Instruction Sheet - Zvc404 & Zvc406 Zone Valve Control - Taco SR501 Wiring Manual

Zone controls, switching relays/ with powerport options and expandable to 20 zones, zone valve controls/with powerport options and expandable to 20 zones, plug-in powerport cards, add-on power controls, fan controls
Table of Contents

Advertisement

Wiring
Diagram
WHITE
120 VAC
INPUT
BLACK
WHITE
120 VAC
INPUT
BLACK
Installation of
Optional System
and/or DHW Circulator
MAIN
EXTRA
N/O COM N/C
END
END
SWITCH
SWITCH
T
SYSTEM CIRCULATOR
BOILER
T
DHW CIRCULATOR
120 VAC
Operation/External Diagnostics: When any thermostat
calls for heat, the appropriate zone valve is energized and the
yellow light goes on. When the zone valve is fully open, the
red light goes on and energizes the end switch relay. The green
light should always be on, indicating that power is connected.
Priority Operation: When zone 6 is switched to the priority
setting and is actuated, all other zones will stop operation until
zone 6 is satisfied. When zone 6 is not switched to priority, all
zones will operate independently. Note: When a circulator is
used on the priority zone instead of a zone valve, jumper 3 and
4 of the priority zone.
Mode Operation: When the mode switch is set to NORMAL,
the end switch relay will be energized if any zone is in opera-
tion. When the switch is set to RESET, the end switch relay
will only be energized if priority zone is in operation.
The Taco Connection: Combine the reliability of the Taco
Zone Valves, Priority Zoning Circulators, Thermostats, and the
"00" family of circulators with the advanced features of the
Taco Zone Controls to achieve total system integration. No
matter the application, Taco now provides the products to
maximize system performance while simplifying both instal-
lation and service.
Do it Once. Do it Right.
TACO, INC., 1160 Cranston Street, Cranston, RI 02920
TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3.
Visit our web site at: http://www.taco-hvac.com
94
ZVC404 & ZVC406 Zone Valve Control
THERMOSTAT
24 VAC
MODE
NORMAL RESET
24 VAC
MAIN
EXTRA
N/O COM
N/C
END
END
ZONE 6 RELAY
SWITCH
SWITCH
T
T
TO CIRCULATOR
OR BOILER
AQUASTAT RELAY
DRY
CONTACTS
2 WIRE ZONE VALVE
(NO END SWITCH)
(See Note)
NEUTRAL
HOT
Telephone: (401) 942-8000
Instruction Sheet
THERMOSTAT
24 VAC
T T
T T
T T
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZVC 406
SIX ZONE ZONE VALVE CONTROL
WITH OPTIONAL PRIORITY
ZONE 1
ZONE 2
ZONE 3
1 2 3 4
1 2 3 4
1 2 3 4
JUMPER
3 & 4
1
2
3
TACO
3 WIRE ZONE VALVE
Specifications:
PRODUCT
NUMBER
TRANSFORMER
NUMBER
OF ZONES
VOLTAGE
ZVC404
4 with Priority
120 VAC Input
ZVC406
6 with Priority
120 VAC Input
All Zone Valve Controls are relay type DPDT and have a single phase motor rating per zone of
1
hp (5A) @ 120 VAC.
6
Features: External Indicator Lights
Switchable Priority
Simplified Wiring
Works with 2, 3, or 4-Wire Zone Valves
Compact Design
Fuse Protected
100% Factory Tested
Isolated End Switch
Extra Set of Dry Contacts
Contractor Friendly PC Board Layout
Universal Thermostat Compatibility
UL Approved
Sturdy Screw Connections
Extended 3 Year Warranty
Made in the USA
Warning: Wiring connections must be made in accordance with all applicable electrical codes. Use copper
wire only. Failure to follow this instruction can result in personal injury or death and/or property damage.
10-18 gauge wire recommended for 120 VAC connections with 9 in.lbs. max torque, 12-22 gauge wire for
thermostat connections with 9 in.lbs. max torque, and 12-22 gauge wire for 24 VAC source with 5 in.lbs.
max torque.
FAX: (401) 942-2360.
Telephone: 905/564-9422.
THERMOSTAT
ZONE 6 PRIORITY
OFF
ON
T T
T T
T T
ZONE 5
ZONE 6
ZONE 4
ZONE 5
ZONE 6
1 2 3 4
1 2 3 4
1 2 3 4
JUMPER
3 & 4
PRIORITY
ZONE
MOTOR
END
SWITCH
4 WIRE ZONE VALVE
(POWER OPEN, SELF CLOSING)
MAX OUTPUT
DIMENSIONS OF ENCLOSURE
AT 24 VAC
WIDTH
1
40 VA
10
3
80 VA
11
FAX: 905/564-9436.
INDIRECT
WATER HEATER
AQUASTAT
OR THERMOSTAT
T STAT 1
VALVE 1
T STAT 2
VALVE 2
T STAT 3
VALVE 3
T STAT 4
VALVE 4
T STAT 5
VALVE 5
T STAT 6
VALVE 6
POWER
SEE NOTE
HEIGHT
DEPTH
3
3
"
6
"
2
"
4
4
4
1
"
7
"
3"
4
2
Printed in USA
Copyright 2000
TACO, Inc.