Temptek CF Series Instruction Manual

Portable chiller covering models from 5 to 40 tons with 'm1' instruments & scroll compressors
Hide thumbs Also See for CF Series:
Table of Contents

Advertisement

I.O.M. #123 updated 11/06/2018
INSTRUCTION MANUAL
• INSTALLATION • OPERATION • MAINTENANCE
Covering models
From 5 to 40 tons
With 'M1' Instruments
& Scroll Compressors
TEMPTEK, INC.
525 East Stop 18 Road Greenwood, IN 46142
317-887-0729 fax: 317-881-1277
Model:
Service Department fax: 317-885-8683
www.Temptek.com
Serial Number :
E-mail: sales@Temptek.com

Advertisement

Table of Contents
loading

Summary of Contents for Temptek CF Series

  • Page 1 INSTRUCTION MANUAL • INSTALLATION • OPERATION • MAINTENANCE Covering models From 5 to 40 tons With ‘M1’ Instruments & Scroll Compressors TEMPTEK, INC. 525 East Stop 18 Road Greenwood, IN 46142 317-887-0729 fax: 317-881-1277 Model: Service Department fax: 317-885-8683 www.Temptek.com Serial Number : E-mail: sales@Temptek.com...
  • Page 3 INSTRUCTION MANUAL CF INSTRUMENT With & SCROLL COMPRESSORS AIR & WATER-COOLED MODELS COVERING INSTALLATION OPERATION MAINTENANCE TEMPTEK, INC. 525 East Stop 18 Road Greenwood, IN 46142 Phone: 317-887-0729 fax: 317-881-1277 Service Department fax: 317-885-8683 www.Temptek.com E-mail: sales@Temptek.com...
  • Page 4: Table Of Contents

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons TABLE OF CONTENTS 1.0 GENERAL Introduction Safety Receiving instructions 1.4 Efficiency Clean air act Water Treatment Components 2.0 INSTALLATION General To and From process connections Water supply connection...
  • Page 5 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons 7.0 RELATED DRAWINGS Mechanical Schematic : Water-Cooled : 5 - 10 Tons Mechanical Schematic : Water-Cooled : 15 - 40 Tons Mechanical Schematic : Air-Cooled : 5 - 10 Tons...
  • Page 6 THIS PAGE INTENTIONALLY BLANK Page: 6...
  • Page 7: General

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons GENERAL Introduction Safety Receiving Instructions Efficiency Clean Air Act Miscellaneous Water Treatment Components Page: 7 TEMPTEK, INC. 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-6352 Fax: 317-881-1277...
  • Page 8: Introduction

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons INTRODUCTION This manual covers portable chillers from 5 to 40 tons (17 to 140 kW) of cooling capacity using the Temptek CF microprocessor control instrument and fixed displacement scroll compressors and digital scroll compressors. The standard fluid operating temperature range for this chiller is 20°F to 80°F for units using R410A refrigerant. Units using other refrigerants have different standard operating ranges. Units operating below 48°F fluid...
  • Page 9 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons WARNING: This equipment contains hazardous voltages that can cause severe injury or death. Disconnect and lock out incoming power before installing or servicing the equipment. WARNING: This equipment contains refrigerant under pressure. Accidental release of refrigerant under pressure can cause personal injury and or property damage.
  • Page 10: Receiving Instructions

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons RECEIVING INSTRUCTIONS Chillers are shipped skid mounted and wrapped in plastic prior to shipment. Check the overall condition of the equipment prior to accepting delivery. Check for visible damage and document any evident damage on the delivery receipt.
  • Page 11: Water Treatment

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons WATER TREATMENT WARNING: Improper water treatment will void unit warranty. The use of untreated or improperly treated water in a portable chiller may result in scaling, erosion, corrosion, algae or slime.
  • Page 12 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons Bypass Pressure Gauges Insulated Reservoir Electrical Cabinet Water Regulator Valve Compressor Water-Cooled Coolant Pump Condenser Water-Cooled Model 10 ton unit shown. ABS fascia, top and enclosure panels removed for photo.
  • Page 13: Installation

