IFM AL1103 Operating Instructions Manual

IFM AL1103 Operating Instructions Manual

Io-link master with profinet interface standardline 8 ports ip 69k
Hide thumbs Also See for AL1103:
Table of Contents

Advertisement

Quick Links

Operating Instructions
IO-Link Master with Profinet interface
StandardLine
8 Ports
IP 69K
AL1103
ifm firmware: 1.1.22 or higher
LR DEVICE: 1.1.0.87 or higher
IO-Link: 1.1.2
English

Advertisement

Table of Contents
loading

Summary of Contents for IFM AL1103

  • Page 1 Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K AL1103 ifm firmware: 1.1.22 or higher LR DEVICE: 1.1.0.87 or higher IO-Link: 1.1.2 English...
  • Page 2: Table Of Contents

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Preliminary note Contents Preliminary note Legal and copyright information ................... 6 Purpose of the document ..................... 6 Symbols and styles used ..................... 6 Modification history ......................7 Safety instructions General ..........................
  • Page 3 Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Preliminary note Configuration Remarks ..........................26 8.1.1 Supported configuration options ....................27 8.1.2 Connection possibilities ......................27 8.1.3 Offline parameter setting ......................30 8.1.4 VPN connection .......................... 30 LR DEVICE: Configure the device ..................31...
  • Page 4 Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Preliminary note 12.1.10 Accessories ..........................65 12.1.11 Electrical connection ........................65 12.2 Profinet ..........................66 12.2.1 Parameter data ........................... 67 12.2.2 Cyclic data ..........................71 12.2.3 Acyclic data ..........................74 Index ifm weltweit •...
  • Page 5: Preliminary Note

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Preliminary note Preliminary note Legal and copyright information ....................... 6 Purpose of the document ......................... 6 Symbols and styles used .......................... 6 Modification history ........................... 7...
  • Page 6: Legal And Copyright Information

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Preliminary note > Legal and copyright information 1631 © All rights reserved by ifm electronic gmbh. No part of this manual may be reproduced and used...
  • Page 7: Modification History

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Preliminary note > Modification history 21676 Version Topic Date New creation of document 31.05.2017...
  • Page 8: Safety Instructions

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Safety instructions Safety instructions General ..............................9 Required background knowledge ......................9 Warnings used ............................9 Safety symbols on the device .........................10 Tampering with the unit ..........................10...
  • Page 9: General

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Safety instructions > General 22068 The plant manufacturer is responsible for the safety of the plant in which the device is installed. If the device is used in a way that is not intended by the manufacturer, the protection supported by the device may be impaired.
  • Page 10: Safety Symbols On The Device

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Safety instructions > Safety symbols on the device 15021 General warning When this symbol is shown, consult the corresponding section in the operating instructions. > Tampering with the unit...
  • Page 11: Functions And Features

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Functions and features Functions and features Permitted use ............................11 Prohibited use ............................11 18761 > Permitted use 7610 The device is designed for use without a control cabinet in the food industry.
  • Page 12: Function

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Function Function Communication, parameter setting, evaluation ..................13 Digital inputs ............................15 IO-Link supply ............................15 7482...
  • Page 13: Communication, Parameter Setting, Evaluation

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Function > Communication, parameter setting, evaluation IO-Link ..............................14 Profinet ..............................14 Parameter setting ...........................14 Visual indication ............................14 7485...
  • Page 14: Io-Link

    7771 The device provides the following configuration options:  Parameter setting of the IO-Link master of the AL1103 with parameter setting software LR DEVICE and/or Profinet projection software  Parameter setting of the connected IO-Link devices (sensors, actuators) with parameter setting software LR DEVICE and/or Profinet projection software ...
  • Page 15: Digital Inputs

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Function > Digital inputs 7584 The device has 8 digital inputs (type 2 according to EN 61131-2). The digital inputs are on pin 2 of the IO-Link ports X01 ... X08.
  • Page 16: Mounting

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Mounting Mounting Mount the device ............................16 22016 > Mount the device 15540 ► Disconnect the system from power before installation. ► For installation choose a flat mounting surface.
  • Page 17: Electrical Connection

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Electrical connection Electrical connection Profinet ports ............................18 IO-Link ports ............................19 Connect the device ..........................20 22017 A qualified electrician must connect the unit. ► Observe the national and international regulations for the installation of electrical equipment.
  • Page 18: Profinet Ports

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Electrical connection > Profinet ports 8020 Connection possibilities Notes on connection possibilities → (→ p. 27) ► Connect the unit via the M12 socket X21 and/or X22 with the Profinet network (e.g.
  • Page 19: Io-Link Ports

    IO-Link circuits 1863 The IO-Link ports of the device meet the requirements of the IO-Link specification 1.0 bis 1.1.2. The power supply of the connected IO-Link devices may only take place via the AL1103. Technical data Further information: → (→ p. 62)
  • Page 20: Connect The Device

