Grounding; Mounting Instructions - Canadian Solar CS6P-PE Installation Manual

Solar module
Hide thumbs Also See for CS6P-PE:
Table of Contents

Advertisement

5.2 GROUNDING 
Although  the  modules  are  certified  to  safety  class  II,  it  is  recommended  that  they  be  grounded  and  the  module 
installation complies with all local electrical codes and regulations.     
The earth grounding connection should be made by a qualified electrician.       
Connect module frames to each other using adequate grounding cables, the recommended size is 4‐14mm
copper  wires.  Holes  provided  for  this  purpose  are  identified  with  a  green  label.  All  the  junctions  on  the  conductive 
connection must be fixed. 
The bolts, nuts, flat washers, lock washers or other relevant hardware should be made of stainless steel.   
Grounding hardware is not provided by Canadian Solar Inc. 
Two specific grounding methods are recommended for Canadian Solar Inc. standard modules with 5 mm grounding holes, 
as described below. Other grounding methods can be acceptable, provided they comply with all local electrical codes and 
regulations. For some modules (SunTuile or NewEdge), standard grounding methods cannot be applied, please refer to 
the most updated relevant technical notes (IM/IEC/SUNT‐EN and IM/IEC/NEWE‐EN). 
Method A: Bolt + Nut with teeth + Cup washer. 
Attach  wire  between  the  flat 
washer and cup washer. Place cup 
washer 
(concave 
side 
up) 
between frame and wire. 
A grounding kit with M5 size SS cap bolt, M5 size SS flat washer, M5 size SS cup washer, and M5 size SS nut (with teeth) is 
used to attach a copper grounding wire to grounding hole pre‐drilled on the frame (see picture above).   
Attach the wire between the flat washer and the cup washer. Ensure the cup washer is between the frame and wire with 
concave  side up  to  prevent  corrosion  due  to  dissimilar  metal.  Tighten the  bolt securely  using  the  SS  nut with  teeth. A 
wrench may be used in this application. The tightening torque is 1 Nm. 
Method B: Bolt + K‐nut + Ring terminal (copper). 
Connect  the  grounding  hardware (M5)  to  the  grounding  hole  on  the  frame  as 
shown in the picture.   
A K‐nut is used to penetrate the frame's anodizing (protective coating) to create 
conductive connection. 
A torque moment of about 3 Nm should be used to fasten the grounding parts 
to module frame.
 
 
www.canadiansolar.com
2
 (AWG 6‐12) 
Tighten  the  bolt  using 
the nut with teeth.
 
EN-Rev 2.4 Copyright© May 2013.CanadianSolarInc.
6.0    MOUNTING INSTRUCTIONS 
Standard modules 
For a clear understanding of module, please refer to the illustration of a standard module shown below: 
 
 
Reference 
Designation 
Grounding holes 
Junction box 
Standard mounting holes 
(long side) 
Additional mounting holes 
(high wind or snow loads) 
Standard mounting holes 
(short side) 
Module frame 
Cables and connectors 
The mounting design must be certified by a registered professional engineer. The mounting design and procedures shall 
comply with local codes and all authorities having jurisdiction. 
Mounting hardware is not provided by Canadian Solar Inc. 
Standard  modules  can  be  mounted  to  a  support  structure  with  several  approved  methods,  either  using  the  mounting 
holes located on the frame back flanges (see Example A), by means of clamps (see Example B) or by means of insertion 
systems. For other installation hardware, please contact your local representative for further information. Failure to use a 
recognized installation method will void Canadian Solar Inc warranty. 
Example A: 
 
 
Bolting   
 
 
               
           
Use appropriate corrosion‐proof fastening materials. All mounting hardware (bolt/spring washer/flat washer/nut) should 
be stainless steel M6 size for bolting method (A), and M8 size for clamping method (B).     
Use  a  torque  wrench  for  installation.  The  above  figure  shows  methods  of  fastening  module  to  support  structure. 
Tightening torques should respectively be within 4~6 Nm and 10~17 Nm for M6x1 (Example A) and M8x1.5 (Example B) 
coarse  thread  bolts,  depending  on  bolt  class.  Different  recommendations  from  specific  clamping  hardware  suppliers 
should prevail. 
Standard modules can be installed in either landscape or portrait position, refer to the detailed instructions in tables 3 to 
6 for further guidance. Note that further countermeasures such the use of additional support bars should be considered 
in heavy snow areas (> 2400 Pa), to avoid damage by the snow accumulating in the lowest row of modules. 
When the addition of a support bar is recommended to enhance mechanical stability and module long term performance 
reliability,  material  of  suitable  resistance  should  be  selected.  Canadian  Solar  Inc  recommends  a  minimum  thickness  of 
50mm for the bar. The support bar centerline should be positioned within 100 mm of the side frame centerline (slight 
shift may be necessary to access module grounding hole). 
 
www.canadiansolar.com
6
4
2
6
1
3
(–
6
4
 
 
 
 
 
Example B:   
 
 
 
 
 
Clamping on 
EN-Rev 2.4 Copyright© May 2013.CanadianSolarInc.
5
4
1
7
3
(+
4
5
 
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents