Dwyer Instruments HT Series Operating Instructions

Dwyer Instruments HT Series Operating Instructions

Rh/temperature transmitter

Advertisement

Quick Links

*Duct Mount unit shown.

DESCRIPTION

Monitor and control relative humidity and temperature in
building energy management systems with the Series HT
Humidity Temperature Transmitter. Designed for demanding
HVAC/EMCS applications, the Series HT provides ±3% RH
accuracy and ±1% stability per year. Routine calibration is
not required with the fully interchangeable sensor. Two-wire
connections allow easy installation directly into air ducts or
within a controlled area.

INSTALLATION

Mounting
The duct mount models must be mounted as described
below:
1. Drill four 1/8 (3.2 mm) diameter holes for the mounting
screws in the locations shown in Figure 1.
2. Cut a 0.866 (22 mm) diameter hole in the duct for the
sensor in the location shown in Figure 1.
3. Attach the duct mounting bracket to the duct with the
four screws provided.
4. Slide the sensor/transmitter assembly through the
center hole
in the mounting bracket and secure into
place by tightening the screw located on the side of the
raised square portion of the mounting bracket.
Reminder: Remove the yellow sensor protection cap
before installing the sensor into your duct.
1.65
[42]
1.65
[42]
FIGURE 1: Drilling Dimensions for Duct Mount Units
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, ,U.S.A.
SERIES HT RH/Temperature Transmitter
Specifications – Installation and Operating Instructions
Ø.125 [3.2]
Tapping Screw
DIN 7981
Ø 0.866 [22] min
1-1/2
3-5/32
[38.10]
[80.17]
3-5/32
[80.17]

PHYSICAL DATA

Relative Humidity Range: 10 to 90% RH.
Temperature Range: Duct mount: -40 to 140˚F (-40 to 60˚C), wall
mount: 23 to 131˚F (-5 to 55˚C).
Accuracy: ±3% RH @ 25˚C; ±0.3˚C @ 25˚C.
Stability: ±2% RH over 2 years.
RH Temperature Dependence: <±1.5% RH from 14 to 140˚ (-10
to 60˚C).
Temperature Dependence: 0.01˚C/˚C.
Temperature Sensor: Pt 1000Ω RTD.
Response Time: 15 seconds.
Output Signal: 4 to 20 mA.
Supply Voltage: 10 to 28 VDC.
Current Consumption: 4 mA minimum.
Operating Humidity Range: Duct mount: 0 to 100%, wall mount:
0 to 90%.
Operating Temperature Range: Duct mount: 14 to 140˚F (-10 to
60˚C), wall mount: 23 to 131˚F (-5 to 55˚C).
Storage Temperature Range: -40 to 140˚F (-40 to 60˚C).
Conduit Connection:
1
/
NPT.
2
Mounting Connection:
3
/
4
Housing Material: ABS plastic.
Enclosure: Duct mount only/IP65.
Weight: 0.6 lb (0.3 kg).

SERIES HT RH/TEMPERATURE TRANSMITTERS

Model
Number
HT00*
Humidity Transmitter, wall mount
HT01
Humidity Transmitter, duct mount
HT10*
Humidity/Temp Transmitter, wall mount
HT11
Humidity/Temp Transmitter, duct mount
*Wall mount not shown

Accessories

No. HT5, Replacement Humidity Sensor
No. HT6, Replacement Pt1000Ω RTD
Phone: 219/879-8000
Fax: 219/872-9057
Lit-By Fax: 888/891-4963
BULLETIN E-90-HT
11-5/8 [295.3]
2-1/8
8-1/2 [215.9]
[53.98]
15/32 DIA.
19/32 DIA.
[11.91]
[15.09]
NPT.
Description
www.dwyer-inst.com
e-mail: info@dwyer-inst.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the HT Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Dwyer Instruments HT Series

  • Page 1 *Wall mount not shown [42] Accessories No. HT5, Replacement Humidity Sensor FIGURE 1: Drilling Dimensions for Duct Mount Units No. HT6, Replacement Pt1000Ω RTD DWYER INSTRUMENTS, INC. Phone: 219/879-8000 www.dwyer-inst.com P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, ,U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com...
  • Page 2 2. Pierce the center of the seal with a cable or a screwdriver. 3. Pull the cable through the hole in the center of the seal. Designed for cable diameters 7...10 mm. ©Copyright 2000 Dwyer instruments, Inc Printed in U.S.A. 4/00 DWYER INSTRUMENTS, INC. Phone: 219/879-8000 www.dwyer-inst.com...

This manual is also suitable for:

Ht00 seriesHt10 seriesHt01Ht11

Table of Contents