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Electrical connection > Connect the device 17542 ► Disconnect power. ► Connect the device via M12 socket X31 to 24 V DC (20...30 V SELV/PELV; according to EN61010-1, secondary circuit with maximum 30 V DC derived from applied voltage up to 300 V of overvoltage category II).
  • Page 21: Operating And Display Elements

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Operating and display elements Operating and display elements Overview ..............................22 LED indicators ............................23 5440...
  • Page 22: Overview

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Operating and display elements > Overview 22025 Status LEDs RDY, BF und SF Status LEDs → (→ p. 23) Status LEDs LNK and ACT of the Profinet...
  • Page 23: Led Indicators

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Operating and display elements > LED indicators 22024 The device only has the following LED indicators: > 7.2.1 Status LEDs 22034 The RDY LED shows the status of the gateway.
  • Page 24: Voltage Supply

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Operating and display elements > 7.2.3 Voltage supply 22026 The interface for voltage supply (X31) has the LED that is marked as US. The LED indicates the status of the voltage supply.
  • Page 25: Configuration

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Configuration Configuration Remarks ..............................26 LR DEVICE: Configure the device ......................31 LR DEVICE: Configure IO-Link devices ....................40 Profinet: Configure the device ........................42 Profinet: Configure IO-Link devices ......................49 Profinet: Programmers' notes .........................49...
  • Page 26: Remarks

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Configuration > Remarks Supported configuration options ......................27 Connection possibilities ..........................27 Offline parameter setting ........................30 VPN connection ............................30 22369...
  • Page 27: Supported Configuration Options

    > 8.1.2 Connection possibilities 12742 Via the two Profinet interfaces X21 and X22, the AL1103 can be simultaneously connected with the Profinet control level (PLC) and the IT infrastructure level (monitoring/parameter setting). The following connection possibilities exist: > Operation without Profinet connection 4364 Operation as independent IO-Link master with connected IO-Link devices.
  • Page 28 Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Configuration > Operation with Profinet connection (without LR DEVICE) 7396 Operation of the IO master as Profinet IO device. As an option, several IO-Link masters can be coupled via the Ethernet interfaces X21 and X22.
  • Page 29 > Operation with Profinet connection and LR DEVICE/LR SmartObserver 7398 The AL1103 can be connected via the two Ethernet interfaces X21 and X22 simultaneously with the Profinet control level (PLC) and the IT infrastructure level (monitoring/parameter setting).  Parameter setting IO-Link master: LR DEVICE and/or Profinet projection software ...
  • Page 30: Offline Parameter Setting

    22762 An active VPN connection blocks the access of the parameter setting software LR DEVICE to the Profinet interface of the AL1103. ► Deactivate the VPN connection in order to be able to access the AL1103 with the LR DEVICE.
  • Page 31: Lr Device: Configure The Device

    Reset IO-Link master to factory settings ....................39 22402 The IO-Link master and the IO-Link devices connected to the AL1103 can be configured with the ifm software LR DEVICE. Further information about operation and functions of the LR DEVICE parameter setting software: ►...
  • Page 32: Set-Up

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Configuration > 8.2.1 Set-up 12759 Factory settings On delivery, the AL1103 is configured with the → (→ p. 60) Before configuration with the LR DEVICE parameter setting software, the user must put the device into operation.
  • Page 33: Configure Communication Profile

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Configuration > 8.2.2 Configure communication profile 22061 In order to copy the access rights to the device: ► Select the [LineRecorder] menu. > The page shows the current settings.
  • Page 34: Configure The Ethernet Interface

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Configuration > 8.2.3 Configure the Ethernet interface 22404 To set the parameters of the Profinet interface (X21/X22): ► Select the [Network] menu. > The page shows the current settings.
  • Page 35: Configure The Interface To The Smartobserver

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Configuration > 8.2.4 Configure the interface to the SmartObserver 12743 In order to set the parameters of the interface to the SmartObserver: ► Select the [LineRecorder] menu.
  • Page 36: Set The Operating Mode Of The Io-Link Ports

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Configuration > 8.2.5 Set the operating mode of the IO-Link ports 8714 The IO-Link ports X01...X08 of the device support the following operating types:  Digital input (DI): binary input signal on pin 4 (C/Q) of the IO-Link port ...
  • Page 37: Set Device Validation And Data Storage

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Configuration > 8.2.6 Set device validation and data storage 7165 In operating mode "IO-Link" the user can set the behaviour of the IO-Link ports regarding device validation and backup/restore of parameter data of the connected IO-Link devices.
  • Page 38 Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Configuration Name Description Possible values  Type compatible IO-Link device is compatible with V1.1 device with the V1.1 IO-Link standard Restore  Verification whether it is an...
  • Page 39: Reset Io-Link Master To Factory Settings

