Taco SR501 Wiring Manual

Zone controls, switching relays/ with powerport options and expandable to 20 zones, zone valve controls/with powerport options and expandable to 20 zones, plug-in powerport cards, add-on power controls, fan controls
Table of Contents

Advertisement

TACO ZONE CONTROLS WIRING GUIDE
Switching Relays – Single Zone Wiring
Switching Relays – Oil Boiler Wiring Safety Notice
Switching Relays – NON EXP Connected Together with Priority
Switching Relays – EXP Connected Together with Priority
Switching Relays – Multiple Indirect Hot Water Heaters
Switching Relays – EXP Connected To Reset Controls (PC700, 702 & 705)
Zone Valve Controls – NON EXP Connected Together with Priority
Zone Valve Controls – EXP Connected Together with Priority
Zone Valve Controls – Connected To Reset Controls (PC700, 702 & 705)
Hydro Air Fan Controls (HAFC 101 & 201)
Specialty Thermostat and Zone Valve Wiring
Radiant Mixing Block
Low Water Cutoffs and Electric Water Feeders
Instruction Sheets
Cross Reference
Do it once.
Do it right.
© Taco Catalog No. 100-9.0
Pages
2 –
2
3 – 4
5 – 11
12 – 14
15 – 16
17 – 28
29 – 34
35 – 38
39 – 46
47 – 51
52 – 56
57 – 58
59 – 61
62 – 63
64 – 79
80 – 86
87 – 97
99 – 100
Effective Date: July 1, 2010
Supersedes Date: July 1, 2007
2
98

Advertisement

Table of Contents
loading

Summary of Contents for Taco SR501

  • Page 1 TACO ZONE CONTROLS WIRING GUIDE Pages Switching Relays – Single Zone Wiring 2 – Switching Relays – Oil Boiler Wiring Safety Notice 3 – 4 Switching Relays – NON EXP Connected Together with Priority 5 – 11 Switching Relays – EXP Connected Together with Priority 12 –...
  • Page 3 TACO Zone Control Product Information Switching Relays Product No. Description SR501 1 Zone Switching Relay SR501-845RP 1 Zone Switching Relay Replacement PC Board for Honeywell R845, RA89A, RA832 or Comparable Relay SR502 2 Zone Switching Relay with Priority SR503 3 Zone Switching Relay with Priority...
  • Page 5 NOTE: No tankless coil priority.
  • Page 6 (cont.) THERMOSTATS (HOT) (NEUTRAL) CIRCUIT THERMOSTAT BREAKER ZONE 4 PRIORITY SR 504 ZONE 1 ZONE 2 ZONE 3 ZONE 4 CUSTOMER FOUR ZONE SWITCHING RELAY EMERGENCY WITH OPTIONAL PRIORITY SWITCH HONEYWELL L8124 POWER OR EQUAL ZONE 1 ZONE 2 THERMAL ZONE 3 ZONE 4 FUSE...
  • Page 7 SR502/503 Switching Relay Controlling Another SR502/503 Switching Relay AQUASTAT ON DHW HEATER MASTER 24 VAC POWER PRIORITY ON VIA JUMPER SR 503 ZONE1 ZONE2 ZONE3 PLACEMENT THREE ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY FUSE 1 AMP POWER ZONE 1 ZONE 2 ZONE 3 N P ZC H X ZR...
  • Page 8 SR502/503 Switching Relay Controlling Another SR504/506 Switching Relay AQUASTAT ON DHW HEATER MASTER PRIORITY ON 24 VAC VIA JUMPER POWER PLACEMENT SR 503 ZONE1 ZONE2 ZONE3 THREE ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY FUSE 1 AMP POWER ZONE 1 ZONE 2 ZONE 3 N P ZC H X ZR...
  • Page 9 Two SR504/506 Switching Relays Connected Together AQUASTAT ON DHW HEATER ZONE 4 PRIORITY PRIORITY SR 504 ZONE 1 ZONE 2 ZONE 3 ZONE 4 FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4 120V RELAY 24 VAC POWER...
