New Or Replacement Line Set - Lennox XP16 Series Unit Information

Hfc-410a
Table of Contents

Advertisement

New or Replacement Line Set

REFRIGERANT LINE SET
This section provides information on installation or
replacement of existing line set. If new or replacement line
set is not being installed then proceed to Brazing
Connections on page 16.
IMPORTANT
Lennox highly recommends changing line set when
converting the existing system from HCFC−22 to
HFC−410A.
If that is not possible and the line set is the
proper size as reference in table 2, use the procedure
outlined under Flushing the System on page 13.
If refrigerant lines are routed through a wall, then seal and
isolate the opening so vibration is not transmitted to the
building. Pay close attention to line set isolation during
installation of any HVAC system. When properly isolated
from building structures (walls, ceilings. floors), the
refrigerant lines will not create unnecessary vibration and
subsequent sounds. See figure 8 for recommended
installation practices. Also, consider the following when
placing and installing a high−efficiency outdoor unit.
Liquid lines that meter the refrigerant, such as RFC1 liquid
lines, must not be used in this application. Existing line set of
proper size as listed in table 2 may be reused. If system was
previously charged with HCFC−22 refrigerant, then existing
line set must be flushed (see Flushing the System on page
19).
Field refrigerant piping consists of liquid and vapor lines from
the outdoor unit to the indoor unit coil (braze connections).
Use Lennox L15 (sweat, non−flare) series line set, or
field−fabricated refrigerant line sizes as listed in table 2.
Table 2. Refrigerant Line Set
Valve Field
Connections
Model
Liquid
Vapor
Line
Line
−018
3/8 in.
3/4 in
−024
(10 mm)
(19 mm)
−030
−036
3/8 in.
7/8 in
−042
(10 mm)
(22 mm)
−048
3/8 in.
1−1/8 in.
−060
(10 mm)
(29 mm)
Inches (mm)
Recommended Line Set
Liqui
Vapor
L15
d
Line
Line Sets
Line
L15−41
3/8 in.
3/4 in
15 ft. − 50 ft.
(10
(19 mm)
(4.6 m − 15
mm)
m)
L15−65
3/8 in.
7/8 in
15 ft. − 50 ft.
(10
(22 mm)
(4.6 m − 15
mm)
m)
3/8 in.
1−1/8 in.
Field
(10
(29 mm)
Fabricated
mm)
NOTE
When installing refrigerant lines longer than 50
feet, see the Lennox Refrigerant Piping Design and
Fabrication Guidelines, CORP. 9351−L9, or contact Lennox
Technical Support Product Applications for assistance.
To obtain the correct information from Lennox, be sure to
communicate the following information:
Model (XP16) and size of unit (e.g. −036).
D
D
Line set diameters for the unit being installed as listed
in table 2 and total length of installation.
Number of elbows vertical rise or drop in the piping.
D
The compressor is charged with sufficient Polyol ester oil for
line set lengths up to 50 feet. Recommend adding oil to
system based on the amount of refrigerant charge in the
system. No need to add oil in system with 20 pounds of
refrigerant or less. For systems over 20 pounds − add one
ounce of every five pounds of refrigerant.
Recommended topping−off POE oils are Mobil EAL ARCTIC
22 CC or ICI EMKARATEt RL32CF.
Polyol Ester (POE) oils used with HFC−410A
refrigerant absorb moisture very quickly. It is very
important that the refrigerant system be kept closed as
much as possible. DO NOT remove line set caps or
service valve stub caps until you are ready to make
connections.
Mineral oils are not compatible with
be added, it must be a Polyol Ester oil.
Page 14
WARNING
IMPORTANT
HFC−410A.
If oil must
XP16

Advertisement

Table of Contents
loading

Table of Contents