SR501-EXP and PC700 Boiler Reset Control Connected to an Existing
OUTDOOR
SENSOR
PC700
ZONE
BOIL
OUT
CONTROL
SEN
SEN
BOILER SENSOR
TO: "ZR" ON BOILER CONTROL
TO: "ZC" ON BOILER CONTROL
BOILER
Boiler and Zone Control(s) need to be on same power supply (same circuit breaker).
SR501-EXP and PC700 Boiler Reset Control Connected to an Existing
OUTDOOR
SENSOR
MASTER
PC700
ZONE
BOIL
OUT
CONTROL
SEN
SEN
FUSE
1 AMP
BOILER SENSOR
TO: "ZR" ON BOILER CONTROL
TO: "ZC" ON BOILER CONTROL
BOILER
Boiler and Zone Control(s) need to be on same power supply (same circuit breaker).
20
Tankless Coil Boiler – Zoning with Circulators
POWER
CONTROLS
END
EXPANSION
THERMOSTAT
SWITCH
OVERRIDE
X
X 1
2
3
4
T/R
T/W
COM
K1-A
MASTER
SR 501-EXP
FUSE
1 AMP
SLAVE
K1
FUSE
5 AMP
K1-B
N
H
ZC ZR
POWER
120VAC
120VAC
INPUT
INPUT
OUTPUT
OUTPUT
JUMPER
Tankless Coil Boiler – Zoning with Zone Valves
POWER
CONTROLS
MODE
END
RESET
EXPANSION
THERMOSTAT
SWITCH
OVERRIDE
RESET
X
X 1
2
3
4
1
2
T/R
T/W
COM
K1-A
MASTER
SR 501-EXP
NORMAL
SLAVE
K1
K2
FUSE
5 AMP
K1-B
K2-A
K2-A
N
H
ZC ZR
H
H
POWER
120VAC
120VAC
CIRC
PRIORITY
INPUT
INPUT
OUTPUT
OUTPUT
OUTPUT
JUMPER
EXISTING
ZONE
CONTROL
MODE
RESET
RESET
1
2
NORMAL
POWER
K2
T STAT
K2-A
K2-A
H
H
CIRC
PRIORITY
OUTPUT
PRIMARY
SYSTEM
CIRCULATOR
(Optional)
WHITE
EXISTING
120 VAC
24
INPUT
VAC
ZONE
BLACK
CONTROL
NORMAL RESET
POWER IN
POWER
T STAT
MAIN
EXTRA
N/O COM N/C
END
END
SWITCH
SWITCH
PRIMARY
SYSTEM
CIRCULATOR
(Optional)
T
SR 504
ZONE1 ZONE2 ZONE3 ZONE4
FOUR ZONE SWITCHING RELAY
WITH OPTIONAL PRIORITY
120V RELAY
X
X
ZONE1 ZONE2 ZONE3 ZONE4
ZC ZR
END
120 VOLT CIRCULATORS
SWITCH
FUSE 1 AMP
REMOVE
JUMPER
THERMOSTATS
T
T
24 VAC
MODE
T T
T T
ZONE 1
ZONE 2
ZONE 3
ZVC 404
FOUR ZONE ZONE VALVE CONTROL
WITH OPTIONAL PRIORITY
ZONE 1
ZONE 2
ZONE 3
ZONE 4 RELAY
1 2 3 4
1 2 3 4
1 2 3 4
JUMPER
3 & 4
1
MOTOR
2
3
2 WIRE ZONE VALVE
TACO
4 WIRE ZONE VALVE
(NO END SWITCH)
3 WIRE ZONE VALVE
(POWER OPEN,
SELF CLOSING)
ZONE VALVE SYSTEM
CIRCULATOR
THERMOSTATS
ZONE 4
PRIORITY
ON
OFF
POWER
ZONE 1
ZONE 2
ZONE 3
ZONE 4
POWER
INPUT
120 VAC
INPUT
H
N
T
SLAVE
ZONE 4
PRIORITY
OFF
T T
T T
ON
T STAT 1
ZONE 4
VALVE 1
T STAT 2
VALVE 2
T STAT 3
VALVE 3
T STAT 4
VALVE 4
POWER
ZONE 4
1 2 3 4
JUMPER
3 & 4
SEE NOTE
PRIORITY
ZONE
END
SWITCH
Note: When a circulator is used on the
priority zone instead of a zone valve,
jumper 3 and 4 of the priority zone.
H
120 VAC
INPUT
N