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons INSTALLATION General Unit Location To and From Process Connections Make-Up Water Supply Connection Air-Cooled Condenser Installation Water-Cooled Condenser Installation Electrical Connection Page: 13 TEMPTEK, INC. 525 East Stop 18 Road Greenwood, Indiana 46142...
  • Page 14: General

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons GENERAL Chillers are shipped skid mounted and wrapped in plastic prior to shipment. Check the overall condition of the equipment prior to accepting delivery. Check for visible damage and document any evident damage on the delivery receipt.
  • Page 15: To And From Process Connections

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons Units with a motor-driven fan may not use duct work unless a booster fan of equal volume rating has been installed in the duct. TO AND FROM PROCESS CONNECTIONS Use appropriately rated hose or fluid piping to connect the process piping going to your process to the “to process”...
  • Page 16: Water Supply Connection

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons MAKE-UP WATER SUPPLY CONNECTION The automatic water make-up system continually monitors the Condenser Condenser Water Make-up From Process To Process Water Out Water In reservoir tank and fills it when needed. Connect as follows: This label marks the Water...
  • Page 17 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons WARNING: Do not attempt to duct exhaust air from a portable chiller using motor driven fans. Exhaust air can only be ducted from a portable chiller using a blower assembly.
  • Page 18: Water-Cooled Condenser

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons WATER-COOLED CONDENSER Connect the facility cooling tower or city water supply to the Condenser From Process To Process “condenser water in” connection on the unit. Water In...
  • Page 19 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons Electrical power supply requirements for standard units are identified on the equipment data tag. Determine that the plant’s voltage supply is the same as the unit’s voltage requirements, taking into account the SSCR Rating. A customer supplied, four conductor cable is required for connection to a customer supplied fused disconnecting means.
  • Page 20 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons Electrical Panel Page: 20 TEMPTEK, INC. 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-6352 Fax: 317-881-1277 Email: service@Temptek.com...
  • Page 21 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons Instrument Transformer Transformer: Line Voltage to 115 volts Terminal Strip Pump Starter Power Entry Terminal Block Pump Overload Block Pump & Transformer Fusing Grounding Bus Bar Ground Lug Compressor &...
  • Page 22 THIS PAGE INTENTIONALLY BLANK Page: 22...
  • Page 23: Operations

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons OPERATIONS General Start Up/Operations Procedure Instrument Shut Down Page: 23 TEMPTEK, INC. 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-6352 Fax: 317-881-1277 Email: service@Temptek.com...
  • Page 24 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons GENERAL Failure to follow the factory required operations procedure may adversely affect the unit’s ability to adequately control process temperature and may create a hazardous operating condition which may result in serious operator injury and/or unit damage. WARNING: Follow all Factory operations procedures. Failure to do so may create a hazardous operating condition which may result in serious operator injury and/or unit damage.
  • Page 25 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons WATER QUALITY CONTROL. Lack of, as well as, improper water treatment can damage the chilling unit. The services of competent water treatment specialist should be obtained and their recommendations followed. It is the equipment owner’s responsibility to prevent damage from foreign material or inadequate...
  • Page 26 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons Compressor Pump’s Electric Motor Pump electric motor and compressors located on typical water-cooled unit. Caution must be taken when checking rotation to avoid electrical shock. A scroll compressor may make a loud rattling noise when rotating in the wrong direction.
  • Page 27 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons Observe the motor shaft. When the ON/ OFF SWITCH is on, the motor shaft will rotate. When switched off, the shaft will slowly “coast” to a stop. As the shaft slows, the operator can identify the rotation of the motor shaft.
  • Page 28 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons PROCESS FLOW ADJUSTMENTS The operator must determine and set proper water flow rate for the most efficient and trouble free operation. Water flow rate through the process is determined by the pressure losses in the process loop. Generally, higher flow rates result in turbulent flow achieving maximum temperature control and lower maintenance. Since the evaporator in most liquid chillers is flow sensitive, the efficiency of operation is directly related to the flow of liquid. Maximum chiller efficiency is obtained at approximately 2.4 gpm per ton of rated capacity. Low liquid flow can reduce efficiency and in some cases allow ice to develop in the evaporator which can damage the evaporator. Excessive liquid flow will trip the motor overload protection...
  • Page 29 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons gauge reading is in the normal operating range for the refrigerant type used in the chiller. For Automatic Low Flow Bypass Valves: A “T” handle or adjusting stem is located on the top of the valve.
  • Page 30 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons Open electrical cabinet panel door. Note that the electrical power is engaged at this point and caution must be observed while the cabinet panel is open. Identify the motor starter block. This block consists of the motor starter contactor and the overload relay.
  • Page 31 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons Place an amp meter on a single power lead coming from the overload relay. Locate the motor name plate on the pump motor housing. The full load amp rating for the motor is listed on the name plate.
  • Page 32: Instrument/Operation

