Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 AL1340 IO-Link: 1.1.2 ifm firmware: 2.1.19 or higher LR DEVICE: 1.3.0.131 or higher English...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Content Table of Contents Preliminary note Legal and copyright information ................... 5 Purpose of the document ..................... 5 Symbols and styles used .....................
Page 3
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Content Configuration LR DEVICE ........................24 8.1.1 Remarks ............................. 25 8.1.2 IoT: Configure access rights ....................... 26 8.1.3 IoT: Configure IP settings ......................
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Preliminary note Legal and copyright information Preliminary note Legal and copyright information ....................... 5 Purpose of the document ......................... 5 Symbols and styles used ..........................
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Preliminary note Symbols and styles used > Symbols and styles used 15989 WARNING Death or serious irreversible injuries may result.
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Safety instructions General Safety instructions General ..............................7 Required background knowledge ......................7 Safety symbols on the device ........................8 Tampering with the unit ..........................
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Safety instructions Safety symbols on the device > Safety symbols on the device 15021 General warning Electrical connection Observe instructions in chapter "Electrical connection"...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Intended use Permitted use Intended use Permitted use ............................9 Prohibited use ............................9 18761 > Permitted use 22052 The IO-Link master serves as a gateway between intelligent IO-Link devices and the fieldbus.
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Function Prohibited use Function Communication, parameter setting, evaluation ..................11 Digital inputs ............................12 IO-Link supply ............................12 7482...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Function Digital inputs > 4.1.5 Visual indication 7772 The device has the following visual indicators: Status and error indication of the gateway, of the Modbus TCP connection and of the system ...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Mounting Mount the device Mounting Mount the device ............................13 22016 > Mount the device 15540 ► Disconnect the system from power before installation.
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Electrical connection IO-Link ports > IO-Link ports 22684 Ports X01...X04: For use as IO-Link port class A: ►...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Electrical connection IO-Link ports > 6.4.1 Input circuit 18629 The inputs of the ports X01...X04 (pin 2) provide a type 2 behaviour according to standard EN61131-2, the connected electronics must be rated for this electrically.
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Electrical connection Connect the device > Connect the device 2580 ► Disconnect power. ► Connect the unit via M12 socket X31 to 24 V DC (20...30 V SELV/PELV, for cULus max.
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Operating and display elements Overview Operating and display elements Overview ..............................19 LED indicators ............................20 5440 > Overview...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Operating and display elements LED indicators > LED indicators 22024 The device only has the following LED indicators: >...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Operating and display elements LED indicators > 7.2.2 Ethernet interface 22027 Each Ethernet interface (X21, X22) has 2 LEDs (LNK and ACT). The LEDs indicate the status of the Ethernet connection.
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Operating and display elements LED indicators > 7.2.5 IO-Link ports (Class A) 22029 Each IO-Link port Class A (X01 ... X04) has 2 LEDs marked as IOL and DI. The LEDs indicate the status of the IO-Link port.
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration LR DEVICE > LR DEVICE Remarks ..............................25 IoT: Configure access rights ........................26 IoT: Configure IP settings ........................27 IoT: Configure the interface to the LR SMARTOBSERVER ..............28...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration LR DEVICE > 8.1.2 IoT: Configure access rights 16555 The access rights define which instance may read and / or write the parameter data, process data and event/diagnostic messages.
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration LR DEVICE > 8.1.3 IoT: Configure IP settings 17713 For access to the IO-Link master via the IT infrastructure the user has to set the IP settings of the IoT port.
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration LR DEVICE > 8.1.4 IoT: Configure the interface to the LR SMARTOBSERVER 16552 To enable data transfer between the device and the LR SMARTOBSERVER monitoring software, the LR SMARTOBSERVER monitoring software interface has to be configured.
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration LR DEVICE > 8.1.5 Fieldbus: configure Modbus TCP port 12284 The configuration of the IP settings of the fieldbus port is only possible via LR DEVICE.
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration LR DEVICE > 8.1.6 IO-Link ports: Activate data transfer to the LR SMARTOBSERVER 16551 The user can decide separately for each IO-Link port if the process data of the connected IO-Link devices should be transferred to the LR SMARTOBSERVER.
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration LR DEVICE > 8.1.7 IO-Link ports: Configure operating mode 17439 The IO-Link ports X01...X04 of the device support the following operating modes: ...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration LR DEVICE > 8.1.8 IO-Link ports: Set the device validation and data storage 17945 In the operating mode "IO-Link" the user can set the behaviour of the IO-Link port with regard to device validation and the storage / restoration of the parameter data of the connected IO-Link device.
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration LR DEVICE > 8.1.9 IO-Link ports: set fail-safe values 11752 In case the Modbus TCP connection is interrupted, fail-safe values can be assigned to the outputs of the IO-Link ports.
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration LR DEVICE > 8.1.11 Firmware: Reset device to factory settings 7209 When the IO-Link master is reset, all parameters are set to the factory settings: To reset the device to factory settings: ►...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration LR DEVICE > 8.1.13 Configure IO-Link devices 11033 To configure the IO-Link devices connected to the device with the LR DEVICEparameter setting...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration Modbus TCP > Modbus TCP Integrate the AL1340 into the Modbus project ..................36 Set IO-Link master and IO-Link ports .....................38 read input data of several IO-Link ports ....................39...
