Shipping and Packing List

Package 1 of 1 contains:
1- Assembled unit
Check unit for shipping damage. Receiving party should
contact last carrier immediately if shipping damage is found.

General

These instructions are intended as a general guide and
do not supersede local codes in any way. Authorities
having
jurisdiction
should
installation.
Requirements
The unit is ETL certified for outdoor installations only at
the clearances to combustible materials listed on unit
nameplate and in figures 1 and 2.
RECOMMENDED SERVICE CLEARANCES IN (mm)
036, 060, AND 120 UNITS
TOP CLEARANCE UNOBSTRUCTED
36 (914) 3 & 5 TON
48 (1219) 10 TON
É É É É É É É É É É
É É É É É É É É É É
É É É É É É É É É É
É É É É É É É É É É
É É É É É É É É É É
É É É É É É É É É É
É É É É É É É É É É
É É É É É É É É É É
É É É É É É É É É É
É É É É É É É É É É
60
BLOWER
É É É É É É É É É É
É É É É É É É É É É
(1524)
É É É É É É É É É É
É É É É É É É É É É
É É É É É É É É É É
É É É É É É É É É É
É É É É É É É É É É
É É É É É É É É É É
60
(1524)
FIGURE 1
SERVICE CLEARANCES IN (mm) - 240 UNITS
TOP CLEARANCE UNOBSTRUCTED
Ç Ç Ç Ç Ç Ç Ç
Ç Ç Ç Ç Ç Ç Ç
Ç Ç Ç Ç
Ç Ç Ç Ç Ç Ç Ç
Ç Ç Ç Ç
96
Ç Ç Ç Ç
(2438)
Ç Ç Ç Ç
Ç Ç Ç Ç
Ç Ç Ç Ç Ç Ç Ç
*66 inches (1676mm)
Ç Ç Ç Ç Ç Ç Ç
recommended
service clearance for
Ç Ç Ç Ç Ç Ç Ç
blower deck removal.
NOTE- ENTIRE PERIMETER OF UNIT BASE REQUIRES SUP­
PORT WHEN ELEVATED ABOVE MOUNTING SURFACE.
FIGURE 2
be
consulted
before
A
60 (1524) 10 TON
A
48 (1219) 3 & 5 TON
60 (1524)
Ç Ç Ç Ç
Ç Ç Ç Ç
48
Ç Ç Ç Ç
(1219)
Ç Ç Ç Ç
Ç Ç Ç Ç
72
(1829)
Danger of sharp metallic edges. Can cause injury.
Take care when servicing unit to avoid accidental
contact with sharp edges.
Installation of heat pumps must conform with standards in
National Fire Protection Association (NFPA) "Standard
for Installation of Air Conditioning and Ventilating
Systems NFPA No. 90A," "Standard for Installation of
Residence Type Warm Air Heating and Air conditioning
Systems NFPA No. 90B," local municipal building codes
and manufacturer's installation instructions.
The National Electric Code (ANSI/NFPA No. 70-1984) is
available from:
National Fire Protection Association
1 Batterymarch Park
PO Box 9101
Quincy, MA 02269-9101
The unit is ETL certified as a heat pump with cooling and
with or without auxiliary electric heat for non-residential
use only at the clearances to combustible materials as
listed on the unit nameplate and in figures 1 and 2.
Installation of ETL certified units must conform with current
standard C273.5 "Installation Requirements for Heat
Pumps" and applicable local codes. Authorities having
jurisdiction should be consulted before installation.
Use of this unit as a construction heater or air conditioner
is not recommended during any phase of construction.
Very low return air temperatures, harmful vapors and
operation of the unit with clogged or misplaced filters will
damage the unit.
If this unit has been used for heating or cooling of
buildings or structures under construction, the following
conditions must be met or the warranty will be void:
S A room thermostat must control the unit. The use of
fixed jumpers that will provide continuous heating or
cooling is not allowed.
S A pre-filter must be installed at the entry to the return
air duct.
S The return air duct must be provided and sealed to
the unit.
S Return air temperature range between 55°F (13°C)
and 80°F (27°C) must be maintained.
S Air filters must be replaced and pre-filter must be
removed upon construction completion.
S The unit components, duct system, air filters and
evaporator coil must be thoroughly cleaned following
final construction clean-up.
S The unit operating conditions (including airflow,
cooling operation, and heating operation) must be
verified according to these installation instructions.