Instruction Sheet
102-145
®
i Series - Outdoor Reset (iSeries-R)
2-Way and 3-Way i Series Mixing Valves
SUPERSEDES: New
EFFECTIVE: August 1, 2003
Plant ID# 001-1025
The iSeries-R is a microprocessor-based valve designed to regulate the supply water temperature to a heating system by modulating
the position of an iSeries Mixing Valve. The iSeries-R operates the valve to provide outdoor reset to the heating system. A boiler sensor
installed on the return line to the boiler is used to protect the boiler against flue gas condensation.
Outdoor Reset
In order to properly control a hot water heating system, the heat supplied to the build-
ing must equal the heat lost by the building.
• The heat supplied to the building is directly proportional to the temperature of the
water and the surface area of the heating element. The higher the temperature of the
water flowing through the heating terminal, the higher the heat output.
• The heat lost from a building is dependent on the outdoor temperature. As the out-
door temperature drops, the building heat loss increases.
These two facts lead to the concept of outdoor reset which increases the supply
water temperature as the outdoor temperature drops. Using this approach, the heat
lost from the building is matched by the heat provided by the terminal units, therefore
providing more comfort and energy savings.
Reset Ratio
The Reset Ratio sets the relationship between outdoor temperature and supply
water temperature. It determines the amount the supply water temperature is raised
for every 1 degree outdoor temperature drop. For example, if a Reset Ratio of 1.2
is selected, the supply water temperature is increased by 1.2 degrees of every 1
degree of outdoor temperature drop.
2-Way / 3-Way Mixing
An iSeries Mixing Valve may be used to mix the hot boiler water temperature with the cooler return water temperature from the system
loop. The position of the iSeries Mixing Valve is modulated in order to inject different rates of hot water into the cool system return water.
This allows for virtually any water temperature to be supplied to the heating system. When deciding between a 2-way or 3-way valve,
maximum flow rates must be considered. See the charts on page 2 before selecting style of valve / piping.
Most boilers cannot operate at low temperatures, therefore the iSeries-R can be modulated back in order to prevent the boiler from
operating at cold temperatures, by installing the boiler return sensor.
1

Advertisement

Table of Contents
loading

Summary of Contents for Taco i Series

  • Page 1 Instruction Sheet 102-145 ® i Series - Outdoor Reset (iSeries-R) 2-Way and 3-Way i Series Mixing Valves SUPERSEDES: New EFFECTIVE: August 1, 2003 Plant ID# 001-1025 The iSeries-R is a microprocessor-based valve designed to regulate the supply water temperature to a heating system by modulating the position of an iSeries Mixing Valve.
  • Page 2 Whenever the iSeries-R is powered up, the LED turns on and the control starts operation. The power to the iSeries-R may be switched through an end switch (e.g. Taco ZVC/SR style zone control) or a thermostat for intermittent operation, or the power source may be...
  • Page 3: Reset Ratio

    Reset Ratio Once the iSeries-R is powered up, it provides outdoor reset at the supply sensor location. The iSeries-R targets a supply temperature based on the outdoor temperature measured and the Reset Ratio dial setting. The Reset Ratio is set using the following formula: Design Supply Temperature - 72°F Reset Ratio = ture...
  • Page 4 Powering the Control For intermittent operation, connect one side of the end switch (e.g. Taco ZVC/SR series zone control) or thermostat to an external 24 V (ac) trans- former. Connect the other side of the zone control’s end switch to the R ter- minal on the iSeries-R.
  • Page 5: Troubleshooting

    In order to prevent heat transmitted through the wall from affecting the sensor reading, it may be necessary to install an insulating barrier behind the enclosure. The sensor should be mounted on a wall which best represents the heat load on the building (a northern wall for most buildings and a southern facing wall for buildings with large south facing glass areas).
  • Page 6: Product Specifications

    Product Specifications Maximum Operating Pressure: 300 PSI (2,100 kPa) Maximum Shutoff Pressure: 125 PSI (875 kPa) Fluid Temperature Range: 20º to 240ºF, (-7º to 115ºC) @ 135ºF (57ºC) ambient Service: Closed systems Hot and Chilled Water, up to 50% Glycol Seat Leakage: Drop-Tight Close-Off Electrical Rating:...
  • Page 7: Ordering Information

    Ordering Information Replacement Parts Part # Description 9300-2044RP Strap-on Sensor 9300-2052RP Outdoor Sensor iT024Q6A1 Outdoor Reset Actuator iU024Q6A1 Setpoint Actuator Notes...
  • Page 8: Limited Warranty Statement

    If in doubt as to whether a particular substance is suitable for use with a Taco product or part, or for any application restrictions, consult the applicable Taco instruction sheets or contact Taco at [401-942-8000].

Table of Contents