environment in preparation for heating or heating claim. • You can set the following setting values using [<,>(left/right)] button. Description Value TH On...
  • Page 169: Th On/Off Variable, Heating Water

    INSTALLER SETTING TH on/off Variable, heating water It is a function to adjust the heating water temperature Thermal On / Off temperature according to the field environment in preparation for heating or heating claim. • You can set the following setting values using [<,>(left/right)] button. Description Value TH On...
  • Page 170: Th On/Off Variable, Cooling Air

    INSTALLER SETTING TH on/off Variable, cooling air It is a function to adjust the cooling air temperature Thermal On / Off temperature according to the field environment in preparation for cooling or cooling claim. • You can set the following setting values using [<,>(left/right)] button. Description Value TH On...
  • Page 171: Th On/Off Variable, Cooling Water

    INSTALLER SETTING TH on/off Variable, cooling water It is a function to adjust the cooling water temperature Thermal On / Off temperature according to the field environment in preparation for cooling or cooling claim. • You can set the following setting values using [<,>(left/right)] button. Description Value TH On...
  • Page 172: Heating Temp. Setting

    INSTALLER SETTING Heating temp. setting • At the leaving water control in heating mode, the control reference water temperature position setting. - If the air / leaving water temperature selection setting is set to leaving water temperature • Change setting values using [<,>(left/right)] button Value Outlet (Default) Inlet...
  • Page 173: Cooling Temp. Setting

    INSTALLER SETTING Cooling temp. setting • At the leaving water control in cooling mode, the control reference water temperature position setting - If the air / leaving water temperature selection setting is set to leaving water temperature • Change setting values using [<,>(left/right)] button Value Outlet (Default) Inlet...
  • Page 174: Pump Setting In Heating

    INSTALLER SETTING Pump setting in heating • It is a function to help the water pump's mechanical life by putting the water pump's rest time • Installer setting function to set water pump operation / delay time option in heating mode •...
  • Page 175: Pump Setting. In Cooling

    INSTALLER SETTING Pump setting. in cooling • It is a function to help the water pump's mechanical life by putting the water pump's rest time • installer setting function to set water pump operation / delay time option in cooling mode •...
  • Page 176: Forced Operation

    INSTALLER SETTING Forced operation • If the product is not used for a long time, the pump will be forced to operate to prevent pump failure and PHEX freezing. • Water pump off After 20 consecutive hours, disable / enable the logic that drives the water pump by itself.
  • Page 177: Cn_Cc

    INSTALLER SETTING CN_CC It is the function to set the usage of the unit’s CN_CC port. • Change setting values using [<,>(left/right)] button Value Description When power is applied to the product, the unit when the contact point D/C Automatic is on in Dry Contact installed state recognizes Dry Contact installation D/C Not Installed Do not use (install) Dry Contact...
  • Page 178: Pump Capacity

    INSTALLER SETTING Pump Capacity It is a function to enable installer to control Pump capacity application model. • In the installer setting list, select Pump Capacity category, and press [OK] button to move to the detail screen. • △T Control - This function automatically adjusts the pump capacity during heating operation.
  • Page 179: Seasonal Auto Temp

    INSTALLER SETTING Seasonal auto temp It is the function to set the operation reference value in Seasonal Auto mode. • In the installer setting list, select Seasonal auto temp category, and press [OK] button to move to the detail screen. Function Description Range...
  • Page 180 INSTALLER SETTING In this mode, setting temperature will follow outdoor temperature automatically. This mode adds the cooling season function to the conventional weather dependent operation mode. Auto-Adjustable Heating Target Temperature Cooling Water Temp Target: LW/EW1 Room Air Temp Target: RA1 Temperature profile of weather dependent operation Water Temp Target: LW/EW2...
  • Page 181: Modbus Address

    INSTALLER SETTING Modbus Address It is function to set the address of the Modbus device that is externally linked to the product. Modbus address setting function is available from indoor unit. • In the installer setting list, select Modbus Address , and press [OK] button to move to the detail screen.
  • Page 182: Cn_Ext

