Electrical Data - LG LC098HV4 Engineering Manual

Single-zone four-way ceiling cassette heat pump systems 3/4 to 3-1/2 tons
Hide thumbs Also See for LC098HV4:
Table of Contents

Advertisement

Electrical Data

Table 4: Electrical Data.
Nominal
Unit Model No.
Tons
3/4
LUU097HV
1
LUU127HV
1-1/2
LUU187HV
1-1/2
LUU189HV
2
LUU247HV
3
LUU367HV
3-1/2
LUU427HV
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
RLA = Rated Load Amps.
Voltage
Hertz Voltage
Range
(Min. to Max.)
60
208 - 230
187 - 253
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as follows:
(Largest motor FLA x 2.25) + (Sum of other motor FLA) rounded down
to the nearest standard fuse size.
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
ELECTRICAL DATA
Compressor
MCA
MOP
Quantity
11.9
15
12.3
18.1
30
20
30
1
18.1
30
24.5
40
Condenser Fan Motor(s)
Compressor
Motor RLA
Condenser
Condenser Fan
(Cooling)
Fan Quantity.
9.0
13.5
1
13.5
13.5
18.0
2
Motor FLA
0.25
0.6
1.6
0.6
0.6 x 2
13

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lc128hv4Lc187hvLc188hv4Lc367hvLc427hvLc247hv

Table of Contents