Humidifier Control - Field Controls EvenAir T32 Installation And User Manual

Thermostat with airflow control
Table of Contents

Advertisement

34 Economizer/Whole House
Fan Control by Timer
(Only displayed if Whole House Fan or
Economizer Control is ON and Economizer/
Whole House Fan Control by Temperature
is OFF)
Factory Default: OFF. Range: On or Off.
Select ON to control Whole House Fan or
Economizer using a 1 to 12 hour timer set in the
thermostat by the user using the User Menu. The
timer starts when the System is switched to ECool.
When the timer expires, the System is set to Off.
Use the
UP
key to
Option
select ON or touch the
DOWN
key to select
OFF.
Touch
NEXT
or
ENTER.
For Humidity and De-humidification wiring
!
information, see the H32 Wiring Hub
Installer Manual.

40 Humidifier Control

Factory Default: OFF. Range: On or Off.
Select ON if a Humidifier is installed.
Use the
UP
key to
select ON or touch the
DOWN
key to select
OFF.
Touch
NEXT
or
ENTER.
41 Automatic Adjustment of Humidity
(RH) Setpoint at Low Outdoor
Temperatures
(Only displayed if Humidity Control is ON)
Factory Default: OFF. Range: On or Off.
Select if automatic adjustment of RH setpoint is
made at low outdoor temperatures.
If automatic adjustment is selected, the RH
setpoint will decrease at outdoor temperatures
below 35F. The RH Setpoint is reduced 1% for
each 2F below 35F.
Use the
UP
key to
Option
select ON or touch the
DOWN
key to select
OFF.
Touch
NEXT
or
ENTER.
INSTALLER SECTION
42 De-Humidication Control
Factory Default: OFF. Range: On or Off.
Select if de-humification is used during cooling
calls.
If de-humidification is On and the humidity is
above the setpoint, the DSBK terminal on the
Wiring Hub will be set to 0VAC to force the
indoor fan to operate at low speed to remove
moisture.
Use the
UP
select ON or touch the
DOWN
key to select
OFF.
Touch
NEXT
NEXT
ENTER
50 Airflow Control
Factory Default: On. Range: On or Off.
This option turns the automatic airflow control on
or off. If off, the dampers fully open, nighttime
airflow options are disabled and airflow is no
longer displayed on the thermostat.
Use the
UP
select ON for airflow
control or touch the
DOWN
key to select
Option
OFF to disable airflow
control.
Touch
NEXT
NEXT
ENTER
If Airflow Control was off and is now being turned on,
the Nighttime Airflow option needs to be turned on
using the User Options.
51 Airflow Update Time
Factory Default: 2 minutes. Range: 1 to 20.
Sets the number of minute between updating the
damper positions during a heating or cooling
call.
Use the
UP/DOWN
keys to set
time(minutes) between
updating the dampers.
Touch
NEXT
52 Enable USER Airflow Control
Factory Default: Off. Range: On or Off.
Homeowners with an unusual work schedule,
NEXT
ENTER
home office, etc. may want to use this option.
When turned On, this option enables the user to
turn off automatic airflow control in the User
Options. Airflow is adjusted by the homeowner.
Nighttime Airflow option is still enabled but can
be turned off using the User Options.
Use the
UP
select ON to enable
the user to turn off
automatic airflow
control in the user
options.
Touch
NEXT
key to
Option
NEXT
ENTER
or
ENTER.
key to
Sleeping
Option
Airflow %
Living
NEXT
ENTER
or
ENTER
.
Option
NEXT
ENTER
or
ENTER.
key to
Option
NEXT
ENTER
or
ENTER.
page 12 of 16
53 Maximum Airflow in Heating to
the Sleeping Area
Factory Default: 150%. Range: 100% to 160%.
Use the
UP/DOWN
Sleeping
keys to select the
Airflow %
maximum allowable
airflow in heating to
the sleeping area.
Touch
NEXT
or
ENTER
.
54 Maximum Airflow in Cooling to
the Sleeping Area
Factory Default: 140%. Range: 100% to 160%.
Use the
UP/DOWN
Sleeping
keys to select the
Airflow %
maximum allowable
airflow in cooling to
the sleeping area.
Touch
NEXT
or
ENTER
.
55 Maximum Airflow in Heating to
the Living Area
Factory Default: 150%. Range: 100% to 160%.
Use the
UP/DOWN
keys to select the
Airflow %
maximum allowable
Living
airflow in heating to
the living area.
Touch
NEXT
or
ENTER.
56 Maximum Airflow in Cooling to
the Living Area
Factory Default: 140%. Range: 100% to 160%.
Use the
UP/DOWN
keys to select the
Airflow %
maximum allowable
Living
airflow in cooling to
the living area.
Touch
NEXT
or
ENTER
.
57 Maximum Temperature
Differential
Factory Default: 2F. Range: 0F to 10F
This is the maximum allowable temperature
difference between the sleeping and living area
temperatures. When the temperature difference is
equal to or greater than the allowed differential,
the airflow is adjusted.
Use the
UP/DOWN
keys to select the
maximum allowable
temperature difference
between the sleeping
and living area
Touch NEXT
or
ENTER.
P/N 780101708 2/18 Rev A
Option
Heat
NEXT
ENTER
Option
Cool
NEXT
ENTER
Option
Heat
NEXT
ENTER
Option
Cool
NEXT
ENTER
Option
NEXT
ENTER