    INSTALLER SETTING CN_EXT It is a function to control external input and output according to DI type set by customer using CN-EXT Port. • In the installer setting list, select CN-EXT Port category, and press [OK] button to move to the detail screen.
  • Page 183: Anti-Freezing Temperature

    INSTALLER SETTING Anti-freezing Temperature Anti-freeze temperature setting is available in installer mode. It prevents frostbite from happening In the range of -25 to -5 degree celsius. Make sure to use this function only when antifreeze is added. • Change setting values using [<, >(left/right)] button NOTE To use this function, the antifreeze short pin(CN_FLOW2, Black) of indoor PCB must be remove and switch No.2 in option SW 3 must be on.
  • Page 184: Add Zone

    INSTALLER SETTING Add Zone Function to set whether or not to use a installed 2nd circuit function using mixing kit. You can set valve closing time[seconds] and hysteresis temperature[ °C] on screen by yourself. Value Default Range Valve Closing Time 240 s 60 ~ 999 s Hysteresis...
  • Page 185: Use External Pump

    INSTALLER SETTING Use External Pump This function can be set to control the external water pump. • In the installer setting list, select Use External Pump category, and press [OK] button to move to the detail screen. • Heating/Cooling You can use this feature when you have installed a 3 Way valve to switch the water flow between the underfloor and the water tank.
  • Page 186 INSTALLER SETTING Party Boiler This function is to configure the 3rd party boiler to be controlled. If the status of this function is “Use”, you can choose control mode of boiler, Auto or Manual. If the mode of this function is set to “Manual”, you can set temperature of the boiler and hysteresis, respectively.
  • Page 187: Meter Interface

    INSTALLER SETTING Meter Interface It is the function that can check the status of energy and power on screen. It collects and calculates power or calorie data to create data for energy monitoring and energy warning alarm pop-ups. This function can be activated in installer mode. There are 2 options, modbus address and unit, in this function.
  • Page 188: Pump Prerun/Overrun

    INSTALLER SETTING Pump Prerun/Overrun Pump Prerun operates to ensure sufficient flow before the compressor is operated. This is a function that allows heat exchange to work smoothly. Pump Overrun removes latent heat from the PHEX by circulating the water flow when the comp is stopped.
  • Page 189: Solar Thermal System

    INSTALLER SETTING Solar Thermal System It is function to set operation reference value in Solar Thermal System. In the installer setting list, select Solar thermal system category, and press [OK] button to move to the detail screen. NOTE To use this function, switch No.2 of option switch 2 must be turned ON and No.3 of option switch 2 must be turned OFF.
  • Page 190 INSTALLER SETTING Descriptions for each parameters are as following. • Solar collector set temp - Min temp : It is the minimum solar collector temperature at which the solar thermal system can operate. - Max temp : It is the maximum solar collector temperature at which the solar thermal system can operate •...
  • Page 191: Energy State

    INSTALLER SETTING Energy state This function is to control the product according to the energy state. When the charged state of ESS is transmitted, it changes the target temperature of heating, cooling and DHW by setting value according to energy state. Select either Signal Mode or Modbus Mode according to the connection type between the product and the ESS.
  • Page 192 INSTALLER SETTING Division Value Default Range Division Value Default Range Use / Not Use Use / Not Use Heat Temp. fixed Heat Temp. +5 °C 0 ~ 30 °C ES 1 ES 5 Cool Temp. fixed Cool Temp. -5 °C -30 ~ 0 °C DHW Temp.
  • Page 193 INSTALLER SETTING When Signal Mode of EES use type is selected, press the Digital Input Assignment button to set the energy state according to the input signal. Input Signal Output state Value TB_SG1 TB_SG2 Default Range fixed fixed ES3-ES8...
  • Page 194: Data Logging

    INSTALLER SETTING Data logging It is the function to set the operation reference value in Seasonal Auto mode. • In the installer setting list, select Data logging category, and press [OK] button to move to the detail screen. NOTE Error history lookup range: 50 Error history information Item: date, time, mode (including Off), set temperature, incoming temperature, outgoing temperature, room temperature, Hot water operation / stop, Hot water set...
  • Page 195: Password Initialization

    INSTALLER SETTING Password Initialization It is the function to initialize (0000) when you forgot the password set in the remote controller. • In the installer setting list, select the password initialization setting category, and press [OK] button to move to the detail screen. •...
  • Page 196: Installer Setting (For 4 Series)

    Function to use 2 remote control environment Function to save the environment settings of the LG Therma V Configuration product for use in LG Therma V Configurator through SD Card. Water pump off After 20 consecutive hours, disable / Forced operation...
  • Page 197 INSTALLER SETTING Segmentation Functions Description At the water control in cooling mode, the control Cooling temp. setting reference water temperature position setting Adjusting range of 'Setting Air Temperature' in Air cooling set temp. cooling mode Adjusting range of 'Setting Leaving Water Water cooling set temp.
  • Page 198 INSTALLER SETTING Segmentation Functions Description Dry contact function is the function that can be Dry Contact Mode used only when the dry contact devices is separately purchased and installed. When connecting the central control, set the Central Control Address central control address of the unit. It is the function to set whether to install (use) Dry Contact.
  • Page 199: Select Temperature Sensor

    INSTALLER SETTING Select Temperature Sensor The product can be operated according to air temperature or water temperature. The selection for setting temperature as air temperature or water temperature is determined. • In the installer setting list, Select Temperature Sensor category, and press [OK] button to move to the detail screen.
  • Page 200: Use Heating Tank Heater

    INSTALLER SETTING Use Heating Tank Heater This is a function to change the set value for the operation of the hot water tank heater, such as heating tank heater use /not use and heater delay time. • In the installer setting list, Select Configuration category, and press [OK] button to move to the detail screen.
  • Page 201: Mixing Circuit

    INSTALLER SETTING Mixing Circuit Function to set whether or not to use a installed mixing circuit function using mixing kit. Value Default Not Use / Heat / Cool Not Use You can set valve closing time[s] and hysteresis temperature[°C] on screen by yourself. Setting the cut-off temperature protects the water from flowing over the cut-off temperature in the mixing circuit during heating operation.
  • Page 202 INSTALLER SETTING Installer setting function to set water mixing pump operation / delay time option in heating/cooling mode Value Default Range Time Setting / Continuous Type Time Setting Operation 3 min 1 ~ 60 min 3 min 1 ~ 60 min * When Continuous Operation is selected, On, Off is disabled.
  • Page 203: Use External Pump

    INSTALLER SETTING Use External Pump This function can be set to control the external water pump. • In the installer setting list, select Use External Pump category, and press [OK] button to move to the detail screen. • Heating/Cooling You can use this feature when you have installed a 3 Way valve to switch the water flow between the underfloor and the water tank.
  • Page 204: Rmc Master/Slave

    INSTALLER SETTING RMC master/slave This function can be select Master/Slave on remote controller to use 2 Remote Control environment • In the Installer setting list, and select RMC master/slave setting category, and press [<,>(left/right)] button to following setting values. Value Master (Default) Slave...
  • Page 205: Lg Therma V Configuration

    INSTALLER SETTING LG Therma V Configuration This function can be set to save the environment settings of the product for use in LG Therma V Configurator through SD Card. • In the Installer setting list, and select LG Therma V Configuration setting category, and press [OK] button to move to the detail screen.
  • Page 206: Forced Operation

    INSTALLER SETTING Forced operation • If the product is not used for a long time, the pump will be forced to operate to prevent pump failure and PHEX freezing. • Water pump off After 20 consecutive hours, disable / enable the logic that drives the water pump by itself.
  • Page 207: Pump Prerun/Overrun

    INSTALLER SETTING Pump Prerun/Overrun Pump Prerun operates to ensure sufficient flow before the compressor is operated. This is a function that allows heat exchange to work smoothly. Pump Overrun removes latent heat from the PHEX by circulating the water flow when the comp is stopped.
  • Page 208: Water Flow Control

    INSTALLER SETTING Water Flow Control This function controls the water flow by controlling the water pump. Select the way to control the water pump and set the target value • In the installer setting list, select Configuration category, and press [OK] button to move to the detail screen.
  • Page 209: Energy Monitoring