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons INSTRUMENT / OPERATION M1 Series Control. This control instrument is used on units with fixed displacement compressors. M1D Series Control. This control instrument is used on units with digital scroll compressors. INSTRUMENT START-UP When the correct electrical power and adequate water supply pressure are supplied to the unit, it is possible to start the unit.
  • Page 33 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons PRECAUTIONS: The chiller control is programmed from the factory with a setpoint range of 48° to 70°F. To operate below 48°F, the addition of inhibited propylene glycol and modification of the limit control settings are required. Diligent monitoring of the water/glycol solution is mandatory to prevent freezing of the evaporator.
  • Page 34 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons Units equipped with a digital scroll compressor (M1D-5A, M1D-5W, M1D- 10A, M1D-10W, M1D-15A, M1D-15W) will operate in the unloaded state for a maximum of 50 seconds out of every 60 seconds.
  • Page 35 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons Low Pressure Fault. After the compressor is turned on, the control has a 15 second buffer for the low pressure fault. If a low pressure condition occurs within the first 15 seconds, the control waits the amount of time specified by the “LP...
  • Page 36: Shut Down Procedure

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons WARNING: Relieve static pressure before disconnection process lines. WARNING: Follow all shut down procedures outlined in this manual. SHUT DOWN/DISCONNECT SEQUENCE PRECAUTIONS/WARNINGS The operator must follow all shut down procedures outlined in this manual. If the operator fails to follow all procedures outlined in this manual, an unsafe condition can develop resulting in damage to the unit or personal injury.
  • Page 37: Troubleshooting

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons TROUBLESHOOTING Unit Will Not Start Compressor Hums But Will Not Start Shuts Off On High Pressure Shuts Off On Low Pressure Compressor Shuts Off On Internal Overload...
  • Page 38: Unit Will Not Start

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons WARNING: Before troubleshooting or servicing this unit, follow all company lock-out tag-out procedures. UNIT WILL NOT START Power off. Check main disconnect. Main line open. Check fuses.
  • Page 39: Shuts Off On Low Pressure

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons Water-cooled units: Water regulator valve. Adjust condenser water regulator valve to maintain * See Temperature-Pressure 100°F to 105°F refrigerant condensing temperature*. If valve is defective, have chart in Section 8.2 for refrigerant pressure.
  • Page 40: Compressor Shuts Off On Internal Overload

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons Air-cooled units: Head pressure too low. Check that entering air temperature is above 60°F. If below 60°F, find out reason why. Water-cooled units: Head pressure too low. Adjust condenser water regulating valve to maintain 100°F - * See Temperature-Pressure 105°F refrigerant condensing temperature*.
  • Page 41: Cooling Capacity Inadequate

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons Filters. Check filter in the chilled water circuit and clean if necessary. Pressure switch (or flow switch). Readjust or replace if defective. Fuses and wiring. Have electrician check the fuses and wiring. COOLING CAPACITY INADEQUATE Low refrigerant charge. Check for adequate refrigerant charge (bubbles or misty sight glass indicates low charge).
  • Page 42 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons All control instruments used in Advantage water chillers are covered by the machine’s warranty. Proprietary “tailor made” instrument are manufactured specifically for Advantage. If you experience problems with your control instrument, it’s as easy as 1-2-3 to execute our repair or replacement system in order to get your equipment running.
  • Page 43: Maintenance

