7.3.3 Terminal Key
Terminal
Type
Function
12
+24 V out
Supply to sensor
18
DI 1
Digital input, start/stop
20
GND
Common frame for digital inputs
55
GND
Common frame for analog inputs
54
AI 2
Sensor input, sensor 1, 0/4-20 mA
61
RS-485 GND Y
GENIbus, frame
68
RS-485 A
GENIbus, signal A (+)
69
RS-485 B
GENIbus, signal B (-)
Note
Note
The RS-485 screen must be connected to frame.
7.3.4 Access to signal terminals
All signal terminals are behind the terminal cover of the CU331SP
front. Remove the terminal cover as shown in Fig.12.
Fig. 12 Access to signal terminals
Fig. 13 Signal terminals
7.3.5 Fitting the conductor
1. Remove the insulation at a length of 0.35 to 0.40 inches (9 to
10 mm).
2. Insert a screwdriver with a tip of maximum 0.015 X 0.1 in (0.4
X 2.5 mm) into the square hole.
3. Insert the conductor into the corresponding round hole.
Remove the screwdriver. The conductor is now fixed in the
terminal.
Fig. 14 Fitting the conductor into the signal terminal

7.4 Connecting the signal relays

As a precaution, signal cables must be separated
Caution
from other groups by reinforced insulation in
their entire lengths.
Fig. 15 Terminals for signal relays (normal state, not activated)
Terminal
Function
C 1
C 2
Common
NO 1
NO 2
Normally open contact
NC 1
NC 2
Normally closed contact
7.4.1 Signal Relay
The signal relays on the CU331SP are predefined as follows:
Relay 1: Pump running
Relay 2: Alarm.
Fig. 16 Terminals for relay connection