Page 37
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration Modbus TCP > Example: Integrate IO-Link master in a CODESYS project 9612 Familiarise yourself with the following CODESYS functions! ...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration Modbus TCP > 8.2.2 Set IO-Link master and IO-Link ports 17986 Configuration Area Register area for the access to the configuration of the IO-Link master: →...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration Modbus TCP > 8.2.3 read input data of several IO-Link ports 10925 Register area for compact access to the input data of the IO-Link ports X01…X04 and X05...X04: →...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration Modbus TCP > 8.2.4 Read input data of individual IO-Link ports 18330 Single Port Access Register area for separate access to input data of the individual IO-Link ports: →...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration Modbus TCP > 8.2.5 Write output data of several IO-Link ports 13874 Output Data Register area for compact access to the output data of the IO-Link ports X01…X04: →...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration Modbus TCP > 8.2.6 Write output data of individual IO-Link ports 12554 Single Port Access Register area for separate access to output data of individual IO-Link ports: →...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration Modbus TCP > 8.2.7 Read diagnostic information and events 7251 Diagnostic data Register area for the access to diagnostic information of the IO-Link ports X01…X04:→...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration Modbus TCP > 8.2.8 Read device information 11039 The user can read device information using the FC43.
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration Modbus TCP > 8.2.11 Modbus TCP: Programmers' notes Rules for accessing the Modbus register ....................45 Supported function codes ........................46 Use acyclic services ..........................46...
Page 46
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration Modbus TCP > Supported function codes 13676 The AL1340 supports the following function codes for read and/or write access to the Modbus register:...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration IoT Core 8.3.1 Configure IoT port 16540 The parameters of the IoT port X23 are saved in the iotsetup substructure. The user can access the...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration IoT Core > 8.3.2 Configure the fieldbus port 11747 The parameters of the fieldbus port X21/X22 are saved in the fieldbussetup substructure. The user...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration IoT Core > 8.3.4 Set application identification 16580 The application name of the IO-Link master is saved in the devicetag substructure. The user can...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration IoT Core > 8.3.7 Read device information 17133 Device information is saved in the deviceinfo substructure. The user can access the following data...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration IoT Core > 8.3.9 Configure IO-Link devices 11002 The ifm IoT Core supports the configuration of the connected IO-Link devices. A parameter is accessed via IO-Link index and subindex (→...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration IoT Core > 8.3.11 Examples Example: Read process data of an IO-Link device ................53 Example: Read several parameter values of the IO-Link master simultaneously ........54 Example: Change name of the IO-Link master ..................54...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration IoT Core > Example: Read several parameter values of the IO-Link master simultaneously 17310 Task: The following current values are to be read by the IO-Link master. Temperature, serial number Solution: Read the current parameter values using the getdatamult (data point temperature service: /processdatamaster/termperature;...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration IoT Core > Example: read the parameter value of an IO-Link device 16546 Task: Read the serial number of the ifm temperature sensor TN2531 at IO-Link port X02...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration IoT Core > Example: Subscribe to event 17946 Task: The current values of the following parameters should be sent regularly to a network server with IP address 192.168.0.4: product name of the IO-Link device at IO-Link port X02, cyclic input data of...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration IoT Core > 8.3.12 Programmers' notes ifm IoT Core: General information ......................57 Device description ..........................57 Access ifm-IoT Core ..........................58 IoT Core: Diagnostic codes ........................60...
Page 58
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration IoT Core > Access ifm-IoT Core 17561 To activate the changes of the parameter values the IoT Core must have the respective write access rights to the IO-Link master (→...
Page 59
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration IoT Core > POST method 16548 Using the POST method the user has read and write access to a data point. A form with the required information is transferred to the IP address of the IO-Link master (IoT port X23).
Page 60
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Configuration IoT Core > IoT Core: Diagnostic codes 17437 The ifm IoT Core uses the following diagnostic codes:...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Operation Identify device Operation Identify device ............................61 Firmware update .............................62 Replace IO-Link device ..........................63 22368 > Identify device 16568 In the online mode, the user can identify the device using the RDY and IoT status LEDs.
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Operation Firmware update Firmware update 16582 The new firmware is installed via the device's web interface. If the firmware update is not successful, deactivate all connections to the Modbus TCP PLC, LR SMARTOBSERVER and LR DEVICE and repeat the process.
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Maintenance Replace IO-Link device Maintenance 21577 The operation of the unit is maintenance-free. ► Clean the surface of the unit when necessary. Do not use any caustic cleaning agents for this! ►...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Factory settings Replace IO-Link device Factory settings 16542 In the factory settings, the device has the following parameter settings:...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix Technical data > 13.1.4 Inputs 22820 Inputs Number of digital inputs 8; (IO-Link Port Class A: 4 x 2) Switching level high [V] 11...30 DC...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix Technical data > 13.1.10 Electrical connection 17850 Voltage supply IN X31 Plug and socket connection Wiring...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix Modbus TCP > 13.2.1 Register Configuration Area ..........................74 Diagnostic data ............................76 Input Data ...............................79 Output Data ............................82 Single Port Access ..........................83...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix Modbus TCP > Diagnostic data SYS_OBJECTID> Register Contents Bits 8-15 Bits 0-7 Mapping: Diagnostics Port X01: →...