    This function can be set to use energy monitoring function of unit. • Change setting values using [<,>(left/right)] button. Value Default Range Energy Monitoring Use/Not Use LG 1Ø / LG 3Ø / Type LG 1Ø EXTERNAL Electric Heater Setting Heater Capacity 6 kW...
  • Page 210: Anti-Freezing Option 1

    INSTALLER SETTING Anti-Freezing Option 1 This function is to select whether to use Type1 or Type2 to prevent freezing when the remote control is turned off. • Change setting values using [<,>(left/right)] button. Value Type1(Default) Type2 CAUTION If the function is set to Type 2, there is a risk of freezing. Function Detection Case...
  • Page 211: Password Reset

    INSTALLER SETTING Password Reset It is the function to initialize (0000) when you forgot the password set in the remote controller. • In the installer setting list, select the password Reset setting category, and press [OK] button to move to the detail screen. •...
  • Page 212: Screed Drying

    INSTALLER SETTING Screed drying This function is a unique feature of AWHP that, when AWHP is installed in a new concrete structure, controls the specific temperature floor heating out temperature for a certain period of time to cure the floor cement. •...
  • Page 213 INSTALLER SETTING NOTE • During Screed drying operation, button input except for installer function and temperature display is restricted. • When the power is applied again after a power outage during product operation, the product operation state before power failure is remembered and the product is automatically operated.
  • Page 214: Heater On Temperature

    INSTALLER SETTING Heater on temperature Depending on local climatic conditions, it is necessary to change the temperature condition in which backup heater turns on / off. • In the installer setting list, Heater on temperature category, and press [OK] button to move to the detail screen.
  • Page 215: Air Heating Set Temp

    INSTALLER SETTING Air heating set temp. Determine heating setting temperature range when air temperature is selected as setting temperature • In the installer setting list, select Air heating set temp. category, and press [OK] button to move to the detail screen. Value Default Range...
  • Page 216: Water Heating Set Temp

    INSTALLER SETTING Water heating set temp. Determine heating setting temperature range when water temperature is selected as setting temperature. • In the installer setting list, select Water heating set temp. category, and press [OK] button to move to the detail screen. Value Default Range...
  • Page 217: Hysteresis Room Air(Heating)

    INSTALLER SETTING Hysteresis Room Air(Heating) It is a function to adjust the heating air temperature Thermal On / Off temperature according to the field environment in order to offer optimized heating operation. • In the Installer setting list, and select Hysteresis Room Air(Heating) category, and press [OK] button to move to the detail screen.
  • Page 218: Hysteresis Heating Water

    INSTALLER SETTING Hysteresis Heating Water It is a function to adjust the heating water temperature Thermal On / Off temperature according to the field environment in order to offer optimized DHW heating operation. • In the Installer setting list, and select Hysteresis Heating Water category, and press [OK] button to move to the detail screen.
  • Page 219: Heating Temp. Setting

    INSTALLER SETTING Heating temp. setting • At the water control in heating mode, the control reference water temperature position setting - If the air / leaving water temperature selection setting is set to leaving water temperature • Change setting values using [<,>(left/right)] button •...
  • Page 220: Pump Setting In Heating

    INSTALLER SETTING Pump setting in heating • It is a function to help the water pump's mechanical life by putting the water pump's rest time • Installer setting function to set water pump on/off interval option during thermo off condition in heating mode.
  • Page 221: Air Cooling Set Temp

    INSTALLER SETTING Air cooling set temp. Determine cooling setting temperature range when air temperature is selected as setting temperature. • In the installer setting list, select Air cooling set temp category, and press [OK] button to move to the detail screen. Value Default Range...
  • Page 222: Water Cooling Set Temp

    INSTALLER SETTING Water cooling set temp. Determine cooling setting temperature range when water temperature is selected as setting temperature. • In the installer setting list, select water cooling set temp category, and press [OK] button to move to the detail screen. Value Default Range...
  • Page 223: Water Supply Off Temp. During Cooling