  • Page 10 Priority Zoning Circulator Controlling SR504/506 Switching Relay MASTER PRIORITY PRIORITY ZONING CIRCULATOR PRIORITY THERMOSTAT BOILER PRIORITY POWER IN PR-IN PR-OUT LIVE NEUT 120 VAC INPUT AQUASTAT ON DHW HEATER THERMOSTATS PRIORITY SLAVE ZONE 6 PRIORITY SR 506 ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6 SIX ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY POWER...
  • Page 14 SR501-EXP Switching Relay Controlling Another SR504/506 Switching Relay AQUASTAT ON DHW HEATER TO: "TT" ON BOILER TO: OPTIONAL ZONE VALVE OR iSeries MIXING VALVE MODE POWER MASTER RESET CONTROLS ZONE EXPANSION THERMOSTAT SWITCH VALVE NORMAL SLAVE FUSE SR 501-EXP 1 AMP...
  • Page 15 FUSE (7 AMP MAX)
  • Page 16 2 Expandable Switching Relays Connected Together SWITCH SETTINGS Master/Slave: Slave Reset/Normal: Normal Priority Zone: Off THERMOSTATS SLAVE SLAVE PLUG-IN CARDS ZONE 4 PRIORITY 1 2 3 4 MASTER POWER EXPANSION ZONE 1 ZONE 2 ZONE 3 ZONE 4 CONTROL INTERFACE SR504-EXP FOUR ZONE SWITCHING RELAY RESET NORMAL...
  • Page 19 PC700 Boiler Reset Control Connected to SR501-EXP Switching Relay OUTDOOR SENSOR SWITCH SETTINGS Master/Slave: Master Reset/Normal: Reset PC700 THERMOSTAT TO: "TT" ON BOILER ZONE BOIL CONTROL TO: OPTIONAL ZONE VALVE OR iSeries MIXING VALVE BOILER SENSOR MODE POWER CONTROLS RESET...
  • Page 20 SR501-EXP and PC700 Boiler Reset Control Connected to an Existing Switching Relay OUTDOOR SENSOR AQUASTAT ON DHW HEATER Note: If Zone Control comes on without a call for heat, reverse Reset Override input (1 & 2) wires on SR501-EXP. TO: "TT" ON BOILER...
  • Page 21 SR501-EXP and PC700 Boiler Reset Control Connected to an Existing Zone Valve Control OUTDOOR AQUASTAT ON SENSOR Note: If Zone Control comes on without a call for heat, DHW HEATER reverse Reset Override input (1 & 2) wires on SR501-EXP.
  • Page 22 SR501-EXP and PC700 Boiler Reset Control Connected to an Existing Tankless Coil Boiler – Zoning with Circulators OUTDOOR SENSOR THERMOSTATS EXISTING POWER ZONE CONTROLS CONTROL MODE RESET EXPANSION THERMOSTAT ZONE 4 SWITCH OVERRIDE RESET SR 504 PRIORITY PC700 ZONE1 ZONE2 ZONE3 ZONE4...
  • Page 26 PC700 Boiler Reset Control Connected to 2 EXP Switching Relays OUTDOOR SENSOR SWITCH SETTINGS Master/Slave: Master THERMOSTATS Reset/Normal: Reset Priority Zone: On or Off MASTER PC700 SLAVE PLUG-IN CARDS ZONE 4 PRIORITY 1 2 3 4 MASTER ZONE BOIL CONTROL POWER EXPANSION ZONE 1 ZONE 2 ZONE 3 ZONE 4...
  • Page 27 PC702 2–Stage Boiler Reset Control Connected to 2 EXP Switching Relays OUTDOOR SWITCH SETTINGS SENSOR Master/Slave: Master THERMOSTATS Reset/Normal: Normal Priority Zone: On or Off DEMAND MASTER PC702 SLAVE PLUG-IN CARDS ZONE 4 PRIORITY BOIL ZONE STAGE STAGE 1 2 3 4 MASTER CONTROL POWER...