Page 77
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix Modbus TCP > Mapping: Diagnostics 17305 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix Modbus TCP > Single Port Access 21513 Register Contents Bits 8-15 Bits 0-7 1000 Port X01: Digital Input - Pin 2 Port X01: Digital Input - Pin 4 (DI) Port X01: →...
Page 84
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix Modbus TCP > Mapping: PQI 21509 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3...
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix Modbus TCP > Acyclic Command Channel 17311 The following Modbus registers are available for acyclic data transmission:...
Page 86
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix Modbus TCP > Request channel 10893 Register Contents Bits 8-15 Bits 0-7 Port No. Index Subindex...
Page 87
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix Modbus TCP > Response channel 6916 Register Contents Bits 8-15 Bits 0-7 Port No. Index Subindex...
Page 88
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix Modbus TCP > Error codes 15475 Error code Description 0x71 Service not available (unknown command has been sent to the IO-Link port)
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix Modbus TCP > 13.2.2 Acyclic commands Command 0x10 – set mode ........................90 Command 0x20 – set validation ID / data storage .................92 Command 0x30 –...
Page 90
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix Modbus TCP > Command 0x10 – set mode 23461 The command changes the operating mode of an IO-Link port of the AL1340.
Page 91
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix Modbus TCP > Command response 14273 Register Contents Bits 8-15 Bits 0-7 Port No. reserved reserved...
Page 92
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix Modbus TCP > Command 0x20 – set validation ID / data storage 23462 The command sets the behaviour of the IO-Link master when connecting a new IO-Link device to an IO-Linkport of the device.
Page 93
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix Modbus TCP > Command response 10919 Register Contents Bits 8-15 Bits 0-7 Port No. reserved reserved...
Page 94
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix Modbus TCP > Command 0x30 – set fail-safe data pattern 23464 The command sets the behaviour of the outputs when the Modbus TCP connection and the corresponding fail-safe values are interrupted.
Page 95
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix Modbus TCP > Command response 10990 Register Contents Bits 8-15 Bits 0-7 Port No. reserved reserved...
Page 96
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix Modbus TCP > Command 0x40 – Reboot 7639 The command reboots the AL1340. > Command request...
Page 102
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix ifm IoT Core Profile: devicetag 17438 Element (identifier) Properties mandatory Comments devicetag type = structure ...
Page 103
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix ifm IoT Core > Profile: parameter 16545 The profile is used to mark the elements of type data as parameters (acyclic data). The profile defines no substructure.
Page 106
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix ifm IoT Core > Service: getdata 12223 Name: getdata Description: Service reads the value of a data point and provides it.
Page 107
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix ifm IoT Core > Service: getdatamulti 17964 Name: getdatamulti Description: The service sequentially reads the values of several data points and provides them. The value and the diagnostic code are provided for each data point.
Page 108
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix ifm IoT Core > Service: getidentity 17134 Name: getidentity Description: The service reads the complete device description of the AL1340 and provides it as JSON object.
Page 109
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix ifm IoT Core > Service: getsubscriptioninfo 17436 Name: getsubscriptioninfo Description: The service provides information about an existing subscription (subscribe).
Page 110
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix ifm IoT Core > Service: iolreadacyclic 12222 Name: iolreadacyclic Description: The service acyclically reads the parameter value of an IO-Link device. It is accessed via IO-Link index and subindex.
Page 111
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix ifm IoT Core > Service: iolwriteacyclic 11035 Name: iolwriteacyclic Description: The service acyclically writes the parameter value of an IO-Link device. It is accessed via IO-Link index and subindex.
Page 112
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix ifm IoT Core > Service: reboot 10986 Name: reboot Description: The service reboots the device. Applicable to: different objects...
Page 113
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix ifm IoT Core > Service: setblock 12224 Name: setblock Description: The service simultaneously sets the values of several data points of a structure.
Page 114
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix ifm IoT Core > Service: setdata 11036 Name: setdata Description: The service sets the value of the data point.
Page 115
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix ifm IoT Core > Service: setelementinfo 7159 Name: setelementinfo Description: The service sets the uid of an element.
Page 116
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Appendix ifm IoT Core > Service: subscribe 10920 Name: subscribe Description: The service subscribes to the values of data points. The data points to be subscribed are transferred as a list.
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Index Index General ....................7 GET method ..................58 Access ifm-IoT Core ................58 Accessories ................... 66 Identify device ..................
Page 118
Operating Instructions IO-Link Master with Modbus TCP interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1340) 04 / 2018 Index reboot ......................112 setblock......................113 setdata ......................114 Offline parameter setting ............... 25 setelementinfo ..................... 115 Operating and display elements ............