    INSTALLER SETTING Water supply off temp. during cooling Determine the leaving water temperature which blocks the flow into underfloor coil in cooling mode. This function is used for preventing condensation on the floor in cooling mode • In the installer setting list, select Water supply off temp. during cooling category, and press [OK] button to move to the detail screen.
  • Page 224 INSTALLER SETTING - Stop temp. : cut-off temp. Stop temp. is valid when FCU is set as ‘Use’. - FCU : determines if FCU is installed or not. - Example : If FCU is set as ’Use’, Stop temp. setting is disabled. However, if actually FCU is NOT installed in the water loop, the unit operates continuously in cooling mode until water temperature meets desired temperature.
  • Page 225: Hysteresis Room Air(Cooling)

    INSTALLER SETTING Hysteresis Room Air(Cooling) It is a function to adjust the cooling air temperature Thermal On / Off temperature according to the field environment in order to offer optimized cooling operation. • In the Installer setting list, and select Hysteresis Room Air(Cooling) setting category, and press [OK] button to move to the detail screen.
  • Page 226: Hysteresis Cooling Water

    INSTALLER SETTING Hysteresis Cooling Water It is a function to adjust the cooling water temperature Thermal On / Off temperature according to the field environment in order to offer optimized cooling operation. • In the Installer setting list, and select Hysteresis Cooling Water setting category, and press [OK] button to move to the detail screen.
  • Page 227: Cooling Temp. Setting

    INSTALLER SETTING Cooling temp. setting • At the water control in cooling mode, the control reference water temperature position setting - If the air / leaving water temperature selection setting is set to leaving water temperature • Change setting values using [<,>(left/right)] button. •...
  • Page 228: Pump Setting In Cooling

    INSTALLER SETTING Pump setting in cooling • It is a function to help the water pump's mechanical life by putting the water pump's rest time • Installer setting function to set water pump on/off interval option during thermo off condition in cooling mode.
  • Page 229: Seasonal Auto Temp

    INSTALLER SETTING Seasonal auto temp. It is the function to set the operation reference value in Seasonal Auto mode. • In the installer setting list, select Seasonal auto temp category, and press [OK] button to move to the detail screen.
  • Page 230 INSTALLER SETTING Default Default Function Description Range Boundary (Circuit1) (Circuit2) Outdoor1,Heat Heating lower ambient Out1 ≤ Out2-1 -10 °C (Out1) temp -25 ~ 35 °C Out2 ≥ Out1 +1 Outdoor2,Heat Heating higher ambient 18 °C Out2 ≤ Out3 -5 (Out2) temp Out3 ≥...
  • Page 231 INSTALLER SETTING In this mode, setting temperature will follow outdoor temperature automatically. This mode adds the cooling season function to the conventional weather dependent operation mode. Auto-Adjustable Heating Target Temperature Cooling Water Temp Target: LW/EW1 Room Air Temp Target: RA1 Temperature profile of weather dependent operation Water Temp Target: LW/EW2...
  • Page 232: Heater Priority

    INSTALLER SETTING Heater priority • Heater priority: It is decided whether to use the boost heater for DHW operation and the backup heater for floor heating at the same time by condition. • Example: If the heater priority is set to 'Main+Boost heater ON', the backup heater and boost heater are turned on/off according to the control logic.
  • Page 233: Dhw Set Temp

    INSTALLER SETTING DHW set temp. Determine heating setting temperature range when DHW temperature is selected as setting temperature • In the installer setting list, select DHW set temp. category, and press [OK] button to move to the detail screen. Value Default Range Min.
  • Page 234: Tank Disinfection Setting

    INSTALLER SETTING Tank disinfection setting 1, 2 • Disinfection operation is special DHW tank operation mode to kill and to prevent growth of legionella inside the tank. - Disinfection active : Selecting enable or disable of disinfection operation. - Start date : Determining the date when the disinfection mode is running. - Start time : Determining the time when the disinfection mode is running.
  • Page 235: Tank Setting1

    INSTALLER SETTING Tank setting1 • In the installer setting list, select tank setting 1 category, and press [OK] button to move to the detail screen. Value Default Range Min. temp. 5 °C 1 ~ 30 °C Comp. Limit Temp. 55 °C 40 ~ 58 °C NOTE "Max outdoor temp."...
  • Page 236: Tank Setting2

