Danfoss Native BACnet VLT HVAC Drive Operating Instructions Manual page 16

Table of Contents

Advertisement

BACnet Objects
Object_Name
Default
ID
name
Writeable
AV:37
AV:38
Reserved for P, I, D
AV:39
AV:40
Setpoint 3
Bus
AV:41
Feedback 3
AV:42
AV:43
Reserved for P, I, D
AV:44
Running
AV:45
Bypass
AV:46
AV:47
AV:48
AV:49
Alarm Log:
AV:50
Error Code
AV:51
Fault Code
PID Start
AV:52
Speed
On
Reference
AV:53
Bandwidth
PID Propor-
AV:54
tional Gain
PID Integral
AV:55
Time
PID Differen-
AV:56
tiation Time
PID Diff. Gain
AV:57
Limit
Table 5.3 Analog Values
1
Either AV:1 or AV:2 controls the drive reference. Only one of them can control the frequency converter at a time and BV:2
decides which one.
2
This value is not directly available in the frequency converter. The value must be calculated as follows:
Par . 16 − 17
AV # 3 =
× 100 %
Par . 4 − 13
3
This value is not directly available in the frequency converter. The value must be calculated as follows:
Par . 16 − 52
AV # 4 =
× 100 %
Par . 20 − 14
4
VLT
®
HVAC Drive fault codes are transmitted as an analog value in AV:51. The Fault codes are mapped as shown in table on
following page. The VLT
®
HVAC Drive alarm codes are shown as well for comparison.
®
VLT
HVAC Drive Native BACnet Operating Instructions
Present_Value
EEPROM
Parameter
Unit
2023
%
896
%
3111
Hours
1530
NONE
Note 4
NONE
2083
Hz
2084
%
2093
NONE
2094
Sec
2095
Sec
2096
NONE
®
MG.14.C1.02 - VLT
is a registered Danfoss trademark
Writeable
Cmd.able
Timeout
x
x
x
x
x
x
x
x
Option
5
5
MCO 104
15