New or Replacement Line Set

REFRIGERANT LINE SET
This section provides information on installation or
replacement of existing line set. If new or replacement line
set is not being installed then proceed to Brazing
Connections on page .
IMPORTANT
Lennox highly recommends changing line set when
converting the existing system from HCFC−22 to
HFC−410A.
If that is not possible and the line set is the
proper size as reference in table 2, use the procedure
outlined under Flushing Line Set and Indoor Coil on page
17.
If refrigerant lines are routed through a wall, then seal and
isolate the opening so vibration is not transmitted to the
building. Pay close attention to line set isolation during
installation of any HVAC system. When properly isolated
from building structures (walls, ceilings. floors), the
refrigerant lines will not create unnecessary vibration and
subsequent sounds. See figure 9 for recommended
installation practices. Also, consider the following when
placing and installing a high−efficiency outdoor unit.
IMPORTANT
Refrigerant lines must not contact structure.
Liquid lines that meter the refrigerant, such as RFC1 liquid
lines, must not be used in this application. Existing line set
of proper size as listed in table 2 may be reused. If system
was previously charged with HCFC−22 refrigerant, then
existing line set must be flushed (see Flushing the System
on page 17).
Field refrigerant piping consists of liquid and vapor lines
from the outdoor unit to the indoor unit coil (braze
connections). Use Lennox L15 (sweat, non−flare) series
line set, or field−fabricated refrigerant line sizes as listed in
table 2.
Table 2. Refrigerant Line Set
Valve Sizes
Model
Liquid
Vapor
Line
Line
−024
3/8" (10)
3/4" (19)
−030
−036
−042
3/8" (10)
7/8" (22)
−048
1−1/8"
−060
3/8 (10)
(29)
506212−01 11/10
Inches (Millimeters)
Recommended Line Set
Liquid
Vapor
L15
Line
Line
Line Sets
L15−41
15 − 50 feet
3/8" (10)
3/4" (19)
(5 − 15 meters)
L15−65
15 − 50 feet
3/8" (10)
7/8" (22)
(5 − 15 meters)
1−1/8
Field
3/8" (10)
(29)
Fabricated
NOTE
When installing refrigerant lines longer than 50
feet, see the Lennox Refrigerant Piping Design and
Fabrication Guidelines, or contact Lennox Technical
Support Product Applications for assistance.
To obtain the correct information from Lennox, be sure to
communicate the following information:
S
Model (XPG15) and size of unit (e.g. −036).
S
Line set diameters for the unit being installed as listed
in table 2 and total length of installation.
S
Number of elbows vertical rise or drop in the piping.
The compressor is charged with sufficient Polyol Ester oil
(POE) for line set lengths up to 50 feet. Recommend
adding oil to system based on the amount of refrigerant
charge in the system. Systems with 20 pounds or less of
refrigerant required no oil to be added.
For systems over 20 pounds − add one ounce for every five
(5) pounds of HFC−410A refrigerant.
Recommended POE oils are Mobil EAL ARCTIC 22 CC or
ICI EMKARATEt RL32CF.
IMPORTANT
If this unit is being matched with an approved line set
or indoor unit coil which was previously charged with
mineral oil, or if it is being matched with a coil which
was manufactured before January of 1999, the coil
and line set must be flushed prior to installation. Take
care to empty all existing traps. Polyol ester (POE) oils
are used in Lennox units charged with HFC−410A
refrigerant. Residual mineral oil can act as an
insulator, preventing proper heat transfer. It can also
clog the expansion device, and reduce the system
performance and capacity.
Failure to properly flush the system per the
instructions below will void the warranty.
Polyol ester (POE) oils used with HFC−410A
refrigerant absorb moisture very quickly. It is very
important that the refrigerant system be kept closed as
much as possible. DO NOT remove line set caps or
service valve stub caps until you are ready to make
connections.
IMPORTANT
Mineral oils are not compatible with
must be added, it must be a Polyol Ester oil.
Page 12