    INSTALLER SETTING Tank setting2 • In the installer setting list, select tank setting 2 category, and press [OK] button to move to the detail screen. Value Default Range Hysteresis 3 °C 2 ~ 4 °C Heating priority Floor heating / DHW...
  • Page 237 INSTALLER SETTING • Tank setting 1, 2 Descriptions for each parameters are as following. - Min temp. : temperature gap from Max outdoor temp. - Max outdoor temp. : maximum temperature generated by AWHP compressor cycle. - Example : If Min temp. is set as ‘5’ and Max outdoor temp. is set as ’48’, then Session A (see the graph) will be started when the water tank temperature is below 43 °C….
  • Page 238: Dhw Time Setting

    INSTALLER SETTING DHW time setting Determine following time duration : operation time of DHW tank heating, stop time of DHW tank heating, and delay time of DHW tank heater operating. - Active time : This time duration defines how long time DHW tank heating can be continued. - Stop time : This time duration defines how long time DHW tank heating can be stopped.
  • Page 239 INSTALLER SETTING Value Default Range Active time 30 min 5~95 min Stop time 30 min 0~600 min...
  • Page 240: Recirculation Time

    INSTALLER SETTING Recirculation time • It is function to set recirculation water pump on/off interval option • In the installer setting list, select Recirculation time category, and press [OK] button to move to the detail screen. Value Default Range DHW recirculation Not use Use / Not use ON Time...
  • Page 241: Solar Thermal System

    INSTALLER SETTING Solar Thermal System It is function to set operation reference value in Solar Thermal System. In the installer setting list, select Solar thermal system category, and press [OK] button to move to the detail screen. NOTE To use this function, switch No.2 of option switch 2 must be turned ON and No.3 of option switch 2 must be turned OFF.
  • Page 242 INSTALLER SETTING Descriptions for each parameters are as following. • Solar collector set temp - Min temp : It is the minimum solar collector temperature at which the solar thermal system can operate. - Max temp : It is the maximum solar collector temperature at which the solar thermal system can operate.
  • Page 243: Pump Test Run

    INSTALLER SETTING Pump test run The pump test run is to test run by operating the water pump for 1 hour. This function can be used for air purging through air vents and checking flow rate and others. • In the installer setting list, Pump Test run category, and press [OK] button to move to the detail screen.
  • Page 244: Frost Protection Temp

    INSTALLER SETTING Frost Protection Temp. This function prevents the unit from freezing. This function sets the freeze protection temperature according to the concentration injected after injecting antifreeze. Make sure to use this function only when antifreeze is added. • Change setting values using [<, >(left/right)] button. •...
  • Page 245: Dry Contact Mode

    INSTALLER SETTING Dry Contact Mode Dry contact function is the function that can be used only when the dry contact devices is separately purchased and installed. • Change setting values using [<,>(left/right)] button. Value Description Auto (Default) Automatically operation ON with release hard lock Manual Keep operation OFF with hard lock NOTE...
  • Page 246: Central Control Address

    INSTALLER SETTING Central Control Address When connecting the central control, set the central control address of the unit. • In the installer setting list, select Central Control Address category, and press [OK] button to move to the detail screen. NOTE Enter address code as hexadecimal value Front: Central Control Gr.
  • Page 247: Cn_Cc

    INSTALLER SETTING CN_CC It is the function to set the usage of the unit’s CN_CC port. • Change setting values using [<,>(left/right)] button Value Description D/C Automatic When power is applied to the product, the unit when the contact point (Default) is on in Dry Contact installed state recognizes Dry Contact installation D/C Not Installed...
  • Page 248: Lg Therma V Configuration

    INSTALLER SETTING LG Therma V Configuration This function can be set to save the environment settings of the product for use in LG Therma V Configurator through SD Card. • In the Installer setting list, and select LG Therma V Configuration setting category, and press [OK] button to move to the detail screen.
  • Page 249: Energy State

