Initial Air Settings; Set Appliance Limit Controls; Prepare The Fuel Unit For Air Venting; Start The Burner - Beckett CF 500/800 Instruction Manual

Oil burner
Table of Contents

Advertisement

Table 5 - Initial air shutter and band settings
Approximate air settings
Rate
GPH
CF500
Shutter
Band
1.75
1
0
2.25
2
0
3.00
10
1
3.50
10
2
4.00
10
3
5.00
10
5
5.50
10
10
6.00
--
--
7.00
--
--
8.00
--
--
Note: These settings are appoximate, and can vary depending on
actual job conditions and overfi re pressure
Initial air settings (Table 5)
Loosen the air band and shutter, and adjust to the
approximate fi ring rate settings given in Table 5.
These initial settings should be adequate for starting the
burner. Once the burner is in operation, the air settings
will be adjusted for best performance as discussed later in
this manual.
Follow the procedures described later in this manual for
fi ne-tuning the air settings.

Set appliance limit controls

Set the appliance limit controls in accordance with the
appliance manufacturer's recommendations.

Prepare the fuel unit for air venting

To vent air from the oil supply line, attach a clear hose
to the pump air bleed valve (fi gure 9) on the fuel unit.
Provide a container to catch the oil. Loosen the pump air
bleed valve.
Vent the air as described in the next section under Start
the burner
.
12
CF800
Tube A
Tube B
Shutter
Band
Shutter
--
--
--
--
--
--
1
0
--
3
0
--
4
0
--
9
0
8
9
5
9
10
3
10
10
8
10
--
--
10

Start the Burner

Failure to follow these instructions
could lead to equipment malfunction
Band
and result in heavy smoke emission,
--
soot-up, hot gas puff-back, fi re and
--
asphyxiation hazards.
--
Do not attempt to start the burner when excess oil has
--
accumulated in the appliance, the appliance is full of
--
vapor, or when the combustion chamber is very hot.
2
Do not attempt to re-establish fl ame with the burner
4
running if the fl ame becomes extinguished during start-
3
up, venting, or adjustment.
5
Vapor-Filled Appliance: Allow the unit to cool off and
all vapors to dissipate before attempting another start.
10
Oil-Flooded Appliance: Shut off the electrical power
and the oil supply to the burner and then clear all ac-
cumulated oil before continuing.
If the condition still appears unsafe, contact the Fire
Department. Carefully follow their directions.
Keep a fi re extinguisher nearby and ready for use.

Starting the burner and venting air

Priming the pump
Failure to bleed the pump properly
could result in unstable combustion,
hot gas puff-back and heavy smoke.
Do not allow oil to intermittently spray into a hot com-
bustion chamber while bleeding.
Install a gauge in the nozzle discharge port tubing or
fully open the pump bleed valve to prevent oil spray
from accumulating in the combustion chamber when
venting air from the fuel pump.
Ensure that all bubbles and froth are purged from the
oil supply system before tightening the pump air bleed
valve.
Initiate a call for heat
While the ignition is on, press and release the reset button
on the R7184 control (hold 1/2 second or less). If the
control has not locked out since it's most recent complete
heat cycle, the lockout time will be extended to 4 minutes
(45 seconds in earlier units), and the ignition will remain
on the entire heat cycle.
Bleed the pump until all froth and bubbles are purged. If
prime is not established within the extended lockout time,
R09, Printed in the USA 01/08
Form 6104BCF5
Explosion and Fire
Hazard
Hot Gas Puff-back and
Heavy Smoke Hazard