LG LC098HV4 Engineering Manual page 45

Single-zone four-way ceiling cassette heat pump systems 3/4 to 3-1/2 tons
Hide thumbs Also See for LC098HV4:
Table of Contents

Advertisement

Table 23: LC367HV System Cooling Capacity Table.
Model No. /
Outdoor
Nominal Capacity
Air Temp.
(Btu/h)
(°F DB)
TC
5
35.66
10
35.61
15
35.56
20
35.51
25
35.45
30
35.40
35
35.35
40
35.30
45
35.25
50
35.20
55
35.15
60
35.10
LC367HV /
65
35.05
36,000
70
34.99
75
34.15
80
33.31
85
32.48
90
31.64
95
30.74
100
29.99
105
29.24
110
28.49
115
27.74
118
26.20
122
25.69
TC = Total Capacity (kBtu/h).
SHC: Sensible Heat Capacity (kBtu/h).
PI = Power input (KW). Power input (KW) includes compressor and fan(s).
Nominal capacity as rated 0 ft. above sea level and a 0 ft. level difference between outdoor and indoor
unit. Corresponding refrigerant piping length is accordance with standard length of each outdoor unit.
68 / 57
73 / 61
SHC
PI
TC
SHC
PI
25.73
1.18
37.87
27.18
1.60
25.92
1.22
37.82
27.38
1.65
26.11
1.25
37.77
27.58
1.69
26.29
1.28
37.71
27.77
1.74
26.48
1.32
37.66
27.97
1.78
26.66
1.35
37.60
28.17
1.83
26.85
1.38
37.55
28.36
1.87
27.03
1.42
37.49
28.55
1.92
27.21
1.45
37.44
28.75
1.96
27.40
1.48
37.39
28.94
2.01
27.58
1.52
37.33
29.13
2.05
27.76
1.55
37.28
29.32
2.10
27.94
1.58
37.22
29.51
2.14
28.12
1.61
37.17
29.70
2.19
27.66
1.72
36.32
29.25
2.26
27.18
1.82
35.47
28.79
2.33
26.69
2.07
34.63
28.31
2.53
26.18
2.32
33.79
27.81
2.73
25.91
2.57
32.88
27.56
2.91
25.21
2.70
32.13
26.87
2.97
24.52
2.82
31.38
26.17
3.03
23.68
2.74
30.63
25.33
2.86
22.97
2.46
29.88
24.61
2.49
21.90
2.18
28.26
23.49
2.15
21.53
2.09
27.71
23.10
2.04
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
PERFORMANCE DATA
Indoor Air Temp. °F DB / °F WB
77 / 64
80 / 67
TC
SHC
PI
TC
SHC
40.09
27.98
1.74
41.69
26.87
40.03
28.18
1.79
41.63
27.07
39.97
28.39
1.83
41.57
27.26
39.92
28.59
1.88
41.51
27.46
39.86
28.79
1.93
41.45
27.65
39.80
28.99
1.98
41.39
27.85
39.74
29.19
2.03
41.33
28.04
39.69
29.39
2.08
41.27
28.23
39.63
29.59
2.13
41.21
28.42
39.57
29.79
2.18
41.15
28.61
39.51
29.99
2.22
41.09
28.80
39.46
30.18
2.27
41.03
28.99
39.40
30.38
2.32
40.97
29.18
39.34
30.58
2.37
40.91
29.37
38.49
30.15
2.43
40.05
28.98
37.64
29.71
2.50
39.20
28.58
36.79
29.24
2.68
38.35
28.15
35.94
28.77
2.86
37.50
27.72
35.02
28.55
3.02
36.00 27.11
34.27
27.87
3.04
35.53
26.69
33.52
27.19
3.06
35.07
26.27
32.77
26.35
2.85
34.32
25.49
32.02
25.65
2.43
33.57
24.84
30.31
24.50
2.05
31.80
23.74
29.74
24.11
1.93
31.21
23.37
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF
wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
The shaded table rows indicate reference data. When operating at this temperature, these values can
be different if the system is not running consistently.
Cooling Capacity Tables
86 / 72
PI
TC
SHC
PI
TC
1.76
44.52
27.10
1.77
46.73
1.81
44.45
27.30
1.82
46.67
1.86
44.39
27.49
1.87
46.60
1.91
44.33
27.69
1.92
46.53
1.96
44.26
27.89
1.97
46.46
2.01
44.20
28.08
2.01
46.40
2.06
44.13
28.27
2.06
46.33
2.11
44.07
28.47
2.11
46.26
2.16
44.01
28.66
2.16
46.20
2.21
43.94
28.85
2.21
46.13
2.26
43.88
29.04
2.26
46.06
2.31
43.82
29.24
2.31
46.00
2.36
43.75
29.43
2.36
45.93
2.41
43.69
29.61
2.41
45.86
2.48
42.82
29.26
2.50
44.99
2.55
41.96
28.89
2.59
44.12
2.73
41.10
28.50
2.77
43.26
2.91
40.25
28.10
2.96
42.40
39.30
27.95
3.11
41.44
2.97
3.02
38.55
27.35
3.11
40.69
3.07
37.80
26.75
3.11
39.94
2.84
37.05
25.99
2.87
39.20
2.40
36.31
25.36
2.40
38.45
2.01
34.42
24.27
2.00
36.48
1.88
33.80
23.90
1.87
35.82
90 / 75
SHC
PI
27.61
1.76
27.81
1.81
28.01
1.86
28.21
1.91
28.41
1.96
28.61
2.01
28.81
2.06
29.01
2.11
29.20
2.16
29.40
2.21
29.59
2.26
29.79
2.31
29.98
2.36
30.18
2.41
29.83
2.51
29.48
2.62
29.11
2.82
28.73
3.02
28.61
3.18
28.02
3.18
27.43
3.18
26.68
2.93
26.07
2.46
24.96
2.05
24.59
1.92
45

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lc128hv4Lc187hvLc188hv4Lc367hvLc427hvLc247hv

Table of Contents