RCD Test Verification (X5, 30.00mA)
Select RCD 30.00mA X5 range using the RCD/LOOP button (Fig. 1
Section 8).
Select & perform 30.00mA X5 RCD Test.
Specification: 20.0mS +/-2mS, +/- Instrument accuracy
Neither current low nor current high LED's should illuminate whist
conducting this test, however if the RCD current fails please refer to
manufacturers specifications.
RCD Test Verification (30.00mA X1)
Select RCD 30.00mA X1 range using the RCD/LOOP button (Fig. 1
Section 8).
Select & perform 30.00mA X1 RCD Test.
Specification: 50.0mS +/-2mS, +/- Instrument accuracy
Neither current low nor current high LED's should illuminate whist
conducting this test, however if the RCD current fails please refer to
manufacturers specifications.