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons MAINTENANCE Warranty Service Procedure Periodic Preventative Maintenance Special Maintenance Solenoid Valve Service Pump Seal Service Checking the Refrigerant Charge Proper Cleaning Procedure for Brazed Plate Evaporator Page: 43 TEMPTEK, INC.
  • Page 44: Warranty Service Procedure

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons WARRANTY SERVICE PROCEDURE In the event of a problem with a chiller that can not be resolved by normal troubleshooting procedures, the customer is invited to consult the Service Department for assistance.
  • Page 45: Special Maintenance

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons SPECIAL MAINTENANCE Any service of the refrigeration system must be accomplished by a certified refrigeration technician. Addition of compressor oil. Addition of refrigerant. Repair of a refrigerant leak. Adjustment of super heat. Changing of filter-drier or drier core. Repair of a refrigeration solenoid.
  • Page 46: Solenoid Valve Service

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons AUTOMATIC WATER MAKE-UP SYSTEM service The automatic water make-up system consists of a level switch (figure 5.4A) and a solenoid valve (figure 5.4B). When the tank level is low the level switch signals the solenoid valve to open allowing make-up water to re-fill the tank.
  • Page 47 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons Coil and solenoid base sub assembly Valve body Core Body Diaphragm Diaphragm assembly Core spring assembly Gasket spring Page: 47 TEMPTEK, INC. 525 East Stop 18 Road Greenwood, Indiana 46142...
  • Page 48: Pump Seal Service

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons PUMP SEAL SERVICE Rotating Member Tension Spring The coolant pump seal is a carbon/niresist shaft seal assembly including a stationary member, rotating member and tension spring (figure 5.5A). The operator can determine the pump seal is leaking when fluid is identified leaking from the pump case adapter.
  • Page 49 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons adapter from the unit and place on a workbench to continue the procedure. Locate and remove the dust cap from motor end to expose slotted motor shaft. The motor shaft is free to rotate, but must be secured to remove the impeller.
  • Page 50 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons When the pump seal replacement procedure is complete, the operator may restart the unit according the section 3. Stationary member Figure 5.5I Stationary member Figure 5.5J Seal members Figure 5.5K...
  • Page 51: Checking The Refrigerant Charge

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons CHECKING THE REFRIGERANT CHARGE All standard chillers are manufactured with thermostatic expansion valves as the metering device to the evaporator. All standard chillers have a refrigerant sight glass (figure 5.6A) with a moisture indicator. To check the...
  • Page 52 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons to below the evaporator outlet. For chillers without a reservoir tank, drain total unit. Connect a water supply hose to the evaporator water outlet. If acid cleaning, connect the discharge hose from the acid pump to the evaporator outlet port.
  • Page 53: Components

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons Components Water System Refrigeration System Options Page: 53 TEMPTEK, INC. 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-6352 Fax: 317-881-1277 Email: service@Temptek.com...
  • Page 54: Water System

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons WATER SYSTEM MOTOR/PUMP ASSEMBLY: The motor/pump assembly circulates chilled fluid to the process loop. The pump assembly is built of total stainless steel to maintain water quality. RESERVOIR. The vented reservoir is sized for the chiller Coolant Pump application to support the flow rate. The reservoir provides a...
  • Page 55 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons the system has been contaminated with moisture. In such case, the filter-drier must be replaced. The replacement of the filter-drier must be completed by a qualified refrigerant service technician. EXPANSION VALVE: The expansion valve throttles flow of refrigerant liquid into the evaporator and creates a pressure Typical Liquid Line Solenoid drop in the refrigerant system that allows the liquid refrigerant to “boil off” inside the evaporator (figure 6.2G).
  • Page 56: Options