    INSTALLER SETTING Energy state This function is to control the product according to the energy state. When the charged state of ESS is transmitted, it changes the target temperature of heating, cooling and DHW by setting value according to energy state. Select either Signal Mode or Modbus Mode according to the connection type between the product and the ESS.
  • Page 250 INSTALLER SETTING Division Value Default Range Division Value Default Range Use / Not Use Use / Not Use Heat Temp. fixed Heat Temp. +5 °C 0 ~ 30 °C ES 1 ES 5 Cool Temp. fixed Cool Temp. -5 °C -30 ~ 0 °C DHW Temp.
  • Page 251 INSTALLER SETTING When Signal Mode of EES use type is selected, press the Digital Input Assignment button to set the energy state according to the input signal. Input Signal Output state Value TB_SG1 TB_SG2 Default Range fixed fixed ES3-ES8...
  • Page 252: Thermostat Control Type

    INSTALLER SETTING Thermostat control type Set the type of thermostat control. • In the Installer setting list, and select Connectivity category, and press [OK] button to move to the detail screen. Type Heat & Cool (Default) Heat & Cool / DHW...
  • Page 253: Pump Operation Time

    INSTALLER SETTING Pump operation time It is a function to show the water pump’s operation time for check mechanical life. • In the Installer setting list, and select Information category, and press [OK] button to move to the detail screen.
  • Page 254: Idu Operation Time

    INSTALLER SETTING IDU operation time It is a function to show the Indoor Unit’s operation time for check mechanical life. • In the Installer setting list, and select Information category, and press [OK] button to move to the detail screen.
  • Page 255: Modbus Address

    INSTALLER SETTING Modbus Address It is function to set the address of the Modbus device that is externally linked to the product. Modbus address setting function is available from indoor unit. • In the installer setting list, select Modbus Address , and press [OK] button to move to the detail screen.
  • Page 256: Modbus Gateway Memory Map

    INSTALLER SETTING Modbus gateway memory map Baud Rate : 9 600 bps Stop Bit : 1 stop bit Parity : None Parity Coil Register (0x01) Register Description Value explanation 00001 Enable/Disable (Heating/Cooling) 0 : Operation OFF / 1 : Operation ON 00002 Enable/Disable (DHW) 0 : Operation OFF / 1 : Operation ON...
  • Page 257 INSTALLER SETTING Holding Register (0x03) Register Description Value explanation 40001 Operation Mode 0 : Cooling / 4 : Heating / 3 : Auto 0 : Water outlet temp. control 40002 Control method (Circuit 1/2) 1 : Water inlet temp. control 2 : Room air control Target temp (Heating/Cooling) 40003...
  • Page 258 INSTALLER SETTING Input Register (0x04) Register Description Value explanation 30001 Error Code Error Code 30002 ODU operation Cycle 0 : Standby(OFF) / 1 : Cooling / 2 : Heating 30003 Water inlet temp. [0.1 °C ×10] 30004 Water outlet temp. [0.1 °C ×10] 30005 Backup heater outlet temp.
  • Page 259: Cn_Ext

    INSTALLER SETTING CN_EXT It is a function to control external input and output according to DI type set by customer using CN-EXT Port. • In the installer setting list, select CN-EXT Port category, and press [OK] button to move to the detail screen.
  • Page 260 INSTALLER SETTING Party Boiler This function is to configure the 3rd party boiler to be controlled. If the status of this function is “Use”, you can choose control mode of boiler, Auto or Manual. If the mode of this function is set to “Auto”, you can set temperature of the boiler and hysteresis, respectively.
  • Page 261: Meter Interface

    INSTALLER SETTING Meter Interface It is the function that can check the status of energy and power on screen. It collects and calculates power or calorie data to create data for energy monitoring and energy warning alarm pop-ups. This function can be activated in installer mode. There are 2 options, modbus address and unit, in this function.
  • Page 262: Current Flow Rate

    INSTALLER SETTING Current flow rate It is the function to check the current flow rate. • In the installer setting list, select Current Flow Rate category, and press [OK] button to move to the detail screen. The current flow rate can be checked. (Range : 7 ~ 80 L/min) •...
  • Page 263: Data Logging