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Configuration > 8.2.7 Reset IO-Link master to factory settings 12740 Factory settings When resetting the AL1103, all parameters are reset to the → (→ p. 60) To reset the device to factory settings: ►...
  • Page 40: Lr Device: Configure Io-Link Devices

    In order to configure the IO-Link devices connected to the AL1103 using the parameter setting software LR DEVICE: Requirements: > AL1103 is correctly installed and connected to the LR DEVICE software via the Profinet interface (X21/X22). > The IO-Link device is connected correctly with the AL1103. >...
  • Page 41: Offline Parameter Setting: Add Io-Link Devices Manually

    Offline parameter setting: Add IO-Link devices manually 22817 The AL1103 supports the automatic recognition of IO-Link devices that are connected to the IO-Link interfaces. In addition to the automatic recognition of IO-Link devices in the online mode, the user can Offline parameter setting also manually add IO-Link devices to the device configuration (e.g.
  • Page 42: Profinet: Configure The Device

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Configuration > Profinet: Configure the device Install GSD file ............................43 Add the device to the Profinet network ....................44 Configure communication profile ......................46 IO-Link-Ports konfigurieren........................47 Configure the Profinet interface ......................48...
  • Page 43: Install Gsd File

    Install GSD file 22410 To represent the AL1103 in a field bus projection software (e.g. STEP 7), ifm provides a GSD file. The user can download the GSD file from the ifm website (→ the GSD file, all parameters, process data, and their valid value ranges are defined.
  • Page 44: Add The Device To The Profinet Network

    ► Open STEP-7 application "HW Config". > Program window shows the hardware structure of the project. ► Open hardware catalogue. ► Move the [AL1103] node via drag&drop from the hardware catalogue to the Profinet connection. > STEP 7 shows the device as Profinet bus participant.
  • Page 45 Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Configuration Add IO-Link ports ► Move the [8 Ports] node via drag&drop from the hardware catalogue to slot 1 of the AL1103. > Step 7 shows available IO-Link interfaces. ► Save the project.
  • Page 46: Configure Communication Profile

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Configuration > 8.4.3 Configure communication profile 22760 In order to configure the access rights to the device: Open device editor ► Open STEP-7 application "HW Konfig".
  • Page 47: Io-Link-Ports Konfigurieren

    The device editor shows the current configuration of the AL1103. Add Profinet module ► Open hardware catalogue. ► Draw the required Profinet module of the AL1103 from the hardware catalogue to the slot. > The device editor shows the slot with the selected Profinet module.
  • Page 48: Configure The Profinet Interface

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Configuration Parameters of the IO-Link Further information about the parameters of the Profinet modules: → ports (→ p. 69) ► Click on [Add] to save the changes.
  • Page 49: Profinet: Configure Io-Link Devices

    > Profinet: Configure IO-Link devices 18428 The AL1103 supports the configuration of the connected IO-Link devices out of the Profinet projection software. The configurable parameters depend on the corresponding IO-Link device. Information about the usable functions: → Profinet: Programmers' notes (→...
  • Page 50: Read And Write I&M Datasets

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Configuration > 8.6.1 Read and write I&M datasets 2261 Symbol / function Meaning Remarks block GET_IM_DATA / FB Function block for reading the I&M datasets of...
  • Page 51: Configure Io-Link Devices

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Configuration > 8.6.3 Configure IO-Link devices 1860 Symbol / function Description Remarks block IO_LINK_DEVICE / Acyclic access to the parameters of an IO-Link Input parameters: FB5001 device ...
  • Page 52: Operation

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Operation Operation Identify device ............................53 Read device information .........................53 Reboot the device ...........................56 Error detection and elimination .......................56 Firmware update .............................57 Exchange IO-Link device........................58 22368...
  • Page 53: Identify Device

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Operation > Identify device 22816 In the online mode, the user can identify the device using the status LEDs RDY, BF und SF ► Start LR DEVICE.
  • Page 54: Web Interface: Read Device And Diagnostic Information

    ID of the IO-Link device [Name] Article number of the IO-Link device  For ifm articles: This article number is stored along with a link to the produkt page on the ifm website. [Serial] Serial number of the IO-Link device...
  • Page 55: Lr Device: Read Device Information

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Operation > 9.2.2 LR DEVICE: Read device information 11614 To show information about the AL1103: ► Start LR DEVICE. ► Scan network for devices. > LR DEVICE shows recognised AL1103.
  • Page 56: Reboot The Device

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Operation > Reboot the device 12760 When restarting the device, all settings are kept. To restart the AL1103: ► Start LR DEVICE. ► Scan the network for devices.
  • Page 57: Firmware Update