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons Non-adjustable “fixed” high pressure switch Non-adjustable “fixed” low pressure switch Typical placement of non-adjustable “fixed” pressure switches. Service valves: These valves are located throughout the system. Only a qualified refrigeration service technician shall operate these valves. UNIT OPTIONS LOW FLOW BYPASS: If your process will experience lower than design flow rates or intermittent flow, a low flow bypass valve will be required.
  • Page 57 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons Audible Alarm: A simple buzzer alarm emits a loud alarm. Visual Alarm: Emits an audible sound and flashes a beacon. CONDENSER SCREEN: Optional for air-cooled models only. The condenser screen is a filter for the air-cooled condenser to prevent air borne Non-fused disconnect show.
  • Page 58 THIS PAGE INTENTIONALLY BLANK Page: 58...
  • Page 59: Related Drawings

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons RELATED DRAWINGS Mechanical Schematic : Water-Cooled : 5 - 10 tons Mechanical Schematic : Water-Cooled : 15 - 40 tons Mechanical Schematic : Air-Cooled : 5 - 10 tons with Propeller Fans...
  • Page 60 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons MECHANICAL SCHEMATIC : WATER-COOLED : 5 - 10 TON MODELS Page: 60 TEMPTEK, INC. 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-6352 Fax: 317-881-1277 Email: service@Temptek.com...
  • Page 61 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons MECHANICAL SCHEMATIC : WATER-COOLED : 15 - 40 TON MODELS Page: 61 TEMPTEK, INC. 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-6352 Fax: 317-881-1277 Email: service@Temptek.com...
  • Page 62 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons MECHANICAL SCHEMATIC : AIR-COOLED : 5 - 20 TON MODELS WITH PROPELLER FANS Page: 62 TEMPTEK, INC. 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-6352 Fax: 317-881-1277...
  • Page 63 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons MECHANICAL SCHEMATIC : AIR-COOLED : 25 - 30 TON MODELS AND 5 - 20 TON MODELS WITH OPTIONAL CENTRIFUGAL BLOWER Page: 63 TEMPTEK, INC. 525 East Stop 18 Road Greenwood, Indiana 46142...
  • Page 64 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons TYPICAL ELECTRICAL SCHEMATIC : AIR-COOLED MODELS Electrical schematic is presented for illustration purposes only. For exact details, consult the electrical drawing supplied with your machine. Page: 64 TEMPTEK, INC.
  • Page 65 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons TYPICAL ELECTRICAL SCHEMATIC : WATER-COOLED MODELS Electrical schematic is presented for illustration purposes only. For exact details, consult the electrical drawing supplied with your machine. Page: 65 TEMPTEK, INC.
  • Page 66: Typical Physical : Air-Cooled : 5 Tons

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons TYPICAL PHYSICAL : AIR-COOLED MODELS : 5 TONS Physical drawings are presented for illustration purposes only. Many units are customized to meet unique needs and to include standard and custom options that may require changes to the unit configuration. Unit dimensions, layout, piping locations and piping sizes should be confirmed with the factory for your specific unit. Page: 66 TEMPTEK, INC.
  • Page 67 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons TYPICAL PHYSICAL : AIR-COOLED MODELS : 7.5 - 10 TONS Physical drawings are presented for illustration purposes only. Many units are customized to meet unique needs and to include standard and custom options that may require changes to the unit configuration. Unit dimensions, layout, piping locations and piping sizes should be confirmed with the factory for your specific unit.
  • Page 68 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons TYPICAL PHYSICAL : AIR-COOLED MODELS : 15 - 20 TONS FAN COOLED Physical drawings are presented for illustration purposes only. Many units are customized to meet unique needs and to include standard and custom options that may require changes to the unit configuration. Unit dimensions,...
  • Page 69 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons 7.10 TYPICAL PHYSICAL : AIR-COOLED MODELS : 15 - 30 TONS WITH BLOWER Physical drawings are presented for illustration purposes only. Many units are customized to meet unique needs and to include standard and custom options that may require changes to the unit configuration. Unit dimensions,...
  • Page 70: Typical Physical : Air-Cooled : 5 - 10 Tons With Remote Condenser

