Instruction Sheet - Pc600 Post Purge Timer Plug-In Powerport Card; Pc605 Priority Protection Plug-In Powerport Card; Pc610 Pump Exercise And Timer Plug-In Powerport Card - Taco SR501 Wiring Manual

Zone controls, switching relays/ with powerport options and expandable to 20 zones, zone valve controls/with powerport options and expandable to 20 zones, plug-in powerport cards, add-on power controls, fan controls
Table of Contents

Advertisement

SUPERSEDES: August 1, 1997
Plant ID No. 9300-867
Operation:
Once the priority zone is satisfied, the PC600 maintains power to the circulator, but does not fire the boiler. The circulator purges excess heat into the priority zone,
minimizing standby loss during warm weather months and optimizing boiler operation when used with a boiler reset control. Power can be maintained to the circu-
lator from a minimum of 10 seconds to a maximum of 420 seconds. The power LED light is energized when the priority zone or the post purge card is in operation.
Installation:
The PC600 can be installed in any one of the PowerPort terminals located on the Taco Expandable (-EXP) Control(s). Remove the shunt/jumper between pins 9
& 10 on the PowerPort terminal before installing the PC600. Align the connector on the base of the post purge card with the PowerPort terminal on the Expandable
Control and push until the two mate.
XX Terminals (Optional):
The XX terminals on the post purge card can be wired to TT on the boiler to fire only when the priority zone is calling for heat. If using a boiler with an internal
reset control, wire the XX terminals in parallel with the TT connections of the internal reset control.
Do it Once. Do it Right.
TACO, INC., 1160 Cranston Street, Cranston, RI 02920
TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3.
SUPERSEDES: MAY 1, 1998
PLANT ID NO. 9300-1012
Operation:
The PC605 Priority Protection Plug-In Card is a solid state control that helps prevent freeze-ups in the event of a priority zone failure. If the priority zone calls for heat
continuously for more than one hour, power is returned to the space heating (non-priority) zones, allowing all zones to function independently. Once the priority zone is
satisfied, the PC605's auto-reset is activated and the priority zone is again allowed to have priority for up to one hour the next time it calls. The one hour time frame is
not adjustable. The red LED light is energized only when the Priority Protection Card is operating in priority override mode.
Installation:
The PC605 can be installed in any unoccupied PowerPort terminal located on the Taco Expandable (-EXP) Control(s). Do not remove the shunt between pins 9 &
10 on the Expandable Control unless a PC600 is also installed. Align the connector on the base of the priority protection card with the PowerPort terminal on the
Expandable Control and push until the two mate. The PC605 can be used in conjunction with any other Taco PC style PowerPort Cards or Add-on Controls.
Do it Once. Do it Right.
TACO, INC., 1160 Cranston Street, Cranston, RI 02920
TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3.
SUPERSEDES: May 31, 1998
Plant ID No. 9300-1025
Operation:
The PC610 Pump Exercise and Timer Plug-In Card is a solid state universal timer designed to cycle all the pumps that are attached to the Expandable Control(s)
at selected time intervals. This minimizes seasonal start-up problems generally associated with harsh water conditions. The control can be configured to reduce
the chance of freeze-ups by cycling the pumps more often during cold weather months. Bacteria can be minimized in heating systems that utilize domestic hot
water heaters as their heat source by systematically circulating the water.
Installation:
The PC610 can be installed in any unoccupied PowerPort terminal located on the Taco Expandable (-EXP) Control(s). Do not remove the shunt between pins 9 & 10 on
the Expandable Switching Relay unless a PC600 is also installed. Align the connector on the base of the priority protection card with the PowerPort terminal on the
Expandable Switching Relay and push until the two mate. The PC610 can be used in conjunction with any other Taco PC style PowerPort Cards or Add-on Controls.
Typical Settings:
Application
Pump Exercise
Bacteria Minimization
Freeze Protection
Do it Once. Do it Right.
TACO, INC., 1160 Cranston Street, Cranston, RI 02920
TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3.
Instruction Sheet
PC600 Post Purge Timer Plug-In PowerPort Card
Telephone: (401) 942-8000
Instruction Sheet

PC605 Priority Protection Plug-In PowerPort Card

Telephone: (401) 942-8000
Instruction Sheet

PC610 Pump Exercise and Timer Plug-In PowerPort Card

On Time
Off Time
30 sec.
2 weeks
4 min.
12 hours
4 min.
1 hour
Telephone: (401) 942-8000
FAX: (401) 942-2360.
Telephone: 905/564-9422.
FAX: 905/564-9436.
FAX: (401) 942-2360.
Telephone: 905/564-9422.
FAX: 905/564-9436.
FAX: (401) 942-2360.
Telephone: 905/564-9422.
FAX: 905/564-9436.
102-094
EFFECTIVE: May 1, 2000
Printed in USA
Copyright 2000
TACO, Inc.
102-095
EFFECTIVE: MAY 1, 2000
Printed in USA
Copyright 2000
TACO, Inc.
102-096
EFFECTIVE: May 1, 2000
Printed in USA
Copyright 2000
TACO, Inc.
97