  • Page 28 PC705 Variable Speed Pump Injection Control Connected to 2 EXP Switching Relays SWITCH SETTINGS Master/Slave: Master Reset/Normal: Reset THERMOSTATS Priority Zone: On or Off OUTDOOR MASTER GREEN/GROUND SENSOR SLAVE PLUG-IN CARDS ZONE 4 (SEE NOTE B PRIORITY ON PAGE 23) 1 2 3 4 MASTER EXPANSION...
  • Page 29 PC700 and PC705 Controls Connected to 2 EXP Switching Relays OUTDOOR SWITCH SETTINGS SENSOR Master/Slave: Master THERMOSTATS Reset/Normal: Reset Priority Zone: On or Off MASTER SLAVE PC700 PLUG-IN CARDS ZONE 4 PRIORITY 1 2 3 4 MASTER ZONE BOIL POWER EXPANSION CONTROL ZONE 1 ZONE 2 ZONE 3 ZONE 4...
  • Page 30 PC702 and PC705 Controls Connected to 2 EXP Switching Relays SWITCH SETTINGS OUTDOOR Master/Slave: Master SENSOR Reset/Normal: Normal THERMOSTATS Priority Zone: On or Off MASTER DEMAND SLAVE PLUG-IN CARDS ZONE 4 PRIORITY PC702 1 2 3 4 MASTER POWER EXPANSION ZONE 1 ZONE 2 ZONE 3 ZONE 4 CONTROL STAGE...
  • Page 31 FUSE (5 AMP MAX)
  • Page 32 FUSE (7 AMP MAX)
  • Page 33 FUSE (7 AMP MAX)
  • Page 34 FUSE (7 AMP MAX)
  • Page 35 FUSE (7 AMP MAX)
  • Page 36 JUMPER 3 & 4 3 & 4 SEE NOTE PRIORITY ZONE MOTOR SWITCH CONTACTS 2 WIRE ZONE VALVE TACO 4 WIRE ZONE VALVE (NO END SWITCH) 3 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING) AQUASTAT ON DHW HEATER THERMOSTAT THERMOSTAT...
  • Page 37 3 & 4 SEE NOTE 3 & 4 PRIORITY ZONE TO BOILER AQUASTAT RELAY MOTOR SWITCH BOILER TACO 2 WIRE ZONE VALVE 4 WIRE ZONE VALVE SYSTEM 3 WIRE ZONE VALVE (NO END SWITCH) (POWER OPEN, SELF CLOSING) PUMP 120 VAC INPUT SYSTEM PUMP AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS.
  • Page 38 3 & 4 AQUASTAT RELAY SEE NOTE 3 & 4 PRIORITY ZONE MOTOR SWITCH BOILER TACO 2 WIRE ZONE VALVE 4 WIRE ZONE VALVE 3 WIRE ZONE VALVE (NO END SWITCH) (POWER OPEN, SELF CLOSING) PUMP 120 VAC INPUT BOILER TURNS ON WHEN ANY ZONE VALVE OPENS.
  • Page 39 PRIORITY ZONE MOTOR SWITCH BOILER SYSTEM PUMP PUMP TACO 2 WIRE ZONE VALVE 4 WIRE ZONE VALVE 3 WIRE ZONE VALVE (NO END SWITCH) (POWER OPEN, SELF CLOSING) 120 VAC INPUT SYSTEM PUMP AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS.
  • Page 40 PRIORITY ZONE MOTOR SWITCH BOILER SYSTEM PUMP PUMP SECONDARY TACO 2 WIRE ZONE VALVE 4 WIRE ZONE VALVE PUMP 3 WIRE ZONE VALVE (NO END SWITCH) (POWER OPEN, SELF CLOSING) 120 VAC INPUT SYSTEM PUMP AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS.