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Operation > Firmware update 22425 The new firmware is installed via the device's web interface. If the firmware update is not successful, deactivate all connections to the Profinet PLC, LR SmartObserver and LR DEVICE and repeat the process.
  • Page 58: Exchange Io-Link Device

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Operation > Exchange IO-Link device 7775 To exchange an IO-Link device: Requirement: > IO-Link device is with factory settings. > IO-Link device supports IO-Link standard 1.1 or higher.
  • Page 59: Maintenance

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Maintenance Maintenance 21577 The operation of the unit is maintenance-free. ► Clean the surface of the unit when necessary. Do not use any caustic cleaning agents for this! ►...
  • Page 60: Factory Settings

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Factory settings Factory settings 22671 In the factory settings, the device has the following parameter settings: Parameters Factory setting [IP address] 0.0.0.0 [Subnet mask] 0.0.0.0 [IP gateway address] 0.0.0.0...
  • Page 61: Appendix

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Appendix Appendix Technical data ............................62 Profinet ..............................66 7156...
  • Page 62: Technical Data

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Appendix > 12.1 Technical data Application ..............................63 Electrical data ............................63 Inputs / outputs ............................63 Inputs ..............................63 Outputs ..............................63 Interfaces ..............................64 Operating conditions ..........................64 Approvals / tests .............................64 Mechanical data .............................65...
  • Page 63: Application

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Appendix > 12.1.1 Application 23710 Application Application Hygienic systems; I/O modules fpr field applications Daisy-chain function Communication interface > 12.1.2 Electrical data 22819 Electrical data Operating voltage 20...30 DC;...
  • Page 64: Interfaces

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Appendix 12.1.6 Interfaces 22822 Interfaces Communication interface Ethernet; IO-Link Communication interface IO-Link; TCP/IP; PROFINET IO Ethernet Transmission standard 10Base-T; 100Base-TX Transmission rate 10; 100 Protocol TCP/IP; PROFINET IO ...
  • Page 65: Mechanical Data

    Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Appendix > 12.1.9 Mechanical data 22825 Mechanical data Weight [g] Materials Housing: PA grey; socket: stainless steel (1.4404 / 316L) > 12.1.10 Accessories 23707 Accessories Accessories (supplied) Protective cap: 1 x M12, stainless steel E12542 >...
  • Page 66 Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Appendix > 12.2 Profinet Parameter data ............................67 Cyclic data ..............................71 Acyclic data ............................74 22433...
  • Page 67 Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Appendix > 12.2.1 Parameter data 1630 Slot Subslot Name Description Parameter of the IO-Link master Master Parameter data of the IO-Link master (→ (→ p. 68))
  • Page 68 Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Appendix > Parameter of the IO-Link master 22788 Parameter Description Possible values  [Access Rights] The access rights to the Profinet + Profinet and LR DEVICE have read...
  • Page 69 Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Appendix > Parameters of the IO-Link ports 22787 Parameter Description Possible values [Fail-safe mode] Behaviour in case the Profinet No Fail Safe deactivated connection is interrupted...
  • Page 70 Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Appendix Parameter Description Possible values  Type compatible V1.1 IO-Link device is compatible with device with Restore the V1.1 IO-Link standard  Verification whether it is an IO-Link...
  • Page 71 Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Appendix > 12.2.2 Cyclic data Profinet modules .............................72 PQI (Port Qualifier Information) ......................73 22429...
  • Page 72 Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Appendix > Profinet modules 22685 Module Description IO-Link 32 I/ 32 O + PQI 32 bytes input and output data and PQI IO-Link 16 I/ 16 O + PQI...
  • Page 73 Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Appendix > PQI (Port Qualifier Information) 22686 Port Qualifier Information (PQI) contains diagnostic information about the IO-Link port. In addition to the process data, the IO-Link master sends the PQI to the Profinet controller.
  • Page 74 Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Appendix > 12.2.3 Acyclic data 22427 > I&M datasets 22778 The AL1103 supports the following I&M datasets (I&M = Identification & Maintenance): > I&M0 (Slot 0)
  • Page 75 Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-05-31 Appendix > I&M0 (Slot 1) 22782 Variable Description Access* Size Vendor ID IO-Link ID of the manufacturer OrderID Order number of the device (numbers are separated by blanks)
  • Page 76 Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-10-27 Index Install GSD file ..................43 Index Interfaces ....................64 IO-Link ....................14 IO-Link circuits ..................19 IO-Link ports ..................19 Accessories ................... 65 IO-Link ports (Class A) ................24 Acyclic data ....................
  • Page 77 Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 69K (AL1103) 2017-10-27 Index Remarks....................26 Required background knowledge ............9 Reset IO-Link master to factory settings ..........39 Safety instructions ................... 8 Safety symbols on the device ..............10 Set device validation and data storage ..........