SMC Networks HRR012-A*-20 Series Operation Manual page 29

Hide thumbs Also See for HRR012-A*-20 Series:
Table of Contents

Advertisement

Class of signal
Display
Function
OFF
Without output
RUN
Run status signal
RMT
Remote status signal
External temperature
EXT.C
control signal
Signal for completion
RDY
of preparation (TEMP
READY)
TEMP OUT
T.OUT
(temperature is out of
the range) signal
Signal for operation
FLT
stop alarm
Signal for continuing
WRN
operation alarm
Maintenance status
MENT
signal
ALM
Alarm status signal
Pass through signal
SW
of contact input signal
ASEL
Alarm status signal
Maintenance status
M.SEL
signal
HRR Series
Table 2.6-2 Operation of contact output signal
Operation
N.O type
Normally, output signal is OFF (open)
N.C type
Normally, output signal is ON (close)
N.O type
When the product operates, signal turns on.
N.C type
When the product operates, signal turns off.
When the product becomes SERIAL REMOTE,
N.O type
signal turns on.
N.C type
When the product becomes LOCAL, signal turns off.
Signal is turned on by activating the external
N.O type
temperature control function.
Signal is turned off by activating the external
N.C type
temperature control function.
When the product becomes completion of preparation
N.O type
(TEMP READY), signal turns on.
When the product becomes completion of preparation
N.C type
(TEMP READY), signal turns off.
Signal is turned on when the temperature is out of the
N.O type
range (TEMP OUT).
Signal is turned off when the temperature is out of the
N.C type
range (TEMP OUT).
N.O type
When operation stop alarm occurs, signal turns on.
N.C type
When operation stop alarm occurs, signal turns off.
N.O type
When continuing operation alarm occurs,
signal turns on.
N.C type
When continuing operation alarm occurs,
signal turns off.
N.O type
The signal is turned on when the maintenance status
signal is generated.
N.C type
The signal is turned off when the maintenance status
signal is generated.
N.O type
When alarm occurs, signal turns on.
N.C type
When alarm occurs, signal turns off.
Outputs the signal which is input to
N.O type
the contact input signal.
Input signal is ON
Outputs the reverse of the signal which is
N.C type
input to the contact input signal.
Input signal is OFF
N.O type
The signal is turned ON when the
selected alarm goes off.
The signal is turned OFF when the selected alarm
N.C type
goes off.
The signal is turned on when the selected
N.O type
maintenance status signal is generated.
The signal is turned off when the selected
N.C type
maintenance status signal is generated.
Chapter 2 Contact input/output communication
Operation of contact output signal
Output signal is ON
Output signal is ON
HRX-OM-W004
2.6 Contact output signal
2-17