  • Page 44 3 & 4 SEE NOTE AQUASTAT RELAY 3 & 4 PRIORITY ZONE MOTOR SWITCH BOILER TACO 2 WIRE ZONE VALVE 4 WIRE ZONE VALVE 3 WIRE ZONE VALVE (NO END SWITCH) (POWER OPEN, SELF CLOSING) SYSTEM CIRCULATOR CIRCULATOR SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS.
  • Page 45 3 & 4 SEE NOTE 3 & 4 PRIORITY ZONE MOTOR SWITCH SYSTEM TACO 2 WIRE ZONE VALVE 4 WIRE ZONE VALVE CIRCULATOR CIRCULATOR 3 WIRE ZONE VALVE (NO END SWITCH) (POWER OPEN, SELF CLOSING) SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS.
  • Page 46 CONTACTS 3 & 4 TO BOILER PRIORITY AQUASTAT RELAY ZONE MOTOR SWITCH BOILER TACO 2 WIRE ZONE VALVE 4 WIRE ZONE VALVE SYSTEM CIRCULATOR 3 WIRE ZONE VALVE (NO END SWITCH) (POWER OPEN, SELF CLOSING) (OPTIONAL LOCATION) SWITCH SETTINGS Master/Slave: Slave...
  • Page 47 3 & 4 SEE NOTE AQUASTAT RELAY 3 & 4 PRIORITY ZONE MOTOR SWITCH BOILER TACO 2 WIRE ZONE VALVE 4 WIRE ZONE VALVE 3 WIRE ZONE VALVE (NO END SWITCH) (POWER OPEN, SELF CLOSING) SYSTEM CIRCULATOR CIRCULATOR SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS.
  • Page 48 JUMPER 3 & 4 BOILER SEE NOTE 3 & 4 PRIORITY ZONE MOTOR SWITCH TACO 2 WIRE ZONE VALVE 4 WIRE ZONE VALVE SYSTEM (NO END SWITCH) 3 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING) CIRCULATOR CIRCULATOR SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS.
  • Page 49 HAFC101 with 1 Speed Air Handler THERMOSTAT To: Aquastat on Optional Power Wire Return Line of to Thermostat Hydro Coil that Requires 24VAC AQUASTAT THERMOSTAT Power On HAFC101 Call for Heat HYDRO AIR FAN CONTROL Fan, Cooling Fan, Heating BOILER AIR HANDLER X X C R Y LOW HIGH...
  • Page 50 HAFC101 with 2 Speed Air Handler THERMOSTAT To: Aquastat on Optional Power Wire Return Line of to Thermostat Hydro Coil that Requires 24VAC THERMOSTAT AQUASTAT Power On HAFC101 Call for Heat HYDRO AIR FAN CONTROL Fan, Cooling Fan, Heating BOILER AIR HANDLER X X C R Y LOW HIGH...
  • Page 51 HAFC201 with 1 Speed Air Handler To: Optional THERMOSTAT Aquastat on Return Line of Hydro Coil Optional Power Wire To: Optional Aquastat to Thermostat or Thermostat to sense that Requires 24VAC low ambient temperature WATER COIL FREEZE PR THERMOSTAT AQUASTATS Power On HAFC201 Call for Heat...
  • Page 52 HAFC201 with 2 Speed Air Handler To: Optional THERMOSTAT Aquastat on Return Line of Hydro Coil Optional Power Wire To: Optional Aquastat to Thermostat or Thermostat to sense that Requires 24VAC low ambient temperature WATER COIL FREEZE PR THERMOSTAT AQUASTATS Power On HAFC201 Call for Heat...
  • Page 54 ZC ZR 120 VOLT CIRCULATORS INPUT SWITCH FUSE 1 AMP 120 VAC INPUT JUMPER TO: "TT" ON BOILER BOILER 3 Wire Thermostat Connected to TACO Zone Valve Control THERMOSTAT THERMOSTAT THERMOSTAT WHITE 120 VAC 24 VAC INPUT BLACK T STAT 1...