    INSTALLER SETTING Data logging This function is to check the operation and error history. • In the installer setting list, select Data logging category, and press [OK] button to move to the detail screen. NOTE Error history lookup range: 50 Error history information Item: date, time, mode (including Off), set temperature, incoming temperature, outgoing temperature, room temperature, Hot water operation / stop, Hot water set...
  • Page 264: Commissioning

    • Refrigerant leakage degrades the performance. If leakage found, contact Installation leakage qualified LG air conditioning installation person. • While cooling operation, condensed dew can drop down to the bottom of the Drainage unit. In this case, prepare drainage treatment (for example, vessel to contain treatment condensed dew) to avoid water drop.
  • Page 265: Starting Operation

    COMMISSIONING To assure best performance of , it is required to perform periodical check and maintenance. It is recommended to proceed following check list for once a year. CAUTION Turn off the power before proceeding maintenance Category Item Check Point •...
  • Page 266: Starting Operation Flow Chart

    COMMISSIONING Starting Operation flow chart START Check whether the power cable and Operate the unit in heating mode. communication cable are completely connected Does Test operation start? Is cold water discharged for * Check the load (In/Out Temp.) more than 3 minutes ? * Check pipe length and amount of refrigerant Is there any temperature...
  • Page 267: Vacuum & Charge Of Refrigerant

    COMMISSIONING Vacuum & Charge of Refrigerant By default, the product was charged of refrigerant. Vacuum and refrigerant charge, If there is leak refrigerant. 1. Vacuum To work of vacuum action. when the leak of refrigerant. SVC Port Manifold gage Manifold valve Pressure gage Open...
  • Page 268 COMMISSIONING 2. Charge of refrigerant You should be charged after vacuum. You can see amount of refrigerant at quality label. Please to charge at cooling mode when there is not full charging. SVC Port Manifold gage Refrigerant cylinder (R32 refrigerant) Refrigerant Refrigerant cylinder...
  • Page 269: How To Drain Remaining Water In The Product

    COMMISSIONING 3. Location of SVC port UN36A (5, 7, 9 kW) UN60A (9, 12, 14, 16 kW) SVC Port SVC Port How to drain remaining water in the product CAUTION If the product is not used for a long period of time with remaining water, there is a risk of freezing in winter.
  • Page 270: Troubleshooting

    COMMISSIONING Troubleshooting operates not properly or it does not start operation, please check following list. CAUTION Turn off the power before proceeding troubleshooting Troubleshooting for Problem while Operation Problem Reason Solution • Set target temperature correctly. • Setting target temperature •...
  • Page 271 COMMISSIONING Troubleshooting for Error Code Display Title Cause of error Check point & Normal condition code Problem in remote room air sensor • Resistance: 10 kΩ at 25 centigrade Problem in refrigerant (inlet side) sensor (unplugged) → for Remote room Problem in refrigerant (outlet side) sensor air sensor •...
  • Page 272 COMMISSIONING Display Title Cause of error Check point & Normal condition code • An instant over current in the U,V,W phase - Comp lock • Instant over current - The abnormal connection of U,V,W DC PEAK • Over Rated current •...
  • Page 273 COMMISSIONING Display Title Cause of error Check point & Normal condition code • Open / Short • Bad connection of thermistor connector Problem in D-pipe • Soldered poorly • Defect of thermistor connector (Open/Short) temperature sensor • Internal circuit error •...
  • Page 274 COMMISSIONING Display Title Cause of error Check point & Normal condition code Fan RPM is less than 10 for 5 • Fan motor damage seconds from start-up operation. Fan lock error • Assembly condition abnormal Fan RPM is less than 40 in operation •...
  • Page 275 LG Electronics Inc. Single Point of Contact (EU/UK) : LG Electronics European Shared Service Center B.V. Krijgsman 1, 1186 DM Amstelveen, The Netherlands Manufacturer : LG Electronics Inc. 84, Wanam-ro, Seongsan-gu, Changwon-si, Gyeongsangnam-do, KOREA UK Importer : LG Electronics U.K. Ltd...