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons 7.11 TYPICAL PHYSICAL : AIR-COOLED MODELS : 5 - 10 TONS WITH REMOTE CONDENSER Physical drawings are presented for illustration purposes only. Many units are customized to meet unique needs and to include standard and custom options that may require changes to the unit configuration. Unit dimensions,...
  • Page 71 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons 7.12 TYPICAL PHYSICAL : AIR-COOLED MODELS : 15 - 30 TONS WITH REMOTE CONDENSER Physical drawings are presented for illustration purposes only. Many units are customized to meet unique needs and to include standard and custom options that may require changes to the unit configuration. Unit dimensions,...
  • Page 72: Typical Physical : Water-Cooled : 5 Tons

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons 7.13 TYPICAL PHYSICAL : WATER-COOLED MODELS : 5 TONS Physical drawings are presented for illustration purposes only. Many units are customized to meet unique needs and to include standard and custom options that may require changes to the unit configuration. Unit dimensions, layout, piping locations and piping sizes should be confirmed with the factory for your specific unit.
  • Page 73 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons 7.14 TYPICAL PHYSICAL : WATER-COOLED MODELS : 7.5 - 10 TONS Physical drawings are presented for illustration purposes only. Many units are customized to meet unique needs and to include standard and custom options that may require changes to the unit configuration. Unit dimensions,...
  • Page 74 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons 7.15 TYPICAL PHYSICAL : WATER-COOLED MODELS : 15 - 30 TONS Physical drawings are presented for illustration purposes only. Many units are customized to meet unique needs and to include standard and custom options that may require changes to the unit configuration. Unit dimensions,...
  • Page 75 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons 7.16 TYPICAL PHYSICAL : WATER-COOLED MODELS : 40 TONS Physical drawings are presented for illustration purposes only. Many units are customized to meet unique needs and to include standard and custom options that may require changes to the unit configuration. Unit dimensions, layout, piping locations and piping sizes should be confirmed with the factory for your specific unit.
  • Page 76: Duct Schematic For Air-Cooled Chillers

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons 7.17 DUCT SCHEMATIC FOR AIR-COOLED CHILLERS For models equipped with centrifugal blower. Models with equipped with fans can not be ducted. NOTE: THIS DRAWING IS FOR EXPLANATION PURPOSES ONLY,...
  • Page 77: Appendix

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons APPENDIX Operations Below 48°F Operating with Glycol (Antifreeze) and with a Setpoint Above 48°F or Below 38°F Ambient Refrigerant Pressure-Temperature Chart Inhibited Propylene Glycol Chiller Capacity and Derate Chart Mechanical Schematic Page: 77 TEMPTEK, INC.
  • Page 78: Operations Below 48°F Fluid Or 38°F Ambient

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons OPERATIONS BELOW 48°F FLUID OR 38°F AMBIENT The chiller is never to be operated below 48°F leaving water temperature without several precautionary measures. All controls are factory adjusted for 48°F and above operations.
  • Page 79 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons If your unit is equipped with an adjustable low pressure switch, adjust the low pressure switch according to the specifications in the chart on the next page. Never lower the cut out setting on the adjustable low pressure switch without adding glycol to the circulating system.
  • Page 80: Operating With Glycol (Antifreeze) And With A Set Point Above 48°F Or Below 38°F Ambient

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons OPERATING WITH GLYCOL (ANTIFREEZE) AND WITH A SET POINT ABOVE 48°F OR BELOW 38°F AMBIENT The chiller is never to be operated below 48°F leaving water temperature without the precautionary measures outlined in section 8.1.
  • Page 81 CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons out setting on the adjustable low pressure switch without adding glycol to the circulating system. Evaporator damage will result and this damage is not covered by the factory warranty.
  • Page 82: Refrigerant Pressure-Temperature Chart

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons REFRIGERANT PRESSURE-TEMPERATURE CHART Page: 82 TEMPTEK, INC. 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-6352 Fax: 317-881-1277 Email: service@Temptek.com...
  • Page 83: Inhibited Propylene Glycol

    CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons INHIBITED PROPYLENE GLYCOL To operate liquid chillers below 48°F, it is necessary to add inhibited propylene glycol to the circulating system to lower the freeze point and prevent damage to the cooling system.