  • Page 57 570 Zone Valve to Switching Relay THERMOSTAT 24 VAC TRANSFORMER 24 VAC POWER SR 503 ZONE1 ZONE2 ZONE3 THREE ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY FUSE 1 AMP POWER ZONE 1 ZONE 2 ZONE 3 N P ZC H X ZR ZONE1 ZONE2 ZONE3...
  • Page 58 FUSE (7 AMP MAX)
  • Page 59: Radiant Mixing Block

    Thermostat Circulator Radiant Mixing Block, Single Zone Boiler Operation Off-Enable On-Control Thermostat Back of Control (Dry Contact) Pump Outdoor ComSup Boil Out Heat Sensor Power Input Boiler Sensor Supply Sensor High Mass Boiler FOR ADDITIONAL WIRING DIAGRAMS, PLEASE SEE www.taco-hvac.com/wiringwizard...
  • Page 60 SWITCH 24 VAC ComSup Boil Out Heat POWER FUSE 1 AMP ZONE1 ZONE2 ZONE3 POWER 120 VOLT CIRCULATORS INPUT SWITCH 24 VAC POWER FUSE 1 AMP Power Input Circ. Supply Boiler Sensor Sensor FOR ADDITIONAL WIRING DIAGRAMS, PLEASE SEE www.taco-hvac.com/wiringwizard...
  • Page 61 Sensor Cord Boiler Operation Off-Enable On-Control Back of Control Thermostat (Relay or Mechanical Type) Pump ComSup Boil Out Heat Pressure Relief HEAT Tank SOURCE Supply Input from Output to Sensor Heat Source System FOR ADDITIONAL WIRING DIAGRAMS, PLEASE SEE www.taco-hvac.com/wiringwizard...
  • Page 62 ZONE2 Off-Enable On-Control Back of Control ZC H ZONE1 ZONE2 Power Pump Input ComSup Boil Out Heat Power Input Pressure Relief Tank Return Supply Input from Output to Sensor Sensor Heat Source System FOR ADDITIONAL WIRING DIAGRAMS, PLEASE SEE www.taco-hvac.com/wiringwizard...
  • Page 63: X-Pump Block

    Typical Radiant Floor to Water Heater Installation Domestic Cold Supply Supply X-PUMP BLOCK Relief Separator Valve Return ASSE 1017 Tempering Exp. Valve Tank RADIANT SYSTEM (Secondary Side Supply of the System) Check Valve Cold WATER HEATER WARNING! A pressure relief valve and expansion tank must be installed on the secondary side in addition to any pressure relief valve and expansion tank which is installed on primary side of system.
  • Page 64: Iseries Mixing Valves

    SR501 1 Z ONE SWIT CHING RELAY 24 VAC SENSOR BOILER POWER COMMON POWER INPUT SUPPLY GREEN OUTDOOR 24 Volt Transformer 120 VAC SENSOR INPUT ERROR Power Input iSeries-R Supply Sensor Boiler Sensor FOR ADDITIONAL WIRING DIAGRAMS, PLEASE SEE www.taco-hvac.com/wiringwizard...
  • Page 65 THREE ZONE ZONE VALVE CONTROL SENSOR ERROR ZONE 1 ZONE 2 ZONE 3 E ND SWITCH 1 2 3 4 1 2 3 4 1 2 3 4 Supply iSeries-R Sensor Boiler Sensor FOR ADDITIONAL WIRING DIAGRAMS, PLEASE SEE www.taco-hvac.com/wiringwizard...
  • Page 66 Wiring for Boilers with Honeywell Control Center Model R8285 or Equivalent TACO LTR0243T-1 FACTORY WIRING FEMALE CONNECTOR MALE CONNECTOR GROUND CONNECTION Alternate TACO LTR0243T-1 Wiring 24 VAC CLASS 2 TRANSFORMER LIMIT CONTROLS 24 VAC VALVE COMMON...
