6.1 METHOD A: BOLTING
The mounting method has been qualified by Canadian Solar Inc., and the method bolting on the short‐side frame has
been certified by VDE, the method bolting on long‐side frame has been certified by both VDE and TUV Rheinland.
Modules should be bolted to support structures through mounting holes located in the frame's back flanges only. Do not
drill additional holes or modify the module frame. Doing so will void the warranty.
Each module must be securely fastened at a minimum of 4 points on two opposite sides, using the most inner mounting
holes. If additional wind loads are anticipated for this installation, additional mounting points should be used. System
designer and installer are responsible for load calculations and for proper design of support structure.
Modules should be bolted at the following hole locations depending on the configuration and load:
Table 3: Authorized attachments for bolting method
Uplift load ≤ 2400 Pa
Downforce load ≤ 2400 Pa
Bolting on long side
frame
Mounting rails may run perpendicularly or parallel to the long side frame
Use 4 standard mounting holes (short side)
Bolting on short
side frame
(except for 6X
Mounting rails may run parallel or
series)
perpendicularly to the short side frame
6.2 METHOD B: CLAMPING
The mounting method has been qualified by Canadian Solar Inc and certified by VDE.
Top or bottom clamping methods will vary and are dependent on the mounting structures. Follow mounting guidelines
recommended by the mounting system supplier.
Each module must be securely fastened at a minimum of 4 points on two opposite sides. The clamps should be
positioned according to the authorized position ranges defined in table 4. Install and tighten the module clamps to the
mounting rails using the torque stated by the mounting hardware manufacturer. System designer and installer are
responsible for load calculations and for proper design of support structure.
www.canadiansolar.com
Uplift load ≤ 2400 Pa
2400 Pa ≤ Downforce load ≤ 5400 Pa
Use 4 standard mounting holes (long side)
Use 4 standard mounting holes (short side). An
additional support bar should be placed below
the module.
Support bar
Mounting rails should run parallel to the short
side frame
EN-Rev 2.4 Copyright© May 2013.CanadianSolarInc.
Canadian Solar Inc. warranty may be void in cases where improper clamps or unsuitable installation methods are found.
When installing inter‐modules or end type clamps, take measures so as:
1. Not to bend the module frame
2. Not to touch or cast shadow on the front glass
3. Not to damage the surface of the frame
4. To ensure the clamps overlap the module frame by at least 5 mm.
5. To ensure the clamps overlap length is at least 40 mm.
Clamp material should be anodized aluminum alloy. Floating type clamps
are not authorized.
Clamp positions are of crucial importance for the reliability of the installation, the clamp centerlines must only be
positioned within the ranges indicated in table 4, depending on the configuration and load.
For configurations where the mounting rails run parallel to the clamps installation side, precautions should be taken to
ensure the module frame (C‐shape) overlap the rail by 15mm or more.
Use 4 clamps on the long side, the allowed range
depends on the module type.
Clamping on
long side
frame
Mounting rails may run perpendicularly or parallel to
Use 4 clamps on the short side, the allowed range
depends on the module type. Mounting rails may run
parallel or perpendicularly to the short side frame
A2
Clamping on
short side
frame
A2
For CS5P and CS6P series, an additional support bar
should be placed below the module where download
force above 1600Pa is expected. Mounting rails
should run parallel to the short side frame.
www.canadiansolar.com
8
Table 4: Authorized attachments for clamping method
Uplift load ≤ 2400 Pa
Downforce load ≤ 2400 Pa
2400 Pa ≤ Downforce load ≤ 5400 Pa
Use 4 clamps on the long side, the allowed range
A1
A1
A1
A1
Mounting rails may run perpendicularly or parallel to
the long side frame.
Use 4 clamps on the short side, the allowed range
depends on the module type. An additional support
bar should be placed below the module.
A2
A2
A2
A2
Mounting rails should run parallel to the short side
EN-Rev 2.4 Copyright© May 2013.CanadianSolarInc.
Uplift load ≤ 2400 Pa
depends on the module type.
B1
B1
B1
B1
the long side frame
A2
A2
Support bar
frame
9