Shipping And Packing List; Operating Gauge Set And Service Valves - Lennox XPG15 Series Installation Instructions Manual

Dual-fuel heat pump units
Hide thumbs Also See for XPG15 Series:
Table of Contents

Advertisement

CAUTION
Physical contact with metal edges and corners while
applying excessive force or rapid motion can result in
personal injury. Be aware of, and use caution when
working near these areas during installation or while
servicing this equipment.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of
refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992.
Approved methods of recovery, recycling or reclaiming
must be followed. Fines and/or incarceration may be
levied for noncompliance.
WARNING
Improper installation, adjustment, alteration, service or
maintenance can cause personal injury, loss of life, or
damage to property.
Installation and service must be performed by a licensed
professional installer (or equivalent) or a service agency.

Shipping and Packing List

Check unit for shipping damage. Consult last carrier
immediately if damage is found.
1
Assembled outdoor unit.
1
K229 relay is shipped in control box of outdoor unit.
Relay is field installed in the furnace control panel. See
figure 18 page 26 for relay installation information.
1
Bag assembly which includes the following items:
1
Bushing (for low voltage wiring)
2
Isolation grommets for liquid and vapor lines

Operating Gauge Set and Service Valves

These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
who have jurisdiction before installation.
TORQUE REQUIREMENTS
When servicing or repairing heating, ventilating, and air
conditioning components, ensure the fasteners are
appropriately tightened. Table 1 shows torque values for
fasteners.
Only use Allen wrenches of sufficient hardness (50Rc −
Rockwell Harness Scale minimum). Fully insert the
wrench into the valve stem recess.
Service valve stems are factory−torqued (from 9 ft−lbs for
small valves, to 25 ft−lbs for large valves) to prevent
refrigerant loss during shipping and handling. Using an
Allen wrench rated at less than 50Rc risks rounding or
breaking off the wrench, or stripping the valve stem
recess.
See the Lennox Service and Application Notes #C−08−1
for further details and information.
To prevent stripping of the various caps used, the
appropriately sized wrench should be used and fitted
snugly over the cap before tightening.
Table 1. Torque Requirements
Parts
Service valve cap
Sheet metal screws
Machine screws #10
Compressor bolts
Gauge port seal cap
OPERATING MANIFOLD GAUGE SET
When checking the system charge, only use a manifold
gauge set that features low−loss anti−blow back fittings.
Manifold gauge set used with HFC−410A refrigerant
systems must be capable of handling the higher system
operating pressures. The gauges should be rated for use
with pressures of 0 − 800 psig on the high side and a low
side of 30" vacuum to 250 psig with dampened speed to
500 psi. Gauge hoses must be rated for use at up to 800
psig of pressure with a 4000 psig burst rating.
Page 5
IMPORTANT
IMPORTANT
Recommended Torque
8 ft. − lb.
11 NM
16 in.− lb.
2 NM
28 in.− lb.
3 NM
90 in.− lb.
10 NM
8 ft.− lb.
11 NM
XPG15 SERIES