  • Page 67 Wiring Boilers with a United Technologies Integrated Control Module and a Taco LTR0243U-1 INTEGRATED BOILER CONTROL MALE CONNECTOR FEMALE CONNECTOR FACTORY WIRING BOILER MODULE WIRING HARNESS Wiring Boilers with a United Technologies Ucontrol or other Integrated Control Modules which accept a 4-pin harness and a Taco LTR0243L-1...
  • Page 68 Wiring Taco LN and LTA-2 Series Low Water Cutoffs Using Burner Circuit Power Source *Factory Installed NOTE: For 24 VAC models, LNA024xx and LTA0243S-2, 24 VAC to be supplied by an EXTERNAL Class 2 power source to terminals H and N. For 120 VAC models, LNA120xx and LTA1203S-2, 120 VAC is supplied by an external circuit to terminals H and N.
  • Page 69 Wiring Taco LT Series (1st generation, -1) Low Water Cutoffs Using Burner Circuit Power Source *Factory Installed NOTE: For 24 VAC models, LTx024xx-1, 24 VAC to be supplied by an EXTERNAL Class 2 power source to terminals H and N.
  • Page 70 For 120 VAC models, LFx120xx, 120 VAC is supplied by an external circuit to terminals H and N. Wiring Taco LF Series Low Water Cutoffs Using Power Source Other Than Burner Circuit NOTE: For 24 VAC models, LFx024xx, 24 VAC to be supplied by an EXTERNAL Class 2 power source to terminals H and N.
  • Page 71 Taco Low Water Cutoff Replacement Guide Taco McDonnell & Miller Hydrolevel Honeywell PS-801-120 PSE-801-120 LFA1203S-1 RW700A1031 PS-800-120 CG450 LTA1203N-1 RW700A1056 PS-850-120 CGT450 LTA1203S-1 RW700A1080 OEM170TD 900C PS-801-M-120 PS-851-M-120 LFM1203S-1 PS-851-SP-M-120 550SV RW700B1054 LTM1203N-1 PS-850-M-120 RW700B1039 LTM1203S-1 900M OEM170MC RW700B1021 901M...
  • Page 72 Taco LF Series 120 Volt LWCO Competitive Wiring Cross Reference 120 VAC Models with 120 VAC Burner Circuits McDONNELL & MILLER PS-801/851-120 w/Red & Amber LEDs TACO LFx120x Series 750 BURNER 120 VAC FACTORY BURNER CIRCUIT 120 VAC CIRCUIT INSTALLED...
  • Page 73 Taco LF Series 24 Volt LWCO Competitive Wiring Cross Reference 24 VAC Models with 24 VAC Burner Circuits TACO LFx024x BURNER 24 VAC FACTORY CIRCUIT CIRCUIT INSTALLED JUMPER NEUTRAL McDONNELL & MILLER HYDROLEVEL 400, 500, 600 & 700 PS-802/852-24 BURNER...
  • Page 74 Taco LTA-2 Series 120 Volt LWCO Competitive Wiring Cross Reference 120 VAC Models with 120 VAC Burner Circuits McDONNELL & MILLER RB-120 TACO LTA1203S-2 COM NC BURNER BURNER 120 VAC 120 VAC FACTORY CIRCUIT CIRCUIT CIRCUIT CIRCUIT INSTALLED JUMPER NEUTRAL NEUTRAL McDONNELL &...
  • Page 75 Taco LTR and LTA-2 Series 24 Volt LWCO Competitive Wiring Cross Reference 24 VAC Models with 24 VAC Burner Circuits McDONNELL & MILLER TACO LTA0243S-2 RB-24E White Yellow Yellow COM NC Wire Wire Wire Wire BURNER BURNER 24 VAC 24 VAC...
  • Page 76 Wiring Taco LF Series Low Water Cutoffs to Taco Electric Water Feeder with the Same Voltages EWF Standard Wiring T a c o L F x 1 2 0 x / L F x 0 2 4 x H O T...
  • Page 77 Wiring Taco 24VAC Electric Water Feeder to Taco LF Series 24VAC Low Water Cutoff or 24VAC McDonnell & Miller or Hydrolevel Low Water Cutoffs M c D o n n e l l & M il l e r P S -8 0 2 /8 5 2 -2 4 H yd ro le v e l 4 0 0 , 5 0 0 , 6 0 0 , &...
  • Page 78 Wiring TACO LTA-2 or LF Series 24VAC Low Water Cutoff to McDonnell & Miller Series WF2 Uni-Match Electric Water Feeder SWITCH POSITION #2 UNI-MATCH WATER FEEDER M&M MODEL WF2-U-24 24VAC Note on switch position: SUPPLY 50/60 Hz Switch setting 1 (M&M), the feed cycle repeats BURNER indefinitely.
  • Page 79 Wiring TACO LF Series 24VAC Low Water Cutoff to Hydrolevel VXT-24 Water Feeder (Non-Display Model) Set Safgard as desired. SAFGARD VXT-24 WATER FEEDER WHITE BLACK 24VAC SUPPLY 50/60 Hz BURNER Remove jumper between H and COM if using power source other than burner circuit NC NO or when using mixed voltages.
  • Page 80 Wiring TACO LTA-2 or LF Series 24VAC Low Water Cutoff to Hydrolevel VXT-24 Programmable Water Feeder (Model with Display) Set Safgard as desired. SAFGARD VRTX-24 WATER FEEDER WHITE BLACK 24VAC SUPPLY 50/60 Hz BURNER Remove jumper between H and COM if using...
  • Page 82: Aquastat Wiring

    Aquastat Wiring (HOT) (NEUTRAL) 120 VAC INPUT TACO ZONE CONTROL END SWITCH CIRCULATOR HONEYWELL L8124A & C OR EQUAL ON BOILER (IF ATTACHED) LINE VOLTAGE OIL BURNER RELAY OR GAS VALVE MILLI-VOLTAGE GAS VALVE TACO ZONE CONTROL END SWITCH CIRCULATOR...
  • Page 83 Aquastat Wiring TACO ZONE CONTROL END SWITCH LINE VOLTAGE OIL BURNER RELAY OR GAS VALVE 120 VAC INPUT CIRCULATOR HONEYWELL L8124G & L OR EQUAL ON BOILER (HOT) (NEUTRAL) (IF ATTACHED) (HOT) (NEUTRAL) 120 VAC INPUT TACO ZONE CONTROL END SWITCH...
  • Page 84 Aquastat Wiring TACO ZONE CONTROL END SWITCH CIRCULATOR ON BOILER (IF ATTACHED) 120 VAC INPUT (HOT) (NEUTRAL) HONEYWELL L8148E OR EQUAL LOW VOLTAGE GAS VALVE TACO ZONE CONTROL END SWITCH CIRCULATOR ON BOILER (IF ATTACHED) MILLI- VOLTAGE VALVE 120 VAC...
  • Page 85 Aquastat Wiring 120 VAC (HOT) (NEUTRAL) INPUT TACO SWITCHING RELAY END SWITCH THERMOSTAT (IF INDEPENDENT ZONE) CIRCULATOR ON BOILER HONEYWELL L8124A & C OR EQUAL LINE VOLTAGE (IF ATTACHED) OIL BURNER RELAY OR GAS VALVE THERMOSTAT TACO (IF INDEPENDENT ZONE)
  • Page 86 Aquastat Wiring (HOT) (NEUTRAL) 120 VAC INPUT TACO SWITCHING RELAY END SWITCH THERMOSTAT (IF INDEPENDENT ZONE) L6006 LIMIT CONTROLER LINE VOLTAGE CIRCULATOR OIL BURNER RELAY HONEYWELL L8148A OR EQUAL ON BOILER OR GAS VALVE (IF ATTACHED) (HOT) (NEUTRAL) 120 VAC...
  • Page 87 Wiring for Boilers with Honeywell Aquastat Model L8124E or Equivalent FACTORY WIRING TACO LTR0243T-1 (unplug from B1 terminal) CIRCULATOR HONEYWELL ON BOILER L8124E MALE (IF ATTACHED) CONNECTOR (HOT) (NEUTRAL) FEMALE 120 VAC CONNECTOR INPUT NOTE: The green wire must be connected to a ground source electrically common to the boiler ground.
  • Page 88 Aquastat Wiring to 24VAC Low Water Cutoff TACO LNA024 or LTA024-2 THERMOSTAT COM NC NO HONEYWELL L8148E CIRCULATOR ON BOILER (IF ATTACHED) SPILL SWITCH (HOT) (NEUTRAL) 120 VAC INPUT LOW VOLTAGE GAS VALVE Aquastat Wiring to 120VAC Low Water Cutoff...
  • Page 89: Instruction Sheets

    Printed in USA TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360. Copyright 2005 TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436. TACO, Inc. Visit our web site at: http://www.taco-hvac.com...
  • Page 90 Printed in USA TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360. Copyright 2005 TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436. TACO, Inc. Visit our web site at: http://www.taco-hvac.com...
  • Page 91 Priority Circulators, Thermostats, and the “00” family of circulators with the Simplified Wiring advanced features of the Taco Zone Controls to achieve total system Fully Enclosed Snap-Out Relays integration. No matter the application, Taco now provides the products Compact Design...
  • Page 92 Switchable Priority Circulators, Thermostats, and the “00” family of circulators with the Simplified Wiring advanced features of the Taco Zone Controls to achieve total system Fully Enclosed Snap-Out Relays integration. No matter the application, Taco now provides the products Compact Design...
  • Page 93 Printed in USA TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360. Copyright 2005 TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436. TACO, Inc. Visit our web site at: http://www.taco-hvac.com...
  • Page 94 Printed in USA TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360. Copyright 2005 TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436. TACO, Inc. Visit our web site at: http://www.taco-hvac.com...
  • Page 95 Printed in USA TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360. Copyright 2000 TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436. TACO, Inc. Visit our web site at: http://www.taco-hvac.com...
  • Page 96 Printed in USA TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360. Copyright 2000 TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436. TACO, Inc. Visit our web site at: http://www.taco-hvac.com...
  • Page 97 When the zone valve is fully open, the red light goes on and ener- tors with the advanced features of the Taco Zone Controls to achieve gizes the end switch relays. The green light should always be on, indi- total system integration.
  • Page 98 TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360. Copyright 1999 Copyright 1999 TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436. TACO, Inc. TACO, Inc. Visit our web site at: http://www.taco-hvac.com...
  • Page 99 Installation: The PC610 can be installed in any unoccupied PowerPort terminal located on the Taco Expandable (-EXP) Control(s). Do not remove the shunt between pins 9 & 10 on the Expandable Switching Relay unless a PC600 is also installed. Align the connector on the base of the priority protection card with the PowerPort terminal on the Expandable Switching Relay and push until the two mate.
  • Page 100: Standard Terms And Definitions

    Standard Terms and Definitions Switching Relay: Transformer and relay in one box, which allows a low voltage thermostat to control a line voltage load (circulator), with an isolated end switch that can energize the boiler. Zone Valve Control: Transformer and relay in one box, which allows a low voltage thermostat to control a low voltage zone valve, with an isolated end switch that can energize the boiler and/or circulators.
  • Page 104 TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360. Copyright 2010 TACO (Canada), Ltd., 8450 Lawson Road, Unit #3, Milton, Ontario L9T 0J8. Telephone: 905/564-9422. FAX: 905/564-9436. TACO, Inc. Visit our web site at: http